INSTALLATION
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the fi replace are defi ned by standoffs. The metal ends of the standoff may NOT be recessed into combustible construction.
Clearance to Combustibles from:
Back 0" (0mm)
Side 0" (0mm)
Floor 0" (0mm)
Minimum Clearance from Top of Front Facing:
Mantel | min. | (445mm) |
Ceiling | 49" | (1245mm) from top of front facing |
Side Wall to Unit:
16"* (406mm)
Horizontal Vent Clearances to Combustibles:
Top | 3" | (76mm) |
Side | 2" | (51mm) |
Bottom | 2" | (51 mm) |
Vertical Vent Clearances to Combustibles:
All Sides | 2" | (51mm) |
Alcove Clearances:
Min. Depth | 36" | (914mm) |
Min. Width* | 84" | (2134mm) |
Min. Height | 84" | (2134mm) |
* Alcove side wall must have a minimum of 16" (406mm) clearance on one side.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not adhered to. It is of greatest importance that this fireplace and vent system be installed only in accordance with these instructions.
INSTALLATION
Regency® L900E Direct Vent Gas Fireplace | 9 |