Heatcraft Refrigeration Products HCS manual Physical Data

Page 42

Physical Data

 

 

 

 

 

 

UNIT SIZE

 

 

 

Description

 

 

03

06

08

10

12

14

18

CFM Range*

 

 

 

 

 

 

 

 

 

Cooling

 

 

800-1650

1600-3170

2400-4100

3000-5150

3550-6400

4150-755

5800-9600

Heating & Ventilating

 

800-2700

1600-5000

2400-7200

3000-9200

3550-9200

4150-12400

5800-12400

 

 

 

 

 

 

 

 

 

 

Fan Type & Shaft Diameter @ Bearing

 

 

 

 

 

 

 

FC, Low Pres.

inches

 

3/4—C

1—C

1—C

1—C

1—C

1 3/16 —PB

1 3/16 —PB

FC, Med. Pres.

inches

 

1—PB

1 3/16 —PB

1 3/16 —PB

1 3/16 —PB

1 3/16 —PB

1 7/16 —PB

1 7/16 —PB

AF, shaft dia. (in) @ bearing

 

 

 

 

 

 

 

 

 

 

 

Type 5 Coils

 

 

 

 

 

 

 

 

 

Large

FH X FL

 

18.00X24

21.00X39

30.00X36

30.00X45

33.00X51

33.00X60

42.00x60

Refrigerant

TH

 

12T

14T

20T

20T

22T

22T

28T

and Water Coils

FACE AREA

 

3.00

5.69

7.50

9.38

11.69

13.75

17.50

Small

FH X FL

 

12.00X24

15.00X39

24.00X36

24.00X45

27.00X51

27.00X60

36.00x60

Refrigerant

TH

 

8T

10T

16T

16T

18T

18T

24T

and Water Coils

FACE AREA

 

2.00

4.06

6.00

7.50

9.56

11.25

15.00

Large Type 5

FH X FL

 

16.50X24

19.50X39

28.50X36

28.50X45

33.00X51

33.00X60

40.50x60

Steam Coils^

TH

 

11T

13T

19T

19T

22T

22T

27T

 

FACE AREA

 

2.75

5.28

7.13

8.91

11.69

13.75

16.88

Small Type 5

FH X FL

 

12.00X24

15.00X39

24.00X36

24.00X45

24.00X51

27.00X60

34.50x60

Steam Coils^

TH

 

8T

10T

16T

16T

18T

18T

23T

 

FACE AREA

 

2.00

4.06

6.00

7.50

9.56

11.25

14.38

 

 

 

 

 

 

 

 

 

 

Type A Coils

 

 

 

 

 

 

 

 

 

Large

FH X FL

 

18.75x24

21.25x39

31.25x36

31.25x45

35.00x51

35.00x60

42.50x60

Refrigerant

TH

 

15T

17T

25T

25T

28T

28T

34T

and Water Coils

FACE AREA

 

3.13

5.76

7.81

9.77

12.40

14.58

17.71

Small

FH X FL

 

12.50X24

16.25X39

25.00X36

25.00X45

28.75X51

28.75X60

35.00X60

Refrigerant

TH

 

10T

13T

20T

20T

23T

23T

28T

and Water Coils

FACE AREA

 

2.08

4.40

6.25

7.81

10.18

11.99

14.58

Filters:

 

 

 

 

 

 

 

 

 

 

Area in Sq. Ft.

 

5.00

6.94

10.00

11.11

15.00

17.50

22.50

Flat

 

 

 

 

 

 

 

2-16 X 25

2-16 X 25

Section

 

 

 

 

 

 

 

1-16 X 20

2-16 X 20

 

Quantity and

 

1-20 X 20

2- 20 X 25

2-16 X 20

4-16 X 25

3-16 X 20

2- 20 X 25

2-20 X 25

 

size

 

1-20 X 16

 

2-16 X 25

 

3- 20X 20

1-20 X 20

2-20 X 20

 

 

 

 

 

 

 

 

 

 

High

Area in Sq. Ft.

 

10.00

13.89

16.67

19.44

22.22

25.00

37.50

Capacity

 

 

 

 

 

 

 

 

 

Section

Quantity and

 

2-20 X 20

4- 20 X 25

6-16 X 25

2-16 X 25

8-16 X 25

4-16 X 25

6-16 X 25

 

size

 

2-16 X 20

 

 

4-20 X 25

 

4-20 X 25

6-20 X 25

 

 

 

 

 

 

 

 

 

 

High

Area in Sq. Ft.

 

6.00

8.00

12.00

14.00

14.00

18.00

24.00

Efficiency

 

 

 

 

 

 

 

 

 

Filter

Quantity and

 

1-24 X 24

2-24 X 24

2-24 X 24

2-24 X 24

2-24 X 24

3-24 X 24

6-24 X 24

Section

size

 

1-12 X 24

 

2-12 X 24

3-12 X 24

3-12 X 24

3-12 X 24

 

 

 

 

 

 

 

 

 

 

 

^The steam coils in models 65 and 75 are not type 5. They are type 8 coils with 1" diameter tubes on 3" centers.

*The CFM range for cooling and heating starts at a low of about 400 fpm through small coil . The maximum CFM for cooling is at no more than 550 fpm through a large coil. The maximum CFM for heating is at no more than 900 fpm through a large coil. The fan tables are on pages 24 through 29.

Fan Type

Bearings

Coils

Filters

FC = Forward curve fan

(Ball Type)

FH X FL

1-24 X 24 Means one 24" by 24 “ filter

AF = Airfoil fan

C = Cartridge

FH = Finned Height , inches

 

Shaft Diameter is inches

PB = Pillow Block

FL = Finned Length, inches

 

 

 

TH = Tubes High

 

 

 

FACE AREA is in Square Feet.

 

 

 

Refrigerant can be either direct

expansion, heat reclaim , or condenser coil.

42

Image 42
Contents Air Handlers Index Quality StandardNomenclature Cabinet style Fan TypeStandard Unit Features Water Coils Air Handler CoilsDirect Expansion Coils Heat Reclaim CoilsAccessories- Electric Heat Construction & DimensionsUnit Heater Dimensions Size Electric Heater Selection Example Maximum KWComponent 208 240 460 480 Accessories Auxilary Sections- All unit Sizes Dimensions, Page 29 to Filters And Auxiliary SectionsMotor Drive Starter Motor Horsepower Description Accessories for Fan and Coil SectionsAvailable Motors, Drives, Motor Starters per Horsepower ‘A’ = AvailableAir Handler Selection Selection ConditionsSelection Procedure Selection ExampleSteam Air volume at Air handler DX air Refrigerant Chilled waterAir Handler Performance Quick Reference Cu m/hAir Handler Performance- Direct Expansion Coil1339 Saturated Suction TemperatureAir Handler Perfromance- Direct Expansion 1553Air Handler Performance- Chilled Water Row CoilsSize Air Area Air Handler Perfromance- Chilled Water Std FaceAir Handler Performance- Hot Water/Steam Heating 0F. AirOne Row Two Row Heating 60F. AirSize Air Sq. Ft Two Row One RowTemperature Difference Coil Perfromance- Heat Reclaim MBH/SQ FTType a and Type 5, hot gas reclaim, heating capacities Actual capacity will vary With coil circuiting Refrigerant Evaporating Temperature FCoil Performance- Direct Expansion MBH/SQ FT 400 450 500 550 600Rows Coil Perfromance- Chilled Water MBH/SQ FTChilled FPM, Type a Coils 1/2 DIA FPM, Type 5 Coils 5/8 DIA500 600 650 700 400 Coil Performance- Heating, Water & SteamFPM, Type 5 Coils 5/8 DIA Rows FPM, Type 8 Coils 1 DIA RowsFan Performance SizeCoil Total Size 14 and Size RPM BHPSize 20 and Size 32 3/8 Airfoil Fan Size 65 and Size High Efficiency Filter Sections- DimensionsDimensions inches High Efficiency Filter SectionMixbox Inlet Duct Connections Accessory Flange PatternDimensions Size Sizes 03 Sizes 20Mix box DimensionsReference Motor and coil connectionSizes 03 41 FC DischargeSizes 50 75 AF 12 5/8 Rows 15 5/8 For All Units Sizes10 1/8 MixboxSizes 50 65 AF Depth is dimensionDimension ‘T’ ‘D’ added toSizes 03 Mounting Locations For Vibration Isolators For All Unit SizesSize Edge For All Unit Sizes All mounting holes are 5/8 inch diameter Rows Inch filtersOne and two row heating coils do not have Models Coil SectionVibration Isolators, Quantity Required Air Flow Reheat Position Preheat PositionTo estimate weights for other coils Net Weights and Metal GaugesWeight in pounds Air Handler Component Unit SizeFace Areas- Air Pressure Drops, Dry Coils Face Area Air Handler Unit Size Square FeetAir Pressure Drops- Cabinets, Filters, Wet Coils Depth Flat & hi 35% Efficient , PleatedFin Air Velocity Feet Per minute Physical Data 19.25 25.50 34.00 40.38 49.50 64.58 74.91 Small Unit SizeCFM Range Cooling 16.04 21.25 27.63 31.88 40.50 51.67 59.42Mechanical Specification