Enviro C-11290, C-10381 owner manual Termination

Page 21

Initial Installation

QUALIFIED INSTALLERS ONLY

wall, run a bead of non-hardening mastic around the edges, so as to make a seal between the termination and the wall. The arrow on the vent termination should be pointing up, insure that the proper clearances to combustible materials are maintained.

5.Before connecting the horizontal run of the vent pipe to the vent termination, slide the black decorative wall thimble cover over the vent pipe.

6.Slide the appliance and vent assembly towards the wall, carefully inserting the vent pipe into the cap assembly. It is important that the vent pipe extend into the vent cap a sufficient distance with a minimum of 1¼” (3.2cm) overlap. Secure the connection between the vent cap pipe and the vent cap by attaching the two sheet metal straps extending from the vent cap assembly into the outer wall of the vent pipe. Use the two sheet metal screws provided to connect the straps to the vent pipe. Bend any remaining portion of the sheet metal straps back towards the vent cap, so the decorative wall thimble will conceal it (see left image in Figure 27).

7.Slide the decorative wall thimble up to the wall surface and attach with the screws provided. Apply decorative brass or chrome trim if desired (see right image in Figure 27).

NOTES:

(a)The four (4) wood screws provided should be replaced with the appropriate fasteners for stucco, brick, concrete, or other types of siding.

(b)For buildings with vinyl siding, a vinyl siding standoff, should be installed between the vent cap and the exterior wall (see Figure 28). Attach the vinyl siding standoff to the horizontal termination. The vinyl siding standoff prevents excessive heat from possibly melting the vinyl siding material. Note that the horizontal vent termination bolts onto the flat portion of the vinyl siding standoff (shaded area in Figure 28), so that an air space will exist between the wall and the vent termination.

(c)The horizontal run of vent pipe must be level and should have a ¼ inch rise for every one foot of run towards the termination. Never allow the vent to run downward. This could cause high temperature and may present the possibility of a fire.

(d)The location of the horizontal vent termination on the exterior wall must not be easily blocked or

obstructed. Refer to Initial Installation - Vent Configurations and Restrictor Settings.

(e)When installing a vent pipe in a chase the minimum clearance to combustibles is 2” (51 mm).

(f)Maintain manufacturer’s clearances to combustibles with venting.

Figure 28: Installing Vent Cap with Vinyl Siding

Figure 29: Installing Horizontal Vent

Stand-Off.

Termination.

21

Image 21
Contents Consumer InstallerGeneral Safety PrecautionsTable of Contents Codes And Approvals TOP Vent DVRear Vent DV Westport Exterior Dimensions SpecificationsMAY OperatingInstructionsPilot Flame Operating InstructionsComponent Sound & Reason Electronic Ignition Module Location Maintenance And ServiceHandles for Removing Door To ReplaceConversion Kit Installation Kit Parts ListRemove the black protection cap from Qualified Installers only Initial InstallationRound Support Vent Termination Restrictions KIT Components Installation InstructionsManufacturer Trade Name Nominal Sizes Installation of Fireplace Horizontal Vent Kit4DSC Shows the vent restrictor position required, relative to Twist-Lock Connection 51mm at top, 1½ 38mm at sides, 1½ 38mm at BottomTermination Pipe and elbows may be utilized in the attic, as Over 18/12 to 20/12 Over 20/12 to 21/12 Follow installation steps 1 & 2 under Initial Do not interfere with the structural integrity of the walls 33a-2002 Test Methods and the Resulting ITS Firebox Top Installation for Top Vented Horizontal Termination Corner InstallationWiring Diagram InstallationCanadian Installations A. InstallationsSpillage Test Venting of a Fireplace Fitted with the Drafthood AdaptorAutomatic Safety Shut Down Spill Switch ReplacementOptional Finishing To Test Valve Pressures GAS Line ConnectionWiring Diagram For Fan Control Wire Size Max. LengthOptional Blower Fan Installation Secondary InstallationComplete Log Placement Log Placement with Rock Wool Brick panel bracket, slots shown Problem Possible Cause Solution Trouble ShootingReference Part Description Part Number Parts List CastEGWP-505PG EGWP-501PG Parts Diagram Cast Parts List Components Parts List Components Parts Diagram Components To the Dealer WarrantyWarranty Installation Data Sheet