Burnham Series 2B manual Minimum Clearances

Page 5

Figure 2: Minimum Clearances

Volume [ft³](m3) = Length [ft](m) x Width [ft](m) x Height [ft](m)

b.Determine Total Input of all appliances in space. Round result to nearest 1,000 Btu per hour (Btuh).

c.Determine type of space. Divide Volume by Total Input.

i. If result is greater than or equal to 50 ft³ (1.4m3) per 1,000 Btuh, space is considered an unconfined space.

ii. If result is less than 50 ft³ (1.4m3) per 1,000 Btuh, space is considered a confined space.

d. Determine building type. A building of unusually tight construction has the following characteristics:

i. Walls and ceiling exposed to outside atmosphere have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed, and

ii. Weather-stripping has been added on openable windows and doors, and

iii. Caulking or sealants applied in joints around window and door frames, between sole plates and floors, between wall- ceiling joints, between wall panels, at plumbing and electrical penetrations, and at other openings.

e.For boiler located in a building of other than unusually tight construction, adequate combustion and ventilation air is normally provided by fresh air infiltration through cracks around windows and doors.

f.For boiler located in building of unusually tight construction, provide outdoor air through two permanent openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Locate one opening within 12 inches (30.5cm) of top of space. Locate remaining opening within 12 inches (30.5cm) of bottom of space. Minimum dimension of air opening is

3 inches (7.6cm). Size each opening per following:

i. Direct communication with outdoors. Minimum free area of 1 square inch (6.5cm2) per 4,000 Btu per hour input of all equipment in space.

ii. Vertical ducts. Minimum free area of 1 square inch (6.5cm2) per 4,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.

iii. Horizontal ducts. Minimum free area of 1 square inch (6.5cm2) per 2,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.

g.Ventilation Duct Louvers and Grilles. Equip outside openings with louvers to prevent entrance of rain and snow, and screens to prevent entrance of insects and rodents.

Louvers and grilles must be fixed in open position or interlocked with equipment to open automatically before burner operation. Screens must not be smaller than ¼ inch mesh.

Consider the blocking effect of louvers, grilles and screens when calculating the opening size to provide the required free area. If free area of louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.

8.Connect gas service from Meter to gas control assembly in accordance with Local Piping Codes and requirements of Gas Company, see Figure 1. They may require piping of larger size than Control Assembly

Connection, especially if run from meter is long or includes several elbows. (See Figure 1 for size of Gas

Connection to gas control assembly).



Image 5
Contents Price $3.00 Series 2 model B Table of Contents Weight Clearances Do not drop boiler. Do not bump boiler jacket against floorMinimum Clearances Boiler Piping Equivalent Length of FittingsSpecific Gravity Correction Factors for Natural Gas Page Page Do not use one vent damper to control two heating appliances Page Wiring Diagrams and Heat Anticipator Settings Page Safety Shutdown Sequence of Operation Page Sequence of Operation Normal Operation Wiring Schematic, Zone Valves II. Operating Instructions Top View of VR Gas Valves Yellow LED Flame Codes Instructions to PUT the Boiler in OperationGreen LED Status Codes Lighting Instructions Check Pilot Burner Flame Check GAS Input Rate to BoilerCombustion Chamber BURN-OFF Check Ignition System Safety SHUT-OFF DeviceIII. Trouble Shooting IV. Service Pilot Burner Location Burner 40mm BurnerAvoid Breathing Fiber Particulates and Dust Section Assembly Gravity Circulation Only Repair PartsCanopy Group Section Assembly and Canopy GroupThis page Left Intentionally Blank Base Assembly USS Manifold and Main Burners Inch Main Burners Manifold and Main Burners 1 Inch Main Burners Only 4B MM Main Burner, Electronic Ignition Only Manifold and Main Burners 40mm Main BurnersMM Main Burners Only 4D MM Main Burner, Natural Gas, 2001-5000 Ft. USA Only MM Main Burners Only 4C MM Main Burner Manifold4D MM Main Burner, LP Gas, 2001-5000 Ft. USA Only 4D MM Main Burner, Natural Gas, 5001-9000 Ft. USA OnlyBurner Only 40mm Burner Only Pilot Burner, Honeywell Q327A1147 Pilot Burner, Honeywell Q348A1002 Jacket Assembly Jacket Assembly, CompletePage Jacket Vestibule Panel Water Trim Limit Control Flame Rollout Switch Transformer/Relay Assembly Intermittent Circulation OnlyBlocked Vent Switch Transformer Continuous and Gravity Circulation OnlyVent Reducer Draft Hood CartonVent Damper Service Record Service Record Service Record Lwco Location Wiring of Typical LwcoLimited Warranty