Air Handler Perfromance- Chilled Water
6 Row Coils*
Table 8
Comfort Cooling
1/2" tube, entering air at 80°F. DB and 67°F. WB
1/2" tube, chilled water, cooling capacities 10 FPI*, 6 rows, large coils, 500 FPM*
| CFM | Coil | 42°F. Entering Water |
| 44°F. Entering Water |
| 45°F. Entering Water |
| |||||||
Unit | Std | Face | MBH |
|
|
| MBH |
|
| MBH |
|
| |||
Size | Air | Area | TOTAL |
| SENS | GPM | PD | TOTAL | SENS | GPM | PD | TOTAL | SENS | GPM | PD |
03 | 1565 | 3.13 | 70 |
| 47 | 13.9 | 5.8 | 63 | 44 | 12.6 | 4.9 | 60 | 43 | 11.9 | 4.4 |
06 | 2880 | 5.76 | 137 |
| 90 | 27.4 | 20.0 | 125 | 84 | 24.9 | 16.8 | 118 | 82 | 23.6 | 15.3 |
08 | 3905 | 7.81 | 184 |
| 121 | 36.7 | 17.0 | 167 | 114 | 33.3 | 14.3 | 158 | 110 | 31.6 | 13.0 |
10 | 4885 | 9.77 | 225 |
| 149 | 44.9 | 8.3 | 214 | 145 | 42.8 | 25.0 | 203 | 140 | 40.6 | 22.8 |
12 | 6200 | 12.40 | 288 |
| 190 | 57.6 | 11.0 | 261 | 179 | 52.2 | 9.2 | 248 | 173 | 49.5 | 8.3 |
14 | 7290 | 14.58 | 346 |
| 227 | 69.1 | 16.8 | 314 | 213 | 62.7 | 14.1 | 298 | 206 | 59.5 | 12.8 |
18 | 8855 | 17.71 | 421 |
| 276 | 84.1 | 17.7 | 382 | 259 | 76.4 | 14.9 | 363 | 251 | 72.5 | 13.6 |
20 | 10025 | 20.05 | 464 |
| 306 | 115.7 | 23.0 | 430 | 292 | 85.8 | 13.5 | 408 | 283 | 81.4 | 12.3 |
26 | 13280 | 26.56 | 618 |
| 407 | 123.4 | 14.1 | 560 | 383 | 111.8 | 11.8 | 531 | 371 | 106.0 | 10.6 |
34 | 16825 | 33.65 | 783 |
| 516 | 156.3 | 15.3 | 709 | 485 | 141.7 | 12.8 | 672 | 470 | 134.3 | 11.5 |
41 | 20365 | 40.73 | 947 |
| 625 | 189.2 | 16.1 | 858 | 588 | 171.5 | 13.4 | 814 | 568 | 162.6 | 12.1 |
50 | 25313 | 50.63 | 1181^ |
| 781 | 236.9 | 15.9 | 1075^ | 735 | 214.8 | 13.3 | 1020^ | 711 | 203.7 | 12.0 |
65 | 32290 | 64.58 | 1538^ |
| 1007 | 307.2 | 23.2 | 1325^ | 916 | 264.6 | 17.6 | 1325^ | 916 | 264.6 | 17.6 |
75 | 37675 | 75.35 | 1795^ |
| 1175 | 358.4 | 24.7 | 1546^ | 1068 | 308.8 | 18.7 | 1546^ | 1068 | 308.8 | 18.7 |
6 Row Coils*
Table 9
Comfort Cooling
5/8" tube, entering air at 80°F. DB and 67°F. WB
5/8" tube, chilled water, cooling capacities 10 FPI*, 6 rows, large coils, 500 FPM*
| CFM | Coil | 42°F. Entering Water |
| 44°F. Entering Water |
| 45°F. Entering Water |
| |||||||
Unit | Std | Face | MBH |
|
|
| MBH |
|
| MBH |
|
| |||
Size | Air | Area | TOTAL |
| SENS | GPM | PD | TOTAL | SENS | GPM | PD | TOTAL | SENS | GPM | PD |
03 | 1500 | 3.00 | 79 |
| 50 | 15.5 | 22.6 | 73 | 48 | 15.5 | 22.4 | 70 | 47 | 15.5 | 22.3 |
06 | 2844 | 5.69 | 146 |
| 94 | 29.5 | 11.9 | 136 | 89 | 29.5 | 11.8 | 131 | 87 | 29.5 | 11.7 |
08 | 3750 | 7.50 | 192 |
| 123 | 39.5 | 11.6 | 179 | 117 | 39.5 | 11.5 | 172 | 115 | 39.5 | 11.5 |
10 | 4690 | 9.38 | 245 |
| 157 | 49.5 | 19.3 | 229 | 149 | 49.5 | 19.2 | 220 | 146 | 49.5 | 19.1 |
12 | 5845 | 11.69 | 307 |
| 196 | 59.5 | 25.0 | 286 | 186 | 59.5 | 24.8 | 275 | 182 | 59.5 | 24.7 |
14 | 6875 | 13.75 | 364 |
| 232 | 79.5 | 14.3 | 328 | 216 | 69.5 | 11.1 | 316 | 211 | 69.5 | 11.1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
18 | 8750 | 17.50 | 449 |
| 289 | 89.5 | 11.9 | 418 | 275 | 89.5 | 11.8 | 402 | 269 | 89.5 | 11.8 |
20 | 9625 | 19.25 | 507 |
| 323 | 99.0 | 20.2 | 472 | 308 | 99.5 | 20.3 | 453 | 300 | 99.0 | 20.0 |
26 | 12750 | 25.50 | 652 |
| 420 | 139.5 | 12.0 | 616 | 404 | 123.5 | 19.1 | 590 | 392 | 119.5 | 17.9 |
34 | 17000 | 34.00 | 863 |
| 557 | 179.5 | 12.6 | 814 | 536 | 159.5 | 18.1 | 786 | 523 | 159.5 | 18.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
41 | 20188 | 40.38 | 1033 |
| 665 | 219.5 | 16.0 | 978 | 642 | 199.5 | 21.9 | 945 | 625 | 199.5 | 21.8 |
50 | 24750 | 49.50 | 1286^ |
| 822 | 279.5 | 13.4 | 1196^ | 784 | 279.5 | 13.3 | 1152^ | 765 | 279.5 | 13.3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
65 | 32291 | 64.58 | 1686^ |
| 1078 | 351.5 | 19.1 | 1549^ | 1018 | 331.5 | 16.9 | 1491^ | 994 | 332.0 | 17.0 |
75 | 37458 | 74.92 | 1922^ |
| 1236 | 378.0 | 17.5 | 1792^ | 1179 | 379.0 | 17.6 | 1722^ | 1148 | 378.0 | 17.4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GPM | = | Gallons per minute |
|
PD | = | Water pressure drop in feet of water | ^ These selections have two fluid circuits. All the other |
MBH | = | BTU per Hour in Thousands | selections have a single fluid circuit. |
Sens. | = | Sensible Capacity |
|
*To estimate performance of coils at other than 10 FPI or at other air speeds or with other water or air temperatures see page 22, or call your representative. With your representative, you can have specific computer selected coils rated for your job conditions.
17