| Coil Performance- Heating, Water & Steam |
|
|
Table 21 | 1/2" and 5/8" tube, entering air 60°F. DB |
Hot Water | Type A and Type 5, 190°F. average water temperature^, heating capacities |
| MBH per SQ FT of coil face area (water velocity=3 fps). |
|
|
| FPM, Type A Coils (1/2" DIA.) |
| FPM, Type 5 Coils (5/8" DIA.) |
| |||||||
| Rows | FPI | 400 | 500 | 600 | 650 |
| 700 | 400 | 500 | 600 | 650 | 700 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 6 | 11.2 | 12.7 | 14.0 | 14.6 |
| 15.2 | 15.1 | 17.0 | 18.5 | 19.3 | 20.0 |
|
| 8 | 14.2 | 16.0 | 17.6 | 18.3 |
| 19.0 | 18.8 | 20.9 | 22.8 | 23.7 | 24.5 |
1 | 10 | 17.1 | 19.2 | 21.0 | 21.9 |
| 22.7 | 21.9 | 24.4 | 26.6 | 27.5 | 28.4 | |
|
| 12 | 19.9 | 22.3 | 24.4 | 25.3 |
| 26.2 | 24.6 | 27.4 | 29.9 | 30.9 | 31.9 |
|
| 14 | 22.7 | 25.4 | 27.6 | 28.6 |
| 29.6 | 26.9 | 30.1 | 32.7 | 33.8 | 34.9 |
|
| 6 | 20.3 | 23.3 | 25.9 | 27.1 |
| 28.3 | 25.8 | 29.5 | 32.6 | 34.0 | 35.4 |
|
| 8 | 25.0 | 28.6 | 31.8 | 33.3 |
| 34.7 | 30.8 | 35.0 | 38.8 | 40.4 | 42.1 |
2 | 10 | 29.4 | 33.6 | 37.3 | 39.0 |
| 40.6 | 34.7 | 39.6 | 43.9 | 45.8 | 47.6 | |
|
| 12 | 33.5 | 38.3 | 42.5 | 44.4 |
| 46.2 | 37.8 | 43.4 | 48.1 | 50.3 | 52.3 |
|
| 14 | 37.3 | 42.6 | 47.3 | 49.4 |
| 51.4 | 40.4 | 46.5 | 51.7 | 54.2 | 56.3 |
|
| 6 | 27.8 | 32.1 | 36.0 | 37.8 |
| 39.6 | 35.2 | 40.8 | 45.6 | 47.9 | 50.1 |
|
| 8 | 33.5 | 38.8 | 43.5 | 45.7 |
| 47.8 | 40.1 | 46.9 | 52.9 | 55.7 | 58.3 |
3 | 10 | 38.4 | 44.7 | 50.2 | 52.7 |
| 55.2 | 43.9 | 51.6 | 58.6 | 61.7 | 64.8 | |
|
| 12 | 42.8 | 49.9 | 56.3 | 59.2 |
| 61.9 | 46.7 | 55.3 | 63.0 | 66.5 | 70.0 |
|
| 14 | 46.7 | 54.7 | 61.8 | 65.0 |
| 68.1 | 48.9 | 58.2 | 66.5 | 70.4 | 74.1 |
To estimate for other entering air and average water temperatures, multiply by correction factor in Table 23.
Actual capacity will vary with coil circuiting and flow rate
|
|
|
|
| 5/8" and 1" tube, entering air 0°F. DB |
|
|
|
| ||||||||||
Table 22 | Type 5*** and Type 8, 190°F. steam at 5 PSIG, heating capacities |
|
| ||||||||||||||||
|
|
|
|
| MBH per SQ FT of coil face area |
|
|
|
| ||||||||||
Steam |
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| FPM, Type 5 Coils (5/8" DIA.) |
|
|
| FPM, Type 8 Coils (1" DIA.) |
| |||||||||||
Rows | FPI |
| 400 |
| 500 |
|
| 600 |
| 650 |
| 700 | 400 |
| 500 | 600 | 650 | 700 | |
| 6 |
| 27.4 |
| 31.0 |
|
| 34.0 |
| 35.4 |
| 36.6 | 23.7 |
| 26.7 | 29.2 | 30.4 | 31.5 | |
| 8 |
| 34.3 |
| 38.2 |
|
| 41.2 |
| 42.4 |
| 43.5 | 30.3 |
| 34.0 | 37.1 | 38.4 | 39.7 | |
1 | 10 |
| 39.6 |
| 43.2 |
|
| 45.5 |
| 46.2 |
| 46.7 | 36.2 |
| 40.3 | 43.7 | 45.1 | 46.4 | |
| 12 |
| 43.3 |
| 46.1 |
|
| 47.0 |
| 56.6 |
| 57.9 | 42.3 |
| 46.3 | 49.2 | 50.4 | 51.4 | |
| 14 |
| 45.6 |
| 47.0 |
|
| 58.7 |
| 59.9 |
| 60.8 | 46.3 |
| 50.2 | 52.9 | 53.9 | 54.8 | |
| 6 |
| 49.4 |
| 56.6 |
|
| 62.8 |
| 65.6 |
| 68.3 |
|
|
|
|
|
|
|
| 8 |
| 56.9 |
| 65.4 |
|
| 72.6 |
| 75.7 |
| 78.4 |
|
|
|
|
|
|
|
2 | 10 |
| 62.8 |
| 72.3 |
|
| 79.7 |
| 82.7 |
| 85.3 |
|
|
|
|
|
|
|
| 12 |
| 67.5 |
| 77.5 |
|
| 84.8 |
| 87.5 |
| 89.8 |
|
|
|
|
|
|
|
| 14 |
| 71.3 |
| 81.4 |
|
| 88.3 |
| 90.7 |
| 92.4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*Type 8 coils offered as one row only on model 65 and 75.
Note: Please contact your representative for ARI ratings for coils. These tables are only estimates. To estimate for other entering air and steam pressures multiply by correction factor in Table 23.
Table 23
Capacity connections Factors to Table 21 for other than 60°F. and 190 average water temperature^
Capcity Correction Facors to Table 22 for other than 0°F. air and 5 PSIG steam***.
Ent Air |
| Average Water Temperature^, | °F. |
|
|
| Steam Pressure, PSIG |
|
| ||||||
Temp. °F. | 120 | 130 | 140 | 150 | 160 | 170 | 180 | 190 | 5 | 10 | 20 | 25 | 30 | 40 | 50 |
1.077 | 1.154 | 1.231 | 1.308 | 1.385 | 1.462 | 1.538 | 1.615 | 1.088 | 1.142 | 1.228 | 1.263 | 1.295 | 1.351 | 1.395 | |
1.000 | 1.077 | 1.154 | 1.231 | 1.308 | 1.385 | 1.462 | 1.538 | 1.044 | 1.098 | 1.184 | 1.219 | 1.251 | 1.306 | 1.351 | |
0 | 0.923 | 1.000 | 1.077 | 1.154 | 1.231 | 1.308 | 1.385 | 1.462 | 1.000 | 1.054 | 1.140 | 1.175 | 1.207 | 1.262 | 1.306 |
10 | 0.846 | 0.923 | 1.000 | 1.077 | 1.154 | 1.231 | 1.308 | 1.385 | 0.956 | 1.010 | 1.096 | 1.131 | 1.162 | 1.218 | 1.262 |
20 | 0.769 | 0.846 | 0.923 | 1.000 | 1.077 | 1.154 | 1.231 | 1.308 | 0.912 | 0.966 | 1.052 | 1.087 | 1.118 | 1.174 | 1.218 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
30 | 0.692 | 0.769 | 0.846 | 0.923 | 1.000 | 1.077 | 1.154 | 1.231 | 0.868 | 0.922 | 1.007 | 1.043 | 1.074 | 1.130 | 1.174 |
40 | 0.615 | 0.692 | 0.769 | 0.846 | 0.923 | 1.000 | 1.077 | 1.154 | 0.824 | 0.878 | 0.963 | 0.999 | 1.030 | 1.086 | 1.130 |
50 | 0.538 | 0.615 | 0.692 | 0.769 | 0.846 | 0.923 | 1.000 | 1.077 | 0.780 | 0.834 | 0.919 | 0.955 | 0.986 | 1.042 | 1.086 |
60 | 0.462 | 0.538 | 0.615 | 0.692 | 0.769 | 0.846 | 0.923 | 1.000 | 0.736 | 0.790 | 0.875 | 0.911 | 0.942 | 0.998 | 1.042 |
70 | 0.385 | 0.462 | 0.538 | 0.615 | 0.692 | 0.769 | 0.846 | 0.923 | 0.692 | 0.746 | 0.831 | 0.867 | 0.898 | 0.954 | 0.998 |
80 | 0.308 | 0.385 | 0.462 | 0.538 | 0.615 | 0.692 | 0.769 | 0.846 | 0.648 | 0.702 | 0.787 | 0.823 | 0.854 | 0.910 | 0.954 |
90 | 0.231 | 0.308 | 0.385 | 0.462 | 0.538 | 0.615 | 0.692 | 0.769 | 0.604 | 0.658 | 0.743 | 0.779 | 0.810 | 0.866 | 0.910 |
100 | 0.154 | 0.231 | 0.308 | 0.385 | 0.462 | 0.538 | 0.615 | 0.692 | 0.560 | 0.614 | 0.699 | 0.734 | 0.766 | 0.822 | 0.866 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
^ Average water temperature = (entering water temp + leaving water temp) divided by 2.
**For type 5, at 5 PSIG, if (total MBH divided by 0.961) divided by coil tubes is more than to 50 LB per tube, the condensate loading may be too high. At higher pressures the condensate loading can be more than 50 LB per tube. Get a computer rating for the application.
23