Regency L900E-NG installation manual LOG SET Installation, 03-41 03-44 03-45 03-4203-43

Page 30

INSTALLATION

LOG SET INSTALLATION

Installation of Interior Brick Panels must be completed before installing the log set.

INSTALLATION

Read the instructions below carefully and refer to the diagrams. If the logs are broken do not use the unit until they are replaced. Broken logs can interfere with pilot operation.

Log kit (Part No. 546-930 and 546-935) contain the following pieces:

a) 03-41

Log Rear

b)03-42 Log Front Left

c)03-43 Log Front Right

d)03-44 Log Cross Left

e)03-45 Log Cross Right

f)902-154 Embers Lava

g)902-179 Vermiculite

h)946-669 Platinum Embers (supplied with packaged manual)

03-41

03-44

03-45

03-4203-43

The "03" reference numbers (i.e. 03-41) are

molded into the rear of each log.

1)Carefully remove the logs from the box and unwrap them. The logs are fragile, handle with care - do not force into position.

2)Place log 03-41 on the rear log support pins.

3)Place log 03-42 on the front left side of the burner. Place the right end of the log into the pin and rest the notch on the left end of the log on the grate.

03-42

Grate

4)Spread some vermiculite on the front log tray next to log 03-42 as shown in the image below.

Note: Do not build up vermiculite as this will cause the next log (03-43) not to sit all the way down. Vermiculite is only needed to conceal the metal inbetween the left and right front logs.

03-42

03-41

30

Regency® L900E Direct Vent Gas Fireplace

Image 30
Contents Libertytm L900E Gas Fireplace Manufactured Mobile Home Requirements Information for MOBILE/MANUFACTURED Homes After First SaleTable of Contents Safety Label InstallationRequirements MA Code CO DetectorUnit Dimensions Installation Checklist InstallationGeneral Safety Information Important Message Save These InstructionsManufactured Mobile Home Additional Requirements Heat Release KITHearth Requirements Locating Your GAS FireplaceClearances Mantel Clearances Mantel LEG ClearancesFraming & Finishing Header On EdgeUnit Assembly Prior to InstallationVenting Introduction Vent Restrictor PositionExterior Vent Termination Requirements Venting Arrangements Horizontal Termination FlexFPI Kit # Length Contains Rigid Pipe Venting Systems Basic Horizontal & Vertical Terminations8 Rigid Pipe Cross Reference Chart 58DVA-16ABL676 & L900 Direct Vent Fireplace Vent Restrictor Setting Allowable Horizontal TerminationsHorizontal Venting with Two 2 90o Elbows Vertical Venting with Three 3 90o Elbows Allowable Vertical Terminations Unit Installation with Horizontal Termination Minimum Vent Unit Installation With Vertical TerminationDiagram FeetUnit Installation Astrocap XLAeration GAS Line Installation Pilot AdjustmentTesting AdjustmentBACK-UP Battery Installation Heat ShieldBrick Panel Installation Handle with care. do not Force Into PositionExterior Brick Panel Installation LOG SET Installation 03-41 03-44 03-45 03-4203-43Embers on bottom brick panel Wiring Diagram Do not cut the ground terminal off under any circumstancesOperating Instructions Operation During Power Outage Backup BatteryNormal Operating Sounds GAS Appliances For Your Safety Read Before Lighting Copy of Lighting Plate InstructionsMaintenance BACK-UP Battery Replacement Control BOX ReplacementMaintainence Do not Remove Valve Tray Replacement Latch ScrewRear Log Stand Parts List Main AssemblyBurner & LOG Assembly Description 910-937Warranty Warranty Limited LifetimeInstaller Please complete the following information