Maintenance and Troubleshooting

9

INTRODUCTION

MAINTENANCE

This section is divided into two parts:

The first part describes the maintenance procedures.

The second part helps you to identify problems that may occur, and gives advice on how to solve these problems.

Preventative maintenance is the key to a reliable, safe and efficient system.The core of any preventive maintenance program is a list of periodic tasks.

In the paragraphs that follow are suggestions for a monthly list and a yearly list.

Note:

The monthly list and the yearly list are an average interval. If your environment is dirty, then the intervals may be shorter.

Caution:

Turn off power before disconnecting or installing sensors, con- trols or modules.

Monthly Checklist

1. Inspect flame-sensing devices for good condition and cleanliness. Keep the glass lens of scanners clean with a soft, damp cloth, since small amounts of dust will measurably reduce the flame signal strength.Wash the flame rod electrode and insulator with soap and water, then rinse and dry thoroughly.

2. Test all the alarm systems for proper signals.

3. Check ignition spark electrodes and check proper gap.

4. Test interlock sequence of all safety equipment as described in Test Procedures: manually make each interlock fail, noting what related equipment closes or stops as specified by the manufac- turer.

Test flame safeguard by manually shutting off gas to the burner.

32

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03

 

Image 32
Contents Bi-Flame Copyright Disclaimer Notice Liability Warranty About this manual Audience Important Notices Document ConventionsTable of Contents Page Page Introduction Product DescriptionAffectedTerminals SpecificationsIntroduction Dimensions Main ChassisPower Module Modules DescriptionIntroduction Module Description Identification Relay ModuleSensor Module Remote DisplayDIP Switch Selection Introduction DIP Switch Location DIP Switch AccessDIP Switch Settings S2 DIP SwitchesS4 DIP Switches S6 DIP SwitchesFunction Summary Combustion Air Flow Check TerminalMain Fuel Valve Proof-of-Closure Terminal Low Fire Start TerminalRecycle Mode Pilot Test ModeInterrupted or Intermittent Pilot Spark, Pilot Flame and Main Flame SeparationAuxiliary Inputs History LogLast Recycle by AIR=XXXXXX or Last Recycle by FLAME=XXXXXXModulation Contacts Valve Leak Fail Lkout Hhhhmmss Valve Leak Sensing Device Vlsd InterfaceValve Leakage Limits Remote Display UnitRS232 Communication Interfaces RS485 optional Fault AlarmReset AirSystem Faults System Lockout ConditionsSystem Installation Page Remote Reset Remote Display Power must be off when inserting or removing the cableJ6 J3 Wiring Diagram & Connections-Main Chassis Do not ground the shield to terminal GND Sensor InstallationIntroduction Sensor Wiring Flame Rods Scanners Scanner Sighting Conditions Test Procedures Introduction Flame Signal Strength Minimum Pilot TestPilot Flame Failure Test Main Flame Faiulre Spark Sighting Test Limits and Interlock TestsIntroduction Maintenance Monthly ChecklistYearly Checklist Troubleshooting Problem Possible Cause Solution Contact Check air filter Check blower rotationRemote Display Messages Bi-Flame Operating Sequence Wait for LO.FIRE Switch AIR ProvenAIR not Proven Lkout Purge AT High FirexxMain Flame on Pilot OFF Automatic ModulationFlame #OX Time = Main # OX FailedPost Purge Main Valve Fail LkoutRemote Display Diagnostic Messages ListedAlphabetically Message Type ExplanationRemote Display Diagnostic Messages UNSAFE-FLM-PURGE Valve LeakageValve Leak Fail Watchdog FailAppendix Conversion FactorsMetric to English Metric to MetricIllustrated Parts List Pos Eclipse Qty Description Part Number