Heatcraft Refrigeration Products HCS manual Electric Heater Selection Example, Maximum KW

Page 7

Accessories- Electric Heat

The standard electric heater section construction

Typical options for the electric heater

 

 

includes:

 

section are:

 

 

 

 

1.

Automatic thermal cutout

 

1.

Fiberglass insulation in cabinet

 

2.

Heat limiters

 

2.

At least one magnetic contactor per step of

3.

Air flow switch

 

 

heating (two or three pole break)

 

 

 

 

3.

Three phase fuse blocks and fuses

 

 

 

 

4.

Transformer with primary fusing

 

 

 

 

5.

Manual reset thermal cutout in control circuit

 

 

 

 

 

 

 

 

 

Maximum KW per

 

 

 

Maximum KW

 

 

contactor and per fuse

 

Component

208 V

240 V

 

460 V

480 V

 

block (at least one

Low amps contactor

9.0

10.4

 

19.9

20.8

 

contactor is required per

 

 

High amps contactor

17.3

19.3

 

38.2

39.9

 

step of heating):

 

 

 

Fuse block

17.3

19.9

 

38.2

39.9

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric Heater Selection Example

A.How many KW is needed to increase temperature of 17000 CFM by 27 °F for Air Handler Model Size 34?

17000 X 27

is:

153 KW IS REQUIRED

3000

 

 

B.How many steps required at 10°F rise per step?

300 X 153

is:

2.7 STEPS ROUNDS UP TO 3 STEPS

17000

 

 

C.How many steps required at 460 volts with low amps contactors?

153

is:

7.7 STEPS ROUNDS UP TO 8 STEPS

19.9

 

 

D.How many steps required at 460 volts with high amps contactors?

153

is:

4.0 STEPS

38.2

 

 

E.How many fuse blocks required?

153

is:

4.0 FUSE BLOCKS

38.2

 

 

°F. Order the 153 KW to get the 27 degree rise.

Throw out the 3 steps (figured at 10°F. rise in part B), because it is smaller than the two values figured per contactor size (parts D & E). Decide whether you want high amps or low amps contactors, if you want low amps contactors, round the 7.7 to 8 and order 8 of the low amps contactors (you now have a possible 8 steps of control). If four steps of control are satisfactory, order the high amps contactors. In either case, the application requires four fuse blocks (part E).

Notes:

1.You must order the split shipment of the fan and coil sections to get electric heat on unit size 03 through unit size 18.

2.All electric heat controls are built into the heater control box.

3.Specify two pole break contactors or three pole break contactors. Two pole contactors only de-energize, while three pole contactors disconnect.

4.Be aware of requirements for heater circuits rated more than 48 amps. According to N.E.C. Code and U.L. you must subdivide the heater elements of such circuits. N.E.C. Code requires that the sub-circuit fuses be furnished by the heater manufacturer.

Commonly Used Control Systems:

A.For small loads (up to 20 KW),consider a multi-stage thermostat.

B.For medium loads (up to 200 KW), consider a modulating thermostat that operates a step controller.

C.For fine control of large loads (above 75 KW), consider a combination step control and SCR vernier system. This scheme has 80% of heater capacity controlled by conventional step controller, with the other 20% on a solid state SCR controller.

D.For 100% proportional control of any size, consider a total SCR control.

E.Heatcraft does not supply : multi-stage thermostats modulating thermostats

But you will want to order contactors and fuse blocks from Heatcraft that are appropriate for for the control scheme specified in the field.

7

Image 7
Contents Air Handlers Quality Standard IndexCabinet style Fan Type NomenclatureStandard Unit Features Heat Reclaim Coils Air Handler CoilsDirect Expansion Coils Water CoilsConstruction & Dimensions Accessories- Electric HeatUnit Heater Dimensions Size Maximum KW Electric Heater Selection ExampleComponent 208 240 460 480 Accessories Filters And Auxiliary Sections Auxilary Sections- All unit Sizes Dimensions, Page 29 to‘A’ = Available Accessories for Fan and Coil SectionsAvailable Motors, Drives, Motor Starters per Horsepower Motor Drive Starter Motor Horsepower DescriptionSelection Conditions Air Handler SelectionSelection Example Selection ProcedureCu m/h Air volume at Air handler DX air Refrigerant Chilled waterAir Handler Performance Quick Reference SteamCoil Air Handler Performance- Direct Expansion1553 Saturated Suction TemperatureAir Handler Perfromance- Direct Expansion 1339Row Coils Air Handler Performance- Chilled WaterSize Air Area Std Face Air Handler Perfromance- Chilled WaterHeating 0F. Air Air Handler Performance- Hot Water/SteamTwo Row One Row Heating 60F. AirSize Air Sq. Ft One Row Two RowCoil Perfromance- Heat Reclaim MBH/SQ FT Temperature DifferenceType a and Type 5, hot gas reclaim, heating capacities 400 450 500 550 600 Refrigerant Evaporating Temperature FCoil Performance- Direct Expansion MBH/SQ FT Actual capacity will vary With coil circuitingFPM, Type a Coils 1/2 DIA FPM, Type 5 Coils 5/8 DIA Coil Perfromance- Chilled Water MBH/SQ FTChilled RowsFPM, Type 8 Coils 1 DIA Rows Coil Performance- Heating, Water & SteamFPM, Type 5 Coils 5/8 DIA Rows 500 600 650 700 400Size Fan PerformanceCoil Total RPM BHP Size 14 and SizeSize 20 and Size 32 3/8 Airfoil Fan High Efficiency Filter Section High Efficiency Filter Sections- DimensionsDimensions inches Size 65 and SizeSizes 03 Sizes 20 Accessory Flange PatternDimensions Size Mixbox Inlet Duct ConnectionsMotor and coil connection DimensionsReference Mix boxDischarge Sizes 03 41 FCSizes 50 75 AF Mixbox For All Units Sizes10 1/8 12 5/8 Rows 15 5/8‘D’ added to Depth is dimensionDimension ‘T’ Sizes 50 65 AFFor All Unit Sizes Sizes 03 Mounting Locations For Vibration IsolatorsSize Edge All mounting holes are 5/8 inch diameter Rows Inch filters For All Unit SizesOne and two row heating coils do not have Air Flow Reheat Position Preheat Position Coil SectionVibration Isolators, Quantity Required ModelsAir Handler Component Unit Size Net Weights and Metal GaugesWeight in pounds To estimate weights for other coilsFace Area Air Handler Unit Size Square Feet Face Areas- Air Pressure Drops, Dry CoilsDepth Flat & hi 35% Efficient , Pleated Air Pressure Drops- Cabinets, Filters, Wet CoilsFin Air Velocity Feet Per minute Physical Data 16.04 21.25 27.63 31.88 40.50 51.67 59.42 Unit SizeCFM Range Cooling 19.25 25.50 34.00 40.38 49.50 64.58 74.91 SmallMechanical Specification