Heatcraft Refrigeration Products HCS manual Coil Perfromance- Heat Reclaim MBH/SQ FT

Page 20

Coil Perfromance- Heat Reclaim MBH/SQ FT

Table 14

Heat Reclaim Coil Selection Example:

Select reclaim coil for Size 26 air handler at 13280 CFM, 344 MBH reclaimed at 45°F. Temperature Difference.

A.Change the application’s requirement at application’s TD to adjusted requirement at 50°F. TD. Use Table 15:

344/0.9 = 382.2 MBH (adjusted)

B.Divide the adjusted MBH by the coil face area:

382.2/ 26.56 = 14.4 MBH (adjusted) per square foot

C.Find the coil air speed:

13280 / 26.56 = 500 fpm

D.Select coil rows and fins per inch from Table 16 at coil air

speed and with enough MBH to meet the MBH (adjusted to 50°F. TD) per square foot

Air Handler

Type A Large

Type 5 Large

Unit

Coil Face Area

Coil Face Area

Size

Square Feet

Square Feet

03

3.13

3.00

06

5.76

5.69

08

7.81

7.50

10

9.77

9.38

 

 

 

12

12.40

11.69

14

14.58

13.75

 

 

 

18

17.71

17.50

20

20.05

19.25

 

 

 

26

26.56

25.50

34

33.65

34.00

 

 

 

41

40.73

40.38

50

50.63

49.50

 

 

 

65

64.58

64.58

75

75.35

74.92

 

 

 

figured in step B:

Select 3 row 8 fin per inch coil with capacity of 14.56 MBH per square foot at 50°F. TD.

For this application, capacity equals: (14.56 x 26.56 x 0.9) or 348 MBH for size 26 at 45°F. TD.

E.When ordering, please specify refrigerant type and the total heat of rejection for each reclaim circuit. Or specify the per cent of the total heat of rejection that is reclaimed for each circuit.

Table 15 Heat reclaim correction factor for temperature difference between air and refrigerant.

Temperature Difference

20

25

30

35

40

45

50

Correction Factor

0.4

0.5

0.6

0.7

0.8

0.9

1.0

60

1.2

Table 16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigeration Gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat Reclaim

1/2" and 5/8" tube, 50°F TD, entering air to condensing temperatire

 

 

 

 

 

 

 

 

 

 

 

Type A and Type 5, hot gas reclaim, heating capacities

 

 

 

 

 

 

 

 

 

MBH per SQ FT of coil face area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FPM, Type A Coils (1/2" DIA.)

 

 

FPM, Type 5 Coils (5/8" DIA.)

 

 

Rows

FPI

400

450

 

500

550

600

400

 

450

 

500

550

 

600

 

 

6

7.70

8.18

 

9.43

9.90

10.25

9.25

 

9.85

 

10.41

10.91

 

11.41

 

 

8

8.90

9.45

 

10.90

11.38

11.85

10.04

 

10.70

 

11.33

11.92

 

12.47

 

2

10

10.40

11.05

 

12.15

12.73

13.18

11.12

 

11.93

 

12.68

13.37

 

14.03

 

 

12

11.70

12.45

 

13.13

13.77

14.35

12.20

 

13.13

 

13.99

14.80

 

15.56

 

 

14

12.88

13.73

 

14.48

15.18

15.83

13.23

 

14.28

 

15.26

16.18

 

17.04

 

 

6

11.08

11.96

 

12.88

13.50

13.98

12.27

 

13.13

 

13.98

14.77

 

15.52

 

 

8

12.60

13.60

 

14.56

15.25

15.90

13.17

 

14.13

 

15.07

15.96

 

16.79

 

3

10

13.93

14.95

 

15.93

16.80

17.63

14.30

 

15.48

 

16.58

17.61

 

18.58

 

 

12

14.91

16.02

 

17.08

18.03

18.95

15.40

 

16.73

 

17.98

19.16

 

20.28

 

 

14

16.08

17.30

 

18.50

19.55

20.58

16.39

 

17.87

 

19.28

20.60

 

21.86

 

 

6

13.27

14.35

 

15.53

16.38

17.18

14.50

 

15.66

 

16.77

17.81

 

18.79

 

 

8

14.98

16.21

 

17.43

18.47

19.47

15.39

 

16.66

 

17.89

19.04

 

20.12

 

4

10

16.20

17.48

 

18.75

19.92

21.07

16.50

 

17.96

 

19.36

20.68

 

21.94

 

 

12

17.47

18.73

 

19.98

21.25

22.50

17.48

 

19.11

 

20.68

22.17

 

23.58

 

 

14

18.57

19.95

 

21.30

22.65

23.97

18.32

 

20.11

 

21.83

23.48

 

25.05

 

 

6

16.41

17.83

 

19.58

20.78

21.90

17.38

 

19.10

 

20.62

22.09

 

23.49

 

 

8

18.35

19.93

 

21.50

23.10

24.67

18.10

 

19.96

 

21.61

23.21

 

24.74

 

6

10

19.13

20.90

 

22.63

24.20

25.75

18.96

 

21.00

 

22.83

24.62

 

26.33

 

 

12

19.80

21.70

 

23.58

25.23

26.87

19.65

 

21.83

 

23.82

25.78

 

27.67

 

 

14

19.87

22.01

 

24.02

26.02

27.95

20.18

 

22.48

 

24.61

26.72

 

28.75

 

 

6

18.25

20.08

 

21.75

23.45

25.08

18.93

 

21.51

 

23.02

24.69

 

26.42

 

 

8

19.29

21.31

 

23.16

25.04

26.86

19.49

 

21.82

 

23.82

25.60

 

27.47

 

8

10

20.04

22.23

 

24.24

26.30

28.28

20.11

 

22.57

 

24.74

26.67

 

28.71

 

 

12

20.51

22.82

 

24.95

27.14

29.26

20.58

 

23.12

 

25.43

27.63

 

29.68

 

 

14

20.82

23.22

 

25.44

27.72

29.95

20.91

 

23.51

 

25.93

28.25

 

30.45

This table for R-22, for R404A & R507, multiply MBH by 0.98

For heat reclaim capacities at other temperature differences, multiply by factor in Table 15.

20

Image 20
Contents Air Handlers Index Quality StandardNomenclature Cabinet style Fan TypeStandard Unit Features Air Handler Coils Direct Expansion CoilsWater Coils Heat Reclaim CoilsUnit Heater Dimensions Size Accessories- Electric HeatConstruction & Dimensions Component 208 240 460 480 Electric Heater Selection ExampleMaximum KW Accessories Auxilary Sections- All unit Sizes Dimensions, Page 29 to Filters And Auxiliary SectionsAccessories for Fan and Coil Sections Available Motors, Drives, Motor Starters per HorsepowerMotor Drive Starter Motor Horsepower Description ‘A’ = AvailableAir Handler Selection Selection ConditionsSelection Procedure Selection ExampleAir volume at Air handler DX air Refrigerant Chilled water Air Handler Performance Quick ReferenceSteam Cu m/hAir Handler Performance- Direct Expansion CoilSaturated Suction Temperature Air Handler Perfromance- Direct Expansion1339 1553Size Air Area Air Handler Performance- Chilled WaterRow Coils Air Handler Perfromance- Chilled Water Std FaceAir Handler Performance- Hot Water/Steam Heating 0F. AirHeating 60F. Air Size Air Sq. FtOne Row Two Row Two Row One RowType a and Type 5, hot gas reclaim, heating capacities Temperature DifferenceCoil Perfromance- Heat Reclaim MBH/SQ FT Refrigerant Evaporating Temperature F Coil Performance- Direct Expansion MBH/SQ FTActual capacity will vary With coil circuiting 400 450 500 550 600Coil Perfromance- Chilled Water MBH/SQ FT ChilledRows FPM, Type a Coils 1/2 DIA FPM, Type 5 Coils 5/8 DIACoil Performance- Heating, Water & Steam FPM, Type 5 Coils 5/8 DIA Rows500 600 650 700 400 FPM, Type 8 Coils 1 DIA RowsFan Performance SizeCoil Total Size 14 and Size RPM BHPSize 20 and Size 32 3/8 Airfoil Fan High Efficiency Filter Sections- Dimensions Dimensions inchesSize 65 and Size High Efficiency Filter SectionAccessory Flange Pattern Dimensions SizeMixbox Inlet Duct Connections Sizes 03 Sizes 20Dimensions ReferenceMix box Motor and coil connectionSizes 03 41 FC DischargeSizes 50 75 AF For All Units Sizes 10 1/812 5/8 Rows 15 5/8 MixboxDepth is dimension Dimension ‘T’Sizes 50 65 AF ‘D’ added toSize Edge Sizes 03 Mounting Locations For Vibration IsolatorsFor All Unit Sizes One and two row heating coils do not have For All Unit SizesAll mounting holes are 5/8 inch diameter Rows Inch filters Coil Section Vibration Isolators, Quantity RequiredModels Air Flow Reheat Position Preheat PositionNet Weights and Metal Gauges Weight in poundsTo estimate weights for other coils Air Handler Component Unit SizeFace Areas- Air Pressure Drops, Dry Coils Face Area Air Handler Unit Size Square FeetFin Air Velocity Feet Per minute Air Pressure Drops- Cabinets, Filters, Wet CoilsDepth Flat & hi 35% Efficient , Pleated Physical Data Unit Size CFM Range Cooling19.25 25.50 34.00 40.38 49.50 64.58 74.91 Small 16.04 21.25 27.63 31.88 40.50 51.67 59.42Mechanical Specification