Harman Stove Company PB 105 manual Pellet Boiler Outdoor Air Reset Operation

Page 25

25

Pellet Boiler Outdoor Air Reset Operation

When the outdoor sensor is installed, at 20° F. or below OAT (Outdoor Air Temperature), the boiler will operate at the temperature set on the Maximum Temperature knob. The boiler water temperature will decrease by 1 degree for every 1 degree in temperature rise of the Outside Air.

Example 1

OAT

Water Temp

Degree Change

Max set at 185o

65o

140o

-45°

 

Min set at 140o

60o

145o

-40°

 

 

 

55o

150o

-35°

 

 

 

50o

155o

-30°

 

 

 

45o

160o

-25o

 

 

40o

165o

-20o

 

 

35o

170o

-15o

 

 

30o

175o

-10o

 

 

25o

180o

-5o

 

 

20o

185o

0o

 

 

15o

185o

0o

 

 

10o

185o

0o

 

 

5o

185o

 

 

 

0o

185o

 

 

 

Example 2

OAT

Water Temp

Degree Change

 

Max set at 180o

65o

150o

*

 

 

Min set at 150o

60o

150o

*

 

 

 

55o

150o

*

 

 

 

50o

150o

-30o

 

 

45o

155o

-25o

 

 

40o

160o

-20o

 

 

35o

165o

-15o

 

 

30o

170o

-10o

 

 

25o

175o

-5o

 

 

20o

180o

0o

 

 

15o

180o

0o

 

 

10o

180o

0o

 

 

5o

180o

0o

 

 

0o

180o

0o

*No change in boiler temperature after reaching minimum setpoint temperature.

Operation

Image 25
Contents Harman PB 105 Pellet Boiler Installation & Operating ManualPage Parts Locations Report # 135-S-16-6 IntroductionHarman Central Heating Products Limited Warranty WarrantyBoiler Kit Materials Refer to AssemblyDesign Installation is to be Performed by a Qualified Installer Venting Venting Venting Ventingti gKeep combustibles away From flue outlet Venting InstallationOutside Air Main Wiring Installation InstallingInstallationDuct Installing Duct/AirInstallationConditioning Example of Typical Tankless Domestic HOT Water Piping InstallationUnion AIR Vent Installation Power Failure / Heat Dissipation Loop Over Heat Safety ZoneTest Draft Test ProcedureFuel and Fuel Storage Fuel SpecificationsStatus Light OperationWithout the Outdoor Air Temperature Sensor Installed Setting The Boiler TemperaturePellet Boiler Outdoor Air Reset Operation Starting a Fire Automatically Turn Mode Selector to OFFMAX. Temp Flip the Igniter Switch up into the Auto positionHave matches or other ignition source ready Lighting a Fire ManuallyOperation Burnpot Cleaning MaintenanceFeeder Chamber Fig To remove the feeder coverRemove Ash Pan Open Ash DoorCleaning Steps Combustion Blower Cleaning Helpful Hints TroubleshootingFuel Atmospheric Conversion Pb105 #8 Ash base Assembly Pb105 #28 Feeder Assembly Stocked at depot BTU Input Range= 0, and 9350 to 113,900 SpecificationsElectrical 120 VAC 60 Hz Pellet Boiler Wiring Diagram DiagramPower Failure Backup Supply Exceeding -.9 in Water Column / -224Pa Testing LabelService Record / Notes Service Record / Notes Proudly Printed On 100% Recycled Paper Quick Reference Auto-Light