Daewoo DSB-071LH owner manual AIR Purging with Vacuum Pump Test RUN, Leak Test

Page 14

INSTALLATION (CONTINUED)

AIR PURGING

Indoor Unit

Air and moisture remaining in the refrigerant system may create adverse conditions as indicated below:

• pressure in the system rises

operating current rises

cooling efficiency drops

moisture in the refrigerant circuit may freeze and block capillary tubing

water may lead to corrosion of parts in the refrigerant system

Outdoor Unit

Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondesables and moisture from the system.

AIR PURGING WITH VACUUM PUMP (TEST RUN)

Confirm each tube (narrow and wide tubes) between the indoor and outdoor units has been properly connected and all wiring for the test run has been completed. Remove the valve caps from the wide and narrow service valves on the outdoor unit. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage (shipping position).

Leak Test

1.With the service valves on the outdoor unit remaining closed, remove the threaded cover on the wide tube service port. (Save for reuse.)

2.Attach a manifold valve (with pressure gauge) and dry nitro- gen gas cylinder to this service port with charge hoses.

 

Manifold Valve

 

Pressure

Lo

Hi

Gauge

 

 

Charge Hose

CAUTION:

Be sure to use a manifold valve for air purging. If it is not avail- able, use a stop valve for this purpose. The “Hi” knob of the man- ifold valve must always be kept closed.

3.Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reaches 150 P.S.I.G. Next, test for leaks with liquid soap.

CAUTION:

Nitrogen Gas Cylinder (Vertical Position)

To avoid nitrogen entering the refrigerant system in a liquid state, the top of the nitrogen gas cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.

4.Do a leak test of all joints of the tubing (both indoor and outdoor) and both wide and narrow service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.

5.After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.

13

Image 14
Contents DSB-071LH Safety Instructions Important NotesContents Wall Bracket Concrete Nails Remote Controller Basic AccessoriesAccessories Supplied with the Unit Copper TubingAccessories 1, 2, 3, 4, 5, 6, 7 Optional AccessoriesAccessories not Supplied with the Unit Description Qty Material SizeInstallation Diagram OverviewSelecting a Site InstallationInstalling the Wall Bracket Brown Blue Blue Black Yellow/Green Mounting the Indoor Unit Preparing the Copper Tubing not Included Connecting Copper TubesTo connect the copper tubes, follow the procedures below Connecting the Drain Hose To connect the drain hose, follow the procedures belowBlack Tubing Leak Test AIR PurgingAIR Purging with Vacuum Pump Test RUN Evacuation Finishing the jobTest RUN Pump DownLocation of Controls Air Cleaning FiltersLCD Remote Controller Indoor UnitIndoor Unit Display Remote Controller Remote DisplayThree Minute Compressor Delay Connecting the AC CordSetting the Unit for Remote Operation OperationHOW to Install Batteries Celsius to Fahrenheit Conversion ChartTo SET Unit to Cool Mode To SET the Unit to Auto ModeSET Unit to Quick Mode FAN SpeedsTo SET Unit to Dehumidifier Mode To Operate FAN onlyTo SET Unit to Heat Mode To Select the FAN DirectionPress the Timer OFF button once to enter the Timer screen To SET the on Timer ModeTo SET the OFF Timer Mode Play. For example, if it is 800 P.M.Emergency Operation To SET Unit to Sleep ModeTo Cancel Sleep Mode Insert cleaned or new black fil- ters back into the unit CHANGING/CLEANING the AIR FiltersCleaning the Indoor Cover After the Season Care and MaintenancePrecautions Before the SeasonPush EMERGENCY/REMOTE Troubleshooting GuideSymptoms Possible Cause Possible Solutions Specifications Model