Gas-Fired Products 175, N7/L7, 100, 40, 150, 200 Replace air switch Restart Troubleshooting Yes

Page 46

Form #43343530 July 08

 

 

 

Clean blower wheel.

 

Replace air switch

 

 

 

 

 

Restart

 

 

 

 

 

 

 

troubleshooting.

 

 

 

 

 

 

 

No

 

Yes

 

 

Does the amber light

Does LED on the

Check the air intake

Remove blower is the

 

Check the pressure

Repair or replace

Replace blower

stay on until the

ignition module flash

and vent are there

wheel free from dirt

 

across the air switch

jumper check all wire

assembly.

thermostat turns off?

No once?

Yes any blockages?

No and dust?

Yes

during hot running is

terminals.

 

it higher than the

 

 

 

 

 

 

minimum required?

 

 

No

Does LED on the ignition module flash three times?

Yes

Check the gas supply pressure with all the heaters on. Does it stay above the minimum required?

 

 

Yes

 

Contact factory for

Remove blockage.

 

assistance.

Restart

No

 

troubleshooting.

 

 

 

Check gas pipe

 

 

sizing, regulators and

 

No

system supply gas

 

 

pressures.

 

No

Check turbulator, are the correct number of lengths installed?

No

Change number of turbulators.

 

No

No

 

Check vent and fresh

Remove blower does

 

the wheel turn freely?

 

air lengths, are they

 

Yes

Yes

within the maximum

 

permissible?

 

Yes

 

Check air plate

Replace air plate.

stamped part

 

numbers. Are they

No

correct?

 

–45–

Yes

After an initial step opening is the manifold gas pressure correct?

No

Adjust manifold pressure. Restart troubleshooting.

 

Remove burner

Is the heater properly

 

casting and check

grounded?

Yes

the orifice. Is it clean

Yes

 

and free from

 

 

blockage?

 

 

No

No

 

Remove blockage.

Correct grounding

 

Restart

problem.

 

troubleshooting.

 

 

 

 

 

 

Yes

 

Check the micro

 

Contact factory for

Replace flame sense

Contact factory for

 

Amps at the FC-FC+

 

assistance.

wire.

assistance.

Yes

terminals of the

Yes

 

 

 

 

module is it greater

 

 

 

 

 

than 0.7µA with flame.

 

 

 

 

 

No

 

 

No

 

 

Check the terminal on

 

Remove and inspect

Check flame sense

Contact factory for

 

the flame sense

 

flame sense

wire does it have

assistance.

 

electrode, is it tight?

Yes

electrode. Is it clean

Yes continuity?

Yes

 

 

 

and the ceramic

 

 

 

 

 

intact?

 

 

Yes

No

No

 

Troubleshoot Ends

Adjust terminal

Repair or replace

Tighten terminals.

 

connection. Restart

flame sense

Restart

 

troubleshooting.

electrode.

troubleshooting.

 

 

 

No

Troubleshooting continued from previous page

Replace gas valve.

Adjust spark gap

Replace electrode.

Are the terminals tight

 

Is there are spark to

 

Remove and re-insert

 

carefully. Restart

 

on the electrode and

 

the side of the burner

 

electrode. If it still

 

troubleshooting.

 

the ignition module?

Yes

cup?

Yes

sparks to the side.

 

 

 

 

 

 

 

Replace electrode.

Has all the air been

Is the LED on the

purged from the gas

ignition module

supply lines?

Yes steady on?

No

Yes

Purge the gas supply

Replace ignition

lines.

module.

Check the inlet pressure to the gas

No valve. Is it between the minimum and maximum for the gas pressure?

No

Adjust manifold gas pressure.

 

Yes

No

 

Check the manifold

 

Check electrode

 

gas pressure during

 

spark gap. Is it 1/8”?

 

start up. Is it zero

Yes

Yes

inches w.c?

 

No

Yes

 

 

 

After an initial step

Remove burner and

 

opening is the

check the orifice. Is it

 

manifold gas pressure

Yes clean and free from

 

correct?

blockage?

 

No

No

 

Adjust manifold

Remove blockage.

 

pressure. Restart

Restart

 

troubleshooting.

troubleshooting.

Yes

 

No

Remove spark

 

Turn off gas and

 

check for spark. Is

electrode and

 

 

there a spark to the

inspect, is the

No

throat of the burner

ceramic cracked or

 

 

cup?

loose?

 

 

 

 

 

Yes

Contact factory for

 

Check nameplate are

assistance.

 

the gas type, orifice

 

No

and airplates correct

 

 

for the stated burner

 

 

specification?

 

 

Yes

 

 

Contact factory for

 

 

assistance.

No

 

 

Check the terminal at

 

Carefully bend the

the electrode does it

 

terminal away from

arc to the burner

Yes

the burner casting.

casting?

 

Restart

 

 

troubleshooting.

No

Replace flame sense wire ignition cable. If problems persist contact factory for assistance.

Image 46
Contents Installation and Operation Instructions Table of Contents Installation Requirements SafetyInstaller Responsibility General InformationFor Canada only High AltitudeMinimum Clearances to Combustibles Minimum Clearances to CombustiblesSpecifications Packing ListBurner Package Numbers Natural GASPTU 40-200 Body Package Descriptions Reflector, 4’ 11 ½’ Accessories End Reflector Accessory PackageExhaust Hood Package Typical Layouts PTU / PTS Series Emitter Length Body Length ModelTypical Assembly Layout Poisonous GAS and Soot HazardPTS Series Dimensions PTU Series Heater Assembly Joining of Tube SectionsTypical Assembly Overview PTU 40FT Shown Typical Suspension Methods Suspension HazardAssembly of Tube Sections CUT HazardAssembly of Extension Section MIN 8’ MAX 10’ Between HangersInserting Turbulators Adding Reflectors Ft. Turbulator SectionsAdding Optional 90º Elbow PTS only Adding Optional Corner Reflector PTS onlyAdding 180U-Bend PTU only Adding Optional U-BEND Reflector PTU onlyAttaching Burner BOX Assembly Connecting the Tiss System InstructionsEnd View Angle Mounted Heaters only GAS Connections and Regulations Do not USE AN Open Flame of ANY Kind to Test for LeaksKEY Dimensions and Components of the GAS Connections Supply Pressure Instructions for Pressure Test Gauge ConnectionManifold PRESSURE- Combination GAS Valve is Factory SET Electrical Connections GAS Control ValvePS/W Ignition Module Terminal Designations 24VAC/RTH/W GNDLOW Voltage 24V Thermostat Connections Single Heater LOW Voltage 24V Thermostat Connections Multiple HeatersVenting Single Heater Venting Vertical Through the RoofSingle Heater Venting Horizontal Through Sidewall #10 Self-Drill Vent Pipe Screws Common Vent Diameter Indirect Venting Unvented HeatersAIR for Combustion Direct Outside AIR for CombustionLighting and Shutdown Instructions Side ViewSequence of Operation Burner Component Locations Cleaning and Maintenance Electric Shock & Explosion HazardTroubleshooting Guide 22.0Form #43343530 JJuly Replace air switch Restart Troubleshooting Yes Replacing Parts Removal of Main Burner and ElectrodesRemoval of GAS Valve and Manifold Assembly AIR Switch Pressure CheckIgnition System Checks Ignition Module DiagnosticsTo Check Flame Sensor Circuit Installation Data Replacement Parts Guide Burner BOXLabels/Manual 22c Body Components Description