Boiler Manual |
PART 5: BOILER PIPING (CONTINUED)
The chart below represents the various system temperatures, their respective flows and friction loss through the Munchkin which will aid in circulator selection.
SYSTEM TEMPERATURE RISE CHART
Model | Friction | 20°∆t | Friction | 25°∆t | Friction | 30°∆t | Friction | 35°∆t | Friction | 40°∆t | Friction | 45°∆t | |
Flow | Flow | Flow | Flow | Flow | Flow | ||||||||
Feet | Feet | Feet | Feet | Feet | Feet | ||||||||
| G P M | G P M | G P M | G P M | G P M | G P M | |||||||
|
|
|
|
|
|
| |||||||
6.5’ | 5 | 4.5’ | 4 | 3’ | 3.3 | 2’ | 2.5 | N/A | N/R | N/A | N/R | ||
7.8’ | 8 | 4.7’ | 6.4 | 2.9’ | 5.3 | 2’ | 4.6 | 1.5’ | 4 | 1’ | 3.5 | ||
80M | 7.8’ | 8 | 4.7’ | 6.4 | 2.9’ | 5.3 | 2’ | 4.6 | 1.5’ | 4 | 1’ | 3.5 | |
140M | 11’ | 14 | 8’ | 11.2 | 6’ | 9.3 | 4.75’ | 8 | 3.75’ | 7 | 2.5’ | 6.2 | |
199M | 17’ | 19 | 12.3’ | 15.2 | 8.5’ | 12.6 | 5.75’ | 10.8 | 4’ | 9.5 | 2.5’ | 8.4 | |
399M | 21’ | 39 | 9’ | 31.2 | 7’ | 26 | 6’ | 22.3 | 5’ | 19.5 | 4’ | 17.3 |
N/R = Not Recommended
N/A = Not Available
I.FILL AND PURGE HEATING SYSTEM
•Attach the hose to balance and purge hose connector or drain valve and run hose to nearest drain
•Close the other side of the balance and purge valve or the shut off valve after the drain.
•Open first zone balance and purge or drain valve to let water flow out the hose. If zone valves are used, open the valves one at a time manually. (Note: You should check valve manufacturer’s instruction prior to opening valves manually, so as not to damage the valve.)
•Manually operate fill valve regulator. When water runs out of the hose, while it’s connected to the balance and purge valve or drain you will see a steady stream of water (without bubbles). Close balance and purge valve or drain to stop the water from flowing. Disconnect the hose and connect it to next zone to be purged.
•Repeat this procedure for additional zones (one at time).
CAUTION
For installation that incorporates standing Iron Radiation and systems with manual vents at the high points. Follow above section and starting with the nearest manual air vent, open vent until water flows out, then close vent. Repeat procedure, working your way toward furthest air vent. It may be necessary to install a basket strainer in an older system where larger amounts of sediment may be present. Annual cleaning of the strainer may be necessary.
Upon completion, make sure that the fill valve is in automatic position and each zone balance and purge or shut off is in an open position and zone valves are positioned for automatic operation.
WARNING
Use only inhibited propylene glycol solutions which are specially formulated for hydronic systems. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems. Glycol mixtures should not exceed 50%.
1.Glycol in hydronic applications which is specially formulated for this purpose includes inhibitors that prevent the glycol from attacking metallic system components. Make certain that the system fluid is checked for the correct glycol concentration and inhibitor level.
2.The glycol solution should be tested at least once a year and as recommended by the glycol manufacturer.
3.
4.A 30% mixture of glycol will result in a BTU output loss of 15% with a 5% increase in head against system circulator.
5.A 50% mixture of glycol will result in a BTU output loss of 30% with a 50% increase in head against system circulator.
16