Air Handler Performance - Quick Reference
Table 1 |
|
|
| Heating and Cooling Performance for Selected Coils |
|
|
|
|
| |||||||
|
|
|
|
|
| At 500 FPM (2.54 m/s) and 10 FPI. |
|
|
|
|
| |||||
|
|
|
|
| See notes for coil descriptions and rating conditions. |
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Note 1 | Note 2 | Note 3 | Note 4 | Note 5 | Note 6 | Note 7 | ||||||||
|
| air volume at | air handler | DX air | Refrigerant | Chilled water | Hot water | Steam | ||||||||
Unit |
| 500 fpm 2.54 m/s | face area | conditioning | Heat reclaim | A/C | Heating | Heating | ||||||||
Size |
| CFM | cu m/h | SQ FT | sq m | MBH | KW | MBH | KW | MBH |
| KW | MBH | KW | MBH | KW |
03 |
| 1565 | 2659 | 3.13 | 0.29 | 58 | 17.0 | 50 | 14.7 | 73 |
| 21.4 | 177 | 51.9 | 93 | 27.3 |
06 |
| 2880 | 4893 | 5.76 | 0.54 | 110 | 32.2 | 92 | 27.0 | 136 |
| 39.9 | 341 | 99.9 | 179 | 52.4 |
08 |
| 3905 | 6635 | 7.81 | 0.73 | 150 | 44.0 | 124 | 36.3 | 179 |
| 52.5 | 452 | 132.4 | 254 | 74.4 |
10 |
| 4885 | 8300 | 9.77 | 0.91 | 190 | 55.7 | 156 | 45.7 | 229 |
| 67.1 | 548 | 160.6 | 317 | 92.9 |
12 |
| 6200 | 10534 | 12.40 | 1.15 | 241 | 70.6 | 198 | 58.0 | 286 |
| 83.8 | 684 | 200.4 | 395 | 115.7 |
14 |
| 7290 | 12386 | 14.58 | 1.36 | 284 | 83.2 | 232 | 68.0 | 328 |
| 96.1 | 812 | 237.9 | 465 | 136.2 |
18 |
| 8855 | 15045 | 17.71 | 1.65 | 345 | 101.1 | 282 | 82.6 | 418 |
| 122.5 | 1034 | 303.0 | 571 | 167.3 |
20 |
| 10025 | 17033 | 20.05 | 1.86 | 390 | 114.3 | 319 | 93.5 | 472 |
| 138.3 | 1162 | 340.5 | 651 | 190.7 |
26 |
| 13280 | 22563 | 26.56 | 2.47 | 520 | 152.4 | 423 | 124.0 | 616 |
| 180.5 | 1520 | 445.4 | 859 | 251.7 |
34 |
| 16825 | 28586 | 33.65 | 3.13 | 659 | 193.1 | 536 | 157.1 | 814 |
| 238.5 | 2026 | 593.6 | 1145 | 335.5 |
41 |
| 20365 | 34601 | 40.73 | 3.79 | 797 | 233.5 | 649 | 190.2 | 978 |
| 286.6 | 2406 | 705.0 | 1360 | 398.5 |
50 |
| 25313 | 43008 | 50.63 | 4.70 | 992 | 290.7 | 807 | 236.5 | 1196 |
| 350.4 | 2637 | 772.6 | 1586 | 464.7 |
65 |
| 32290 | 54861 | 64.58 | 6.00 | 1253 | 367.1 | 1029 | 301.5 | 1549 |
| 453.9 | 3798 | 1112.8 | 1848 | 541.5 |
75 |
| 37675 | 64011 | 75.35 | 7.00 | 1462 | 428.4 | 1200 | 351.7 | 1792 |
| 525.1 | 4407 | 1291.3 | 2156 | 631.7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Notes
Note 1 - Air volume in CFM and cubic meters per hour for air speed of 500 fpm or 2.54 meter per second through a large face area 1/2" tube diameter (Type A) coil for each air handler model.
See pages 42 & 43 for range of air volumes for each model.
Note 2 - Face area of large size 1/2" diameter tube coil for each air handler in square feet and square meters. 5/8" & 1" diameter tube coils have slightly smaller face areas. See page 42 & 43 for other coils.
Note 3 - Direct expansion halocarbon air conditioning in thousands of BTUH and kilowatts. Performance is for a
| 1/2" tube, 4 row, 10 FPI coil with 40°F. (4.4ºC.) evaporating temperature and entering air |
| temperatures at 80°F. (26.7ºC.) dry bulb and 67°F. (19.4ºC.) wet bulb. See pages 14, 15, and 21 for |
| other coils and conditions. |
Note 4 - | Halocarbon refrigerant gas heat reclaim (thousands of BTUH and kilowatts). Performance is for a 1/2" |
| tube, 3 row, 10FPI coil with a 50°F. TD (or 27.7 degrees centigrade of temperature difference) |
| between entering air and condensing temperature. See page 20 for other coils and conditions. |
Note 5 - | Chilled water air conditioning in thousands of BTUH or kilowatts. Performance is for a 5/8" tube, 6 |
| row, 10FPI coil with 44°F. (6.7ºC.) entering water temperature. Entering air temperatures are 80°F. |
| (26.7ºC.) dry bulb and 67°F. (19.4ºC.) wet bulb. The fluid pressure drop is less than 25 feet (0.76 |
| kilogram per square centimeter) and the water velocity is less than 6 fps (1.83 meters per second). |
| See pages 16,17,and 22 for other coils and conditions. |
Note 6 - Hot water heating performance in thousands of BTUH or kilowatts. Performance is for a 5/8" tube, 2 row, 10 FPI coil with 200°F. (93.3ºC.) entering water temperature. The entering air temperature is 0°F.
Note 7 - Steam heating performance in thousands of BTUH or kilowatts. The coils are 5/8" tube, 1 row, and 10 FPI (coils for models 65 and 75 are 1" diameter tubes). The entering air temperature is 60°F. (15.6ºC.) and the steam pressure is 5 psig (1.38 kilogram per square centimeter). See pages 18, 19, and 23 for other coils and conditions.