In multiple heater applications, the combustion air intake may be ducted individually or common ducted in the same configuration as shown for venting in Section 16.0. For combustion air intake duct sizing, please refer to the Vent Sizing Table and use the diameter indicated, based on the number of heaters per duct.

SIDE VIEW

(straight configuration)

Combustion Air Intake

Flue vent termination must be 1 ft. (30 cm) higher than combustion air inlet cap.

18.0) LIGHTING AND SHUTDOWN INSTRUCTIONS

Never operate the heater with the access panel open or removed.

The access panels must be closed tightly with all the necessary screws during operation.

Failure to do so may result in death, serious injury or property damage.

The access doors on either side of the burner must be securely fastened before operating the heater.

DANGER

FIRE HAZARD

Never operate the heater with the access panel open or removed. This access panel must be closed tightly with all the necessary screws during operation.

Failure to do so may result in death, serious injury or property damage

SIDE VIEW

1) Turn on the gas and electrical supply. Rotate the gas valve knob counter-clockwise

to the “ON” position.

2)Set the thermostat to call for heat (high fire). The blower motor will energize.

3)Ignition should occur after the 15-second pre-purge.

4)If the burner fails to light, or flame is not detected during the first trial for ignition (a period of approximately 15 seconds) the gas valve is de-energized and the control goes through an inter purge delay of approximately 60 seconds before another ignition attempt. The control will attempt two additional ignition trials before going into lockout, and the valve relay will be de-energized immediately. The blower will be turned off following a post-purge period of approximately 30 seconds.

5)If the heater does not light, manually reset the thermostat or shut off power completely for 5 minutes before attempting to relight.

6)CAUTION: The heater must be grounded. Poor grounding will give nuisance lockouts, particularly during momentary power interruptions.

7)When the thermostat is satisfied with high heat, the heater will switch to low fire.

8) To shut off the heater, rotate the gas valve knob clockwise to the “OFF” position and turn off the gas at the manual gas shut off valve supplying the heater and disconnect the electrical supply.

NOTE: THE LIGHTING AND SHUTDOWN INSTRUCTIONS ARE ALSO SHOWN ON THE PERMANENT NAMEPLATE LABEL ATTACHED TO THE HEATER.

Form #43343530

 

July 08

–39–

Image 40
Contents Installation and Operation Instructions Table of Contents Safety Installer ResponsibilityInstallation Requirements General InformationFor Canada only High AltitudeMinimum Clearances to Combustibles Minimum Clearances to CombustiblesSpecifications Packing ListBurner Package Numbers Natural GASPTU 40-200 Body Package Descriptions Reflector, 4’ 11 ½’ Accessories End Reflector Accessory PackageExhaust Hood Package Typical Layouts PTU / PTS Series Emitter Length Body Length ModelTypical Assembly Layout Poisonous GAS and Soot HazardPTS Series Dimensions PTU Series Heater Assembly Joining of Tube SectionsTypical Assembly Overview PTU 40FT Shown Typical Suspension Methods Suspension HazardAssembly of Tube Sections CUT HazardAssembly of Extension Section MIN 8’ MAX 10’ Between HangersInserting Turbulators Adding Reflectors Ft. Turbulator SectionsAdding Optional 90º Elbow PTS only Adding Optional Corner Reflector PTS onlyAdding 180U-Bend PTU only Adding Optional U-BEND Reflector PTU onlyAttaching Burner BOX Assembly Connecting the Tiss System InstructionsEnd View Angle Mounted Heaters only GAS Connections and Regulations Do not USE AN Open Flame of ANY Kind to Test for LeaksKEY Dimensions and Components of the GAS Connections Supply Pressure Instructions for Pressure Test Gauge ConnectionManifold PRESSURE- Combination GAS Valve is Factory SET Electrical Connections GAS Control ValveIgnition Module Terminal Designations 24VAC/R TH/WPS/W GNDLOW Voltage 24V Thermostat Connections Single Heater LOW Voltage 24V Thermostat Connections Multiple HeatersVenting Single Heater Venting Vertical Through the RoofSingle Heater Venting Horizontal Through Sidewall #10 Self-Drill Vent Pipe Screws Common Vent Diameter Indirect Venting Unvented HeatersAIR for Combustion Direct Outside AIR for CombustionLighting and Shutdown Instructions Side ViewSequence of Operation Burner Component Locations Cleaning and Maintenance Electric Shock & Explosion HazardTroubleshooting Guide 22.0Form #43343530 JJuly Replace air switch Restart Troubleshooting Yes Replacing Parts Removal of Main Burner and ElectrodesRemoval of GAS Valve and Manifold Assembly AIR Switch Pressure CheckIgnition System Checks Ignition Module DiagnosticsTo Check Flame Sensor Circuit Installation Data Replacement Parts Guide Burner BOXLabels/Manual 22c Body Components Description