Heatcraft Refrigeration Products HCS manual Coil Performance- Direct Expansion MBH/SQ FT

Page 21

Coil Performance- Direct Expansion MBH/SQ FT

Table 17

Wet Evaporator Capacity

1/2" and 5/8" tube, entering air 80°F. DB, 67°F. WB

Type A and Type 5, direct expansion at 40ºF. evaporating, cooling capacities

MBH per SQ FT of coil face area

 

 

FPM, Type A Coils (1/2" DIA.)

 

FPM, Type 5 Coils (5/8" DIA.)

 

Rows

FPI

400

450

500

550

600

400

450

500

550

 

600

 

6

11.3

12.1

12.8

13.4

14.0

13.1

13.8

14.5

15.2

 

15.8

 

8

13.0

13.9

14.7

15.4

16.1

14.9

15.8

16.6

17.4

 

18.1

3

10

14.4

15.3

16.2

17.0

17.8

16.2

17.2

18.2

19.0

 

19.8

 

12

15.4

16.5

17.4

18.3

19.1

17.3

18.4

19.4

20.3

 

21.2

 

14

16.3

17.4

18.4

19.3

20.2

18.0

19.2

20.4

21.4

 

22.4

 

6

14.0

15.0

16.0

16.9

17.7

15.8

16.8

17.8

18.7

 

19.5

 

8

15.9

17.1

18.2

19.2

20.1

17.7

18.9

20.0

21.0

 

22.0

4

10

17.4

18.7

19.8

20.9

22.0

19.0

20.4

21.7

22.8

 

23.9

 

12

18.5

19.9

21.2

22.3

23.4

19.9

21.4

22.8

24.1

 

25.3

 

14

19.4

20.9

22.2

23.5

24.6

20.7

22.3

23.8

25.2

 

26.5

 

6

15.9

17.1

18.3

19.3

20.3

17.9

19.2

20.5

21.6

 

22.6

 

8

18.3

19.7

21.1

22.3

23.5

19.8

21.3

22.7

24.0

 

25.2

5

10

19.8

21.3

22.8

24.2

25.5

21.0

22.7

24.3

25.7

 

27.1

 

12

20.9

22.6

24.2

25.6

27.0

21.8

23.6

25.4

27.0

 

28.5

 

14

21.8

23.6

25.3

26.8

28.3

22.5

24.4

26.3

28.0

 

29.6

 

6

17.8

19.2

20.5

21.7

22.8

19.7

21.2

22.7

24.0

 

25.3

 

8

19.7

21.3

22.7

24.1

25.4

21.4

23.1

24.8

26.3

 

27.8

6

10

21.1

22.8

24.4

25.9

27.2

22.5

24.4

26.3

28.0

 

29.7

 

12

22.1

23.9

25.6

27.2

28.7

23.3

25.3

27.3

29.2

 

31.0

 

14

22.9

24.8

26.6

28.2

29.8

23.9

26.0

28.1

30.1

 

32.0

 

6

20.9

22.7

24.3

25.9

27.4

22.3

24.2

26.0

27.7

 

29.4

 

8

22.7

24.7

26.6

28.4

30.0

23.8

25.9

28.0

29.9

 

31.7

8

10

23.9

26.1

28.1

30.1

31.9

24.6

27.0

29.3

31.3

 

33.3

 

12

24.8

27.1

29.3

31.3

33.2

25.2

27.7

30.1

32.4

 

34.6

 

14

25.4

27.8

30.1

32.2

34.2

25.7

28.2

30.7

33.1

 

35.4

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Please contact your representative for ARI ratings for coils. These tables are only estimates. For extimates for other web bulb and evaporator temperatures, multiply by correction factors in Table 18.

Actual capacity will vary

with coil circuiting

Table 18:

 

 

 

 

 

 

Capacity Correction Factors* To Coil Performance

 

 

 

 

 

 

 

 

 

 

 

Of 67°F Wb And 40°F Evaporating

 

 

 

 

 

 

Ent Air WB

 

 

 

 

 

Refrigerant Evaporating Temperature °F.

 

 

 

 

 

 

Temp. °F.

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

60

0.820

0.794

0.768

0.740

0.713

0.685

0.656

0.628

0.598

0.568

0.538

0.506

0.475

0.442

0.409

0.376

61

0.862

0.837

0.810

0.783

0.756

0.727

0.698

0.670

0.640

0.610

0.580

0.548

0.517

0.484

0.452

0.418

62

0.907

0.881

0.854

0.827

0.799

0.771

0.743

0.714

0.684

0.654

0.623

0.592

0.561

0.528

0.496

0.462

63

0.950

0.923

0.897

0.870

0.842

0.814

0.785

0.756

0.727

0.696

0.666

0.635

0.603

0.571

0.538

0.505

64

0.994

0.969

0.942

0.914

0.887

0.859

0.831

0.802

0.772

0.742

0.712

0.680

0.649

0.616

0.583

0.550

65

1.040

1.014

0.988

0.960

0.933

0.905

0.876

0.847

0.818

0.788

0.757

0.726

0.694

0.662

0.629

0.596

66

1.087

1.061

1.035

1.008

0.980

0.952

0.923

0.894

0.864

0.835

0.804

0.773

0.741

0.709

0.676

0.642

67

1.136

1.109

1.083

1.055

1.028

1.000

0.971

0.943

0.913

0.883

0.852

0.822

0.789

0.757

0.724

0.691

68

1.185

1.158

1.132

1.105

1.077

1.050

1.020

0.992

0.962

0.932

0.901

0.870

0.838

0.806

0.773

0.740

69

1.235

1.209

1.182

1.155

1.127

1.100

1.071

1.042

1.012

0.982

0.952

0.920

0.889

0.856

0.824

0.790

70

1.286

1.260

1.235

1.206

1.179

1.152

1.122

1.094

1.063

1.033

1.003

0.972

0.940

0.908

0.875

0.841

71

1.339

1.313

1.285

1.260

1.231

1.203

1.175

1.146

1.115

1.086

1.055

1.024

0.993

0.960

0.927

0.894

72

1.393

1.365

1.340

1.314

1.285

1.257

1.229

1.200

1.170

1.140

1.110

1.079

1.046

1.015

0.981

0.948

73

1.450

1.422

1.395

1.369

1.340

1.313

1.285

1.255

1.225

1.195

1.165

1.134

1.103

1.070

1.036

1.003

74

1.505

1.479

1.451

1.425

1.396

1.370

1.340

1.310

1.281

1.252

1.221

1.190

1.159

1.126

1.094

1.060

* Note: correction factor = (enthalpy of air temperature - enthalpy of evaporator temperature) in BTU/LB divided by 16.39

21

Image 21
Contents Air Handlers Quality Standard IndexCabinet style Fan Type NomenclatureStandard Unit Features Direct Expansion Coils Air Handler CoilsWater Coils Heat Reclaim CoilsAccessories- Electric Heat Construction & DimensionsUnit Heater Dimensions Size Electric Heater Selection Example Maximum KWComponent 208 240 460 480 Accessories Filters And Auxiliary Sections Auxilary Sections- All unit Sizes Dimensions, Page 29 toAvailable Motors, Drives, Motor Starters per Horsepower Accessories for Fan and Coil SectionsMotor Drive Starter Motor Horsepower Description ‘A’ = AvailableSelection Conditions Air Handler SelectionSelection Example Selection ProcedureAir Handler Performance Quick Reference Air volume at Air handler DX air Refrigerant Chilled waterSteam Cu m/hCoil Air Handler Performance- Direct ExpansionAir Handler Perfromance- Direct Expansion Saturated Suction Temperature1339 1553Air Handler Performance- Chilled Water Row CoilsSize Air Area Std Face Air Handler Perfromance- Chilled WaterHeating 0F. Air Air Handler Performance- Hot Water/SteamSize Air Sq. Ft Heating 60F. AirOne Row Two Row Two Row One RowTemperature Difference Coil Perfromance- Heat Reclaim MBH/SQ FTType a and Type 5, hot gas reclaim, heating capacities Coil Performance- Direct Expansion MBH/SQ FT Refrigerant Evaporating Temperature FActual capacity will vary With coil circuiting 400 450 500 550 600Chilled Coil Perfromance- Chilled Water MBH/SQ FTRows FPM, Type a Coils 1/2 DIA FPM, Type 5 Coils 5/8 DIAFPM, Type 5 Coils 5/8 DIA Rows Coil Performance- Heating, Water & Steam500 600 650 700 400 FPM, Type 8 Coils 1 DIA RowsSize Fan PerformanceCoil Total RPM BHP Size 14 and SizeSize 20 and Size 32 3/8 Airfoil Fan Dimensions inches High Efficiency Filter Sections- DimensionsSize 65 and Size High Efficiency Filter SectionDimensions Size Accessory Flange PatternMixbox Inlet Duct Connections Sizes 03 Sizes 20Reference DimensionsMix box Motor and coil connectionDischarge Sizes 03 41 FCSizes 50 75 AF 10 1/8 For All Units Sizes12 5/8 Rows 15 5/8 MixboxDimension ‘T’ Depth is dimensionSizes 50 65 AF ‘D’ added toSizes 03 Mounting Locations For Vibration Isolators For All Unit SizesSize Edge For All Unit Sizes All mounting holes are 5/8 inch diameter Rows Inch filtersOne and two row heating coils do not have Vibration Isolators, Quantity Required Coil SectionModels Air Flow Reheat Position Preheat PositionWeight in pounds Net Weights and Metal GaugesTo estimate weights for other coils Air Handler Component Unit SizeFace Area Air Handler Unit Size Square Feet Face Areas- Air Pressure Drops, Dry CoilsAir Pressure Drops- Cabinets, Filters, Wet Coils Depth Flat & hi 35% Efficient , PleatedFin Air Velocity Feet Per minute Physical Data CFM Range Cooling Unit Size19.25 25.50 34.00 40.38 49.50 64.58 74.91 Small 16.04 21.25 27.63 31.88 40.50 51.67 59.42Mechanical Specification