PART 5: BOILER PIPING (CONTINUED)
10.The Safety Relief Valve is installed at the factory. Pipe the discharge of the safety relief valve to prevent injury in the event of pressure relief. Pipe the discharge 6” above the drain to a drain. Provide piping that is the same size as the safety relief valve outlet. Never block the outlet of safety relief valve.
H. CIRCULATOR SIZING
The Munchkin Boiler Heat Exchanger does have pressure drop which must be considered in your system design. Refer to the graph in Fig. 5- 1 below for pressure drop through the Munchkin Boiler Heat Exchanger for recom- mended pump selection at a 20∆t design.
Figure
| 32 |
|
|
|
|
|
|
|
|
| 30 |
|
|
|
|
|
|
|
|
| 28 |
|
|
|
|
|
|
|
|
| 26 |
|
|
|
|
|
|
|
|
Head | 24 |
|
|
|
|
|
|
|
|
22 |
|
|
|
|
|
|
|
| |
20 |
|
|
|
|
|
|
|
| |
of |
|
|
|
|
|
|
|
| |
18 |
|
|
|
|
|
|
|
| |
in Feet |
|
|
|
|
|
|
|
| |
16 |
|
|
|
|
|
|
|
| |
14 |
|
|
|
|
|
|
|
| |
Friction | 12 |
|
|
|
|
|
|
|
|
10 |
|
|
|
|
|
|
|
| |
8 |
|
|
|
|
|
|
|
| |
| 6 |
|
|
|
|
|
|
|
|
| 4 |
|
|
|
|
|
|
|
|
| 2 |
|
|
|
|
|
|
|
|
| 0 |
|
|
|
|
|
|
|
|
| 5 | 10 | 15 | 20 | 25 | 30 | 35 | 37.5 | 40 |
|
|
|
| Flow in Gallons per Minute |
|
|
|
|
MUNCHKIN 399M
*NOTE: The recommended circulators are based on 1 gpm per 10,000 btu/hr with 20°∆t.
Figure
CIRCULATOR SIZING CHART
for Central Heating Circulator (P1)* and SuperStor Ultra Circulator (P2)*
|
| Taco | |
| P1 |
| P2 |
T50/T80/80M | 007 |
| 009 |
140M | 0010 |
| 0011 |
199M | 0011 |
| 0013 |
399M |
|
Grundfos
P1 | P2 |
UPS | UPS |
Bell & Gossett
P1 | P2 |
Note: SuperStor Ultra Indirect pump assumes the following: (6) 90 degree elbows and (1) tee on the run of 20' and 1" of copper tube size, but does not include any flow checks or zone valves.
*See drawings on the following pages