Initial Installation

QUALIFIED INSTALLERS ONLY

Gas Line Connection and Testing:

WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to

this appliance.

 

 

Manifold

Inlet

GAS LINE CONNECTION

Pressure Tap

Pressure Tap

This stove is equipped with a certified flexible pipe

located on the right side of the unit terminating in a ⅜”

male NPT fitting. Consult your local authorities codes or

the CAN/CGA B 149 (1 or 2) installation code in Canada,

or in the USA gas installations follow either local codes

or the current edition of the National Fuel Gas Code ANSI

Z223.1.

The efficiency rating of this appliance is a product

TPTT H TH

T

P

I

OL

 

IH

OUT

O

L

NI

 

OF

 

F

 

P

I

L

T

O

NO

 

thermal efficiency rating determined under continuous

operating conditions and was determined independently

of any installed system.

Pilot Adjustment

Hi/Low

Gas Control

Screw

Knob

Knob

Figure 50: Fully Labeled Gas Valve.

The appliance and its shutoff valves must be disconnected from the gas supply piping system during any pressure testing where the pressure exceeds ½ PSIG (3.45 KPa) or damage will occur to the valve.

The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psig (3.45 KPa).

Always check for gas leaks with a soap and water solution after completing the required pressure test.

TO TEST VALVE PRESSURES

The pressure taps are located on the left side of the valve

Turn set screw 1 turn counter clockwise to loosen,

Place 5/16” (8 mm) I.D. hose over pressure tap system.

Check pressures using a manometer.

When finished, release pressure, remove hose & tighten set screw.

Table 7: Pressure and BTU Information.

 

Natural Gas

Propane

Main Burner

#39 DMS

#53 DMS

Manifold Pressure

3.8” W.C. / 0.95KPa

11.0” W.C. / 2.7KPa

 

 

 

Min. Manifold Pressure

1.1” W.C. / 0.27KPa

2.7” W.C. / 0.67KPa

 

 

 

Max Supply Pressure

7.0” W.C. / 1.74KPa

13.0” W.C. / 3.28KPa

 

 

 

Min. Supply Pressure

5” W.C. / 1.24KPa

12.0” W.C. / 2.98KPa

 

 

 

Max BTU/hr Input

30,000 BTU/hr (8.80KW)

26,500 BTU/hr (7.76KW)

 

 

 

Min. BTU/hr Input

17,000 BTU/hr (4.98 KW)

14,000 BTU/hr (4.10KW)

Venturi Setting

1/16” min.

3/16” min.

NEVER USE AN OPEN FLAME FOR LEAK TESTING.

32

Image 32
Contents Installer ConsumerSafety Precautions GeneralTable of Contents Rear Vent DV Codes And ApprovalsTOP Vent DV Specifications Westport Exterior DimensionsOperatingInstructions MAYOperating Instructions Pilot FlameComponent Sound & Reason Maintenance And Service Electronic Ignition Module LocationTo Replace Handles for Removing DoorKit Parts List Conversion Kit InstallationRemove the black protection cap from Initial Installation Qualified Installers onlyRound Support Vent Termination Restrictions Installation Instructions KIT ComponentsInstallation of Fireplace Horizontal Vent Kit Manufacturer Trade Name Nominal Sizes4DSC Shows the vent restrictor position required, relative to 51mm at top, 1½ 38mm at sides, 1½ 38mm at Bottom Twist-Lock ConnectionTermination Pipe and elbows may be utilized in the attic, as Over 18/12 to 20/12 Over 20/12 to 21/12 Follow installation steps 1 & 2 under Initial Do not interfere with the structural integrity of the walls 33a-2002 Test Methods and the Resulting ITS Firebox Top Corner Installation Installation for Top Vented Horizontal TerminationInstallation Wiring DiagramCanadian Installations A. InstallationsVenting of a Fireplace Fitted with the Drafthood Adaptor Spillage TestOptional Finishing Automatic Safety Shut DownSpill Switch Replacement GAS Line Connection To Test Valve PressuresWire Size Max. Length Wiring Diagram For Fan ControlSecondary Installation Optional Blower Fan InstallationComplete Log Placement Log Placement with Rock Wool Brick panel bracket, slots shown Trouble Shooting Problem Possible Cause SolutionParts List Cast Reference Part Description Part NumberEGWP-505PG EGWP-501PG Parts Diagram Cast Parts List Components Parts List Components Parts Diagram Components Warranty To the DealerWarranty Installation Data Sheet