Initial Installation
QUALIFIED INSTALLERS ONLY
WARNING:
Operation of this heater when not connected to a properly installed and maintained venting system can result in carbon monoxide (CO) poisoning and possible death.
Preparation For Installation:
•Remove the packaging from the appliance, and check to make sure there is no damage. If damage is found, please report it to both the carrier and your dealer as soon as possible.
•Before beginning, carefully check the glass door and the log set
•Locate a position where the flue system of the stove can be properly installed without damaging the integrity of the building; e.g. cutting a wall or ceiling joist.
•Check stove and flue system clearance requirements.
•Locate the stove where it can be accessed by a gas supply line.
•Locate the stove in a large and open room that is centrally located in the house. This will optimize heat circulation and comfort.
•As the stove can be equipped with a convection fan, ensure that an electrical outlet is within 6 ft (1.8 m) of the stove.
•The flow of combustion and ventilation air must not be obstructed.
Clearances to Combustibles:
A. Sidewall to unit | 11 inches | (27.9 cm) |
B. Backwall to unit | 2.5 inches | (6.35 cm) |
C. Corner to unit | 2.5 inches | (6.35 cm) |
D. Ceiling | 60 inches above floor (152.4 cm) | |
E. Floor | (hard wood and linoleum) 0 inches |
Note: When installing on a carpeted surfaces a non- combustible hearth pad must be used.
Minimum Alcove Dimensions:
Width | 48 inches (121.9 cm) |
Height | 60 inches (152.4 cm) |
Depth (max) | 24 inches (60.96 cm) |
|
| Back wall | Adjacent wall |
|
| C | |
Side wall |
| B | |
|
| ||
A |
| C | |
|
| ||
| Front | Adjacentwall | |
|
|
Figure 14: Clearances to combustibles.
CLEARANCES MUST BE SUFFICIENT TO ALLOW ACCESS FOR MAINTENANCE AND SERVICE.
Planning Your Installation:
When planning your installation, it will be necessary to select the proper length of vent pipe for your particular requirements. It is important to note when passing through a wall, the maximum allowable wall thickness is 10 inches (25.4 cm), 1½ inches (3.8 cm) clearance to combustibles must be maintained. Select the amount of vertical rise desired for
Refer to Initial Installation - Vent Configuration and Restrictor Settings for venting parameters.