Boiler Manual |
PART 14: TROUBLESHOOTING (CONTINUED)
Table 14-2: 925 Control Board FAULT Codes
Code | Description |
| Remedy | |
|
| 1. | Check circulation pump operation | |
|
| 2. | Assure that there is adequate flow through the boiler by accessing the status menu and assuring that there is less than a 50°F rise from the | |
|
|
| return thermister to the supply thermister. | |
|
| 3. | Check thermister reading on supply thermister. Replace switch if faulty. | |
F00 | High Limit Exceeded. | 4. | If this is a new installation, disconnect the two light grey wires from the zone control, and twist the wires together. Depress the S4 reset | |
|
|
| button. If the fault clears, the problem is outside the boiler | |
|
| 5. | If this is an existing installation with glycol in it, check the condition of the water pressure switch. It may be necessary to jump out the water | |
|
|
| pressure switch (temporarily only, as a trouble shooting aid) The 24 VAC signal, may have grounded through the glycol if the water pressure | |
|
|
| switch is leaking. | |
|
| 1. | Push the red reset button on the switch. | |
|
| 2. | Check the flue temperature during operation using a combustion analyzer. | |
F01 | Vent Temperature Limit Exceeded. | 3. | Replace the vent limit switch if faulty. | |
|
| 4. | Verify the combustion drain if clear and draining properly. | |
|
| 5. | Visually inspect the target wall to see if it is intact. If not intact replace target wall. | |
| Interrupted or Shorted | 1. | Check the electrical connection to the thermister on the outlet manifold. Verify 5 VDC by checking in Molex connector. Verify thermister | |
F02 |
| values by referencing chart in this manual. | ||
Supply (Outlet) Thermister. |
| |||
| 2. | Replace thermister if necessary. | ||
|
| |||
| Interrupted or Shorted | 1. | Check the electrical connection to the thermister on the inlet manifold. Verify 5 VDC by checking in Molex connector. Verify thermister | |
F03 |
| values by referencing chart in this manual. | ||
Return (Inlet) Thermister. |
| |||
| 2. | Replace thermister if necessary. | ||
|
| |||
| Supply (Outlet) | 1. | Check circulation pump operation. | |
F05 | 2. | Assure that there is adequate flow through the boiler by accessing the status menu and assuring that there is less than a 50°F rise from the | ||
Temperature exceeds 230°F. | ||||
|
| return thermister to the supply thermister. | ||
|
|
| ||
F06 |
| 1. | Check circulation pump operation. | |
Return (Inlet) Temperature | 2. | Assure that there is adequate flow through the boiler by accessing the status menu and assuring that there is less than a 50°F rise from the | ||
| Exceeded 230°F. |
| return thermister to the supply thermister. | |
|
| 3. | Check direction of flow on boiler circulator. (See Piping Details in this manual.) | |
|
| 1. | Watch the igniter through the observation window provided. | |
| No flame detected – The boiler will | 2. | If there is no spark, check the spark electrode for the proper ¼” gap. Use 2 quarters together as a gauge to hold ignitor against to check | |
| make three attempts at ignition |
| gap distance. | |
F09 | before the control goes into this | 3. | Remove any corrosion from the spark electrode and flame rectifier probe. | |
| lockout condition. *See spark | 4. | If there is a spark but no flame, check the gas supply to the boiler. | |
| electrode detail. | 5. | If there is a flame, check the flame sensor. | |
|
| 6. | Check any flue blockage or condensate blocks. | |
|
| 1. | Monitor the gas pressure to the unit while in operation. | |
|
| 2. | Assure that the flame is stable when lit. | |
| Loss of Flame Signal – The boiler | 3. | Check to see if the green light on the display module is out while the boiler is running. | |
F10 | will relight 4 times before the control | 4. | If the green light doesn’t come on or goes off during operation check the flame signal on the status menu. | |
| goes into this lockout condition. | 5. | If the signal reads less than 1 microampere, clean the flame rectifier probe. | |
|
| 6. | If the flame rectifier probe continues to read low, replace it. | |
|
| 7. | Check the stability of the flame rectification signal. If the signal is unstable, you may need to replace the burner gasket. | |
|
| 1. | Turn the gas off to the unit at the service valve. | |
|
| 2. | If the flame signal is still present replace the igniter. | |
| False Flame Signal – The boiler will | 3. | If the flame signal is not present after turning off the gas supply, check the gas valve electrical connection. | |
F11 | lock out if it senses a flame signal | 4. | If there is no power to the gas valve, remove the valve and check for obstruction in the valve seat or replace the gas valve. | |
| when there should be none present. | 5. | Turn the gas on at the service valve after corrective action is taken. | |
|
| 6. | Check for condensate back up. Condensate back up can damage the refractory wall, and if the wall falls against the rectifier probe, it may | |
|
|
| conduct the signal to ground, giving a false reading. | |
| Combustion Fan Speed Low – The | 1. | Check the combustion air fan wiring. | |
| boiler will lock out if it senses that | 1a. | Check the quality of the 24 VAC signal by measuring from any connected safety to ground. A low voltage situation may cause a “false” | |
F13 | the fan speed is less than 70% of |
| error code | |
expected rate for more than 60 | 2. | Replace the combustion air fan. | ||
| ||||
| seconds. | 3. | Replace the control board. | |
| Combustion Fan Speed High – The | 1. | Check the combustion air fan wiring. | |
| boiler will lock out if the fan speed is | |||
F14 | 2. | Replace the combustion air fan. | ||
more than 130% of expected rate for | 3. | Replace the control board. | ||
| ||||
| more than 60 seconds. |
|
| |
|
| 1. | Make sure the connector is correctly connected to the gas valve. | |
|
| 2. | Check the electrical wiring from the valve to the control board. | |
|
| 2a. | Voltage readings will be from | |
F18 | Gas Valve Error |
| with the pins. | |
|
| 2b. | On the 399M only, check the 24 VAC relay block. | |
|
| 3. | Replace the low voltage wiring harness assembly. | |
|
| 4. | Replace control board. | |
| Supply voltage frequency out of range. | |||
F19 | ||||
|
|
| ||
| Watchdog | Call factory for further assistance. Watchdog | ||
F30 | ||||
|
|
| ||
| Parameter Memory | Call factory for further assistance. Parameter memory error, reprogramming needed | ||
F31 | ||||
|
|
| ||
| Parameter Memory Write Error | Call factory for further assistance. Parameter memory write error | ||
F32 | ||||
|
|
| ||
| Programming Error | Call factory for further assistance. Parameter memory error, reprogramming needed | ||
F33 | ||||
|
|
| ||
| Parameters Programmed | Press S4 reset | ||
PP | ||||
|
|
| ||
| Internal processor error, due to incoming voltage problems. | |||
Nc | ||||
|
|
| ||
| Internal error |
|
| |
F |
|
| ||
|
|
|
60