Burnham Series 2B manual Do not use one vent damper to control two heating appliances

Page 9

Figure 7: Plug-in Damper Installation

WARNING

Failure to properly install and use this Blocked Vent Switch may result in property damage, personal injury or loss of life.

12. TO MEET FEDERALLY MANDATED EFFICIENCIES, THIS BOILER MUST BE EQUIPPED WITH A VENT DAMPER.

OPEN the VENT DAMPER CARTON and remove the Installation Instructions. READ THE INSTALLA- TION INSTRUCTIONS THOROUGHLY before proceeding.

The automatic gas control valve supplied on each Series 2™ boiler provides the redundancy referenced in the vent damper Installation Instructions.

CAUTION

Do not use one vent damper to control two heating appliances.

A.The vent damper should be the same size as the outlet of the Draft Hood. (See Figure 1) Unpack the damper carefully - DO NOT FORCE IT CLOSED! Forcing the damper may damage the gear train and void the warranty. The damper assembly includes a prewired connection harness for use on all 24V Standing Pilot or electronic ignition control systems.

B.Mount the vent damper assembly after the draft hood, as close to the draft hood as practicable without modification to the draft hood or vent damper. (Refer to Figure 7 and to instructions packed with the vent damper for specific instructions). This is a must for the wiring harness to fit and the damper position indicator to be visible to the users.

NOTICE

Provide adequate clearance for servicing.

WARNING

Provide 6" (15.2cm) minimum clearance between damper and combustible construction.

C.Install the 90° BX connector attached to the flexible conduit in the 7/8" knockout on the left side of the jacket. Plug the factory wired Vent Damper Harness into the polarized receptacle. Install a cable clamp around the flexible conduit and attach to the Jacket top panel. (See Figure 7).

NOTICE

Please refer to the specifications, installation instructions and troubleshooting guide packed in the vent damper carton for complete detailed installation instructions. Also refer to Figure 7 in this manual.

DContinuous Ignition (Standing Pilot) Only. Remove knockout from vent damper blade.

E.Size 202 Only. Install 4" x 3" reducing fitting on vent damper outlet.

13.Install vent connector from reducing fitting (202 Only), draft hood or damper to chimney, see

Figure 8.



Image 9
Contents Price $3.00 Series 2 model BTable of Contents Weight Clearances Do not drop boiler. Do not bump boiler jacket against floorMinimum Clearances Equivalent Length of Fittings Specific Gravity Correction Factors for Natural GasBoiler Piping Page Page Do not use one vent damper to control two heating appliances Page Wiring Diagrams and Heat Anticipator Settings Page Safety Shutdown Sequence of Operation Page Sequence of Operation Normal Operation Wiring Schematic, Zone Valves II. Operating Instructions Top View of VR Gas Valves Yellow LED Flame Codes Instructions to PUT the Boiler in OperationGreen LED Status Codes Lighting Instructions Check Pilot Burner Flame Check GAS Input Rate to BoilerCombustion Chamber BURN-OFF Check Ignition System Safety SHUT-OFF DeviceIII. Trouble Shooting IV. Service Pilot Burner Location Burner 40mm BurnerAvoid Breathing Fiber Particulates and Dust Section Assembly Gravity Circulation Only Repair PartsCanopy Group Section Assembly and Canopy GroupThis page Left Intentionally Blank Base Assembly USS Manifold and Main Burners Inch Main Burners Manifold and Main Burners 1 Inch Main Burners Only Manifold and Main Burners 40mm Main Burners MM Main Burners Only4B MM Main Burner, Electronic Ignition Only 4D MM Main Burner, Natural Gas, 2001-5000 Ft. USA Only MM Main Burners Only 4C MM Main Burner Manifold4D MM Main Burner, LP Gas, 2001-5000 Ft. USA Only 4D MM Main Burner, Natural Gas, 5001-9000 Ft. USA OnlyBurner Only 40mm Burner Only Pilot Burner, Honeywell Q327A1147 Pilot Burner, Honeywell Q348A1002 Jacket Assembly Jacket Assembly, CompletePage Jacket Vestibule Panel Water Trim Limit Control Flame Rollout Switch Transformer/Relay Assembly Intermittent Circulation OnlyBlocked Vent Switch Transformer Continuous and Gravity Circulation OnlyDraft Hood Carton Vent DamperVent Reducer Service Record Service Record Service Record Lwco Location Wiring of Typical LwcoLimited Warranty