INSTALLATION
EXTERIOR VENT TERMINATION REQUIREMENTS
INSTALLATION
A= Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm)
B= Clearance to window or door that may be opened *(12"/30cm) #(9"/23cm)
C= Clearance to permanently closed window *(min. 12"/30cm)
D= Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of (24"/60cm) from the centerline of the terminal (min. 33"/84cm) check with local code.
E= Clearance to unventilated soffi t (min. 33"/84cm)
F= Clearance to outside corner: with AstroCap Termination Cap (min. 13")
G= Clearance to inside corner: with AstroCap Termination Cap (min. 18")
H= Not to be installed above a meter/regulator assembly within (3'/90cm) horizontally from the centerline of the regulator.
J= Clearance to service regulator vent outlet *(min. 36"/90cm)
K= Clearance to
L= Clearance to a mechanical air supply inlet *(min. 72"/1.8m) #3' (91cm) above if within 10' (3m) horizontally.
M= Clearance above paved sidewalk or a paved driveway located on public property *(min. 84"/2.1m)
N= Clearance under veranda, porch, deck, or balcony *(min. 33"/84cm)
Note:
-Excluding direct vent or
-Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor.
-If the vent termination is accessible, a certifi ed guard shall be installed.
*As specifi ed in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances.
# In accordance with the current ANSI Z223.1/NFPA 54, Natioinal Fuel Gas Code.