Enviro C-10381, C-11290 Corner Installation, Installation for Top Vented Horizontal Termination

Page 28

Initial Installation

QUALIFIED INSTALLERS ONLY

Installation of Top Vented; Horizontal Termination:

This is the most common type of installation style. Set the unit in place.

Install a minimum 24” (61 cm) vertical chimney.

Install a 90° elbow, and mark the exterior wall where the vent would pass through.

Cut a 10” (25.4 cm) minimum hole in the wall to maintain clearances to combustibles around vent pipe. Frame hole if as shown in Figure 26.

Install wall thimble.

Install interior finished collar

Install the vent section through the wall and then install the vent termination.

Seal around the termination using a non hardening mastic.

CORNER INSTALLATION:

This type of installation can be used in a corner installation. If a 90° elbow is used in the horizontal plane, 36” (91.4 cm) must be subtracted from the allowable horizontal run shown in Figure 23.

Installation of Top Vented; Vertical Termination:

Termination

Inside

finished collar

Wall thimble

Vent pipe

Drywall

Exterior wall

Siding

Figure 43: Installation for Top Vented; Horizontal Termination.

Place the unit in place.

Drop a plumb bob from the ceiling to the center point of the flue outlet.

Cut a 10” (25.4 cm) hole in the ceiling and the roof. Refer to Figure 30.

Install the ceiling support and insulation guard.

Install the roof flashing. Ensure that the roof flashing is installed under the roofing material so that a watertight seal is created.

Install the flue pipe from the top of the unit through the roof.

Ensure that all flue pipe and unit maintain required clearances to combustibles.

CORNER INSTALLATION:

This type of installation can be used in a corner installation. If a 90° elbow is used in the horizontal plane, 36” (91.4 cm) must be subtracted from the allowable horizontal run shown in Figure 23.

Vent cap

Roof flashing

Roof

truss

Insulation

gaurd

Ceiling

support

Inside

finished collar

Flue pipe

Figure 44: Installation for Top Vented;

Vertical Termination.

28

Image 28
Contents Installer ConsumerSafety Precautions GeneralTable of Contents TOP Vent DV Codes And ApprovalsRear Vent DV Specifications Westport Exterior DimensionsOperatingInstructions MAYOperating Instructions Pilot FlameComponent Sound & Reason Maintenance And Service Electronic Ignition Module LocationTo Replace Handles for Removing DoorKit Parts List Conversion Kit InstallationRemove the black protection cap from Initial Installation Qualified Installers onlyRound Support Vent Termination Restrictions Installation Instructions KIT ComponentsInstallation of Fireplace Horizontal Vent Kit Manufacturer Trade Name Nominal Sizes4DSC Shows the vent restrictor position required, relative to 51mm at top, 1½ 38mm at sides, 1½ 38mm at Bottom Twist-Lock ConnectionTermination Pipe and elbows may be utilized in the attic, as Over 18/12 to 20/12 Over 20/12 to 21/12 Follow installation steps 1 & 2 under Initial Do not interfere with the structural integrity of the walls 33a-2002 Test Methods and the Resulting ITS Firebox Top Corner Installation Installation for Top Vented Horizontal TerminationInstallation Wiring DiagramCanadian Installations A. InstallationsVenting of a Fireplace Fitted with the Drafthood Adaptor Spillage TestSpill Switch Replacement Automatic Safety Shut DownOptional Finishing GAS Line Connection To Test Valve PressuresWire Size Max. Length Wiring Diagram For Fan ControlSecondary Installation Optional Blower Fan InstallationComplete Log Placement Log Placement with Rock Wool Brick panel bracket, slots shown Trouble Shooting Problem Possible Cause SolutionParts List Cast Reference Part Description Part NumberEGWP-505PG EGWP-501PG Parts Diagram Cast Parts List Components Parts List Components Parts Diagram Components Warranty To the DealerWarranty Installation Data Sheet