INSTALLATION
Horizontal Venting with Two (2) 90o Elbows
INSTALLATION
One 90o elbow = Two 45o elbows.
Option |
| V | H + H1 | With these | options, | |
A) | 3' | Min. | 2' Max. | |||
maximum total pipe length | ||||||
B) | 4' | Min. | 4' Max. | |||
is 30 feet with minimum of | ||||||
C) | 6' | Min. | 8' Max. | 10 feet total vertical and | ||
|
|
|
| maximum 10 | feet total | |
D) | 8' | Min. | 9' Max. | |||
|
|
|
| horizontal. |
| |
E) | 10' Min. | 10' Max. |
| |||
|
|
Please note minimum 1 foot between 90o elbows is required.
VENT RESTRICTOR SETTING:
Vent restrictor at 0" - factory set, no adjustment required.
Horizontal Venting with Three (3) 90o Elbows
One 90o elbow = Two 45o elbows.
Option V | H | V + V1 H + H1 |
A)2' Min. 1' Max. 5' Min. 2' Max.
B)3' Min. 1' Max. 6' Min. 3' Max.
C)4' Min. 3' Max. 8' Min. 6' Max.
D)5' Min. 4 Max. 10' Min. 8' Max.
E)5' Min. 4' Max. 11' Min. 10' Max.
VENT RESTRICTOR SETTING:
Vent restrictor at 0" - factory set, no adjustment required.
With these options, max. total pipe length is 30 feet with min. of 11 feet total vertical and max. 10 feet total horizontal.
Please note min. 1 foot between 90o
20 | Regency® L900E Direct Vent Gas Fireplace |