Vermont Casting DVT38S2 Final Finishing, Gas Specifications, Gas Inlet and Manifold Pressures

Page 7

������

�������

������

�������FP1362

Fig. 7 Valve box framing.

If marble, tile or any other noncombustible decora- tive face finish material is desired, a 3” (76mm) wide noncombustible board (recommended Dura-Rock) is to be nailed to the nailing flanges on both sides of the unit. Also, 12” (305mm) of noncombustible board is to be nailed to the front face of the U-chan- nel and the top framing member above the standoff.

Combustible material can then be brought to the outside edges of the noncombustible board installed earlier. Any noncombustible decorative face finish could be brought to the sides and top of the unit and can cover the framing and sheet rock. If a decora- tive facing is not desired, then the noncombustible boards must be double thickness and brought flush with the face of the unit.

Final Finishing

Noncombustible materials such as brick or tile may be brought to the edges of the face of the appliance.

Gas Specifications

 

 

GAS

MAX.

MIN.

 

 

INPUT

INPUT

MODEL

FUEL

CONTROL

B.T.U.H

B.T.U.H.

DVT38S2RN

Natural Gas

Millivolt

56,000

38,000

DVT38S2RP

Propane

Millivolt

56,000

45,500

DVT38S2EN

Natural Gas

24V Hi/Lo

56,000

38,000

DVT38S2EP

Propane

24V Hi/Lo

56,000

45,500

Gas Inlet and Manifold Pressures

 

Natural

LP (Propane)

Minimum Inlet Pressure

5.5” w.c.

11.0” w.c.

Maximum Inlet Pressure

14.0” w.c.

14.0” w.c.

Manifold Pressure

3.5” w.c.

10.0” w.c.

 

 

 

DVT38S2 Units: GFSN6Q3, GFSE6Q3

Chateau™ Decorative Gas Appliance

DVT38S2

Certified To

ANSI Z21.50b-2005 / CSA 2.22b-2005

Vented Gas Fireplace

High Elevations

Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4,500 feet (1,370m) above sea level.

For elevations above 4,500 feet (1,370m) in USA, installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.

In Canada, please consult provincial and/or local authorities having jurisdiction for installations at elevations above 4,500 feet (1,370m).

WARNING: Improper installation, adjust- ment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.

Gas Line Installation

When purging gas line the front glass must be removed.

A gas shut off valve must be installed on the gas pipe line going into the appliance within easy access.

The gas pipeline can be brought in through the bottom right side of the valve box assembly.

The gas line connection can be made with properly tinned 1/2” copper tubing or 1/2” gas tight. Some municipalities have additional local codes, it is always best to consult your local authority and the CSA-B149.1installation codes.

For USA installations consult the current National Fuel Gas Code, ANSI Z223.1/NFPA 54.

1/2” NPT X 1/2” Flare

Shut-off Valve

 

 

1/2” Gas Tight or

 

 

Tinned Copper

 

 

(from valve)

FP297A

1/2” Gas Supply

(Not provided)

 

 

Fig. 8 Typical gas supply installation.

20009543

7

Image 7
Contents What to do if YOU Smell GAS INSTALLER/CONSUMER Safety InformationTable of Contents Locating Your Fireplace Installation & Operating InstructionsPlease Review the Following Carefully Critical DimensionStandard Framing Mantel Surround FramingMantels Clearance to CombustiblesHearth Nailing flanges Framing and FinishingGas Inlet and Manifold Pressures Gas Line InstallationFinal Finishing Gas SpecificationsElectrical Junction Box E Units Only Remote ON/OFF SwitchElectronic Gas Control Valve Location of Vent Termination General VentingGeneral Venting Information Termination Location Canadian Installations1 US Installations2USA Installations Canadian InstallationsGeneral Information Assembling Vent Pipes SK8 Venting Pipes Application Restrictor Plate GuideHorizontal Termination Vertical TerminationMm on the bottom Sidewall ApplicationsAlways install horizontal venting on a level plane Sidewall InstallationStep Horizontal length requirement Sidewall Installation with Stationary Glass Facing OutsideInstallation Procedure Installing the 38S2VDK DoorRestrictor plate use in straight up installation Turn shutter plate over to cover opening Installing firestop spacer Vertical Through-the-Roof InstallationMin 610mm Component Description Model Number Chimney ComponentsOperating Instructions Glass Frame Assembly RemovalGlass Cleaning Restrictor Plates InstallationLog, Lava Rock and Ember Placement Ceramic Refractory InstallationLava rock and ember placement Position the log front right. Hold the log Flame Characteristics Flame & Temperature AdjustmentRN/RP & EN/EP Models Trim frame in place Trim InstallationTo Turn Off Gas To Heater Lighting and Operating InstructionsValve Lighting and Operating InstructionsLighting Instructions Turning Off the Gas to the ApplianceSIT Nova 820 Millivolt Valve Troubleshooting the Gas Control SystemSIT 822 Valve with a Honeywell Electronic Ignitor Allow unit to cool if it has been operating Conversion PrecautionsConversion Procedure Fuel Conversion InstructionsReplace regulator Pilot Flame AdjustmentBattery Replacement for Ignitor Module MaintenanceCleaning the Standing Pilot Control System Cleaning Electronic Ignition SystemDVT38S2 Decorative Gas Appliance DVT38S2 DVT38S2Fuel Conversion Kits DVT38Model Functions Controlled AccessoriesRemote Controls Full Surround MantelProduct Covered by this Warranty Limited Lifetime WarrantyModel EnerGuide Ratings Fireplace Efficiency % Efficiency Ratings