J. Installing Vertical Termination Cap
•Attach the vertical termination cap by sliding the inner collar of the cap into the inner flue of the pipe section while placing the outer collar of the cap over the outer flue of the pipe section.
•Secure the cap by driving three
Termination Cap
Brackets/ |
| (1 of three) |
| ||
|
| |
Bolts |
|
|
Storm
Collar
Screws
Caulk
Figure 10.24
K. Installing Decorative Wall Components (SLP only)
A decorative wall thimble can be installed on an interior wall through which the vent passes. The decorative wall thimble is used to cover the wall shield firestop.
•Slide the decorative wall thimble over the last section of horizontal pipe before passing through the wall to the outside.
•Once the pipe section and the termination cap have been connected, slide the wall thimble up to the interior wall surface and attach with screws provided. See Figure 10.25.
Figure 10.25 Wall Thimble
L.Heat Shield Requirements for Horizontal Termination
WARNING! Risk of Fire! To prevent overheating and fire, heat shields must extend through the entire wall thick- ness.
•DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap (shown in Figure 10.26).
•Heat shields must overlap
There are two sections of the heat shield. One section is
If the wall thickness does not allow the required
•If the wall thickness is less than 4 in./102 mm (DVP) or
•Use an extended heat shield if the finished wall thickness is greater than
•The extended heat shield may need to be cut to length maintaining sufficient length for a
•Attach the extended heat shield to either of the existing heat shields using the screws supplied with the extended heat shield. Refer to “Vent Components Diagrams” in the back of this manual.
•Rest the small leg on the extended heat shield on top of the pipe section to properly space it from the pipe section.
Important Notice: Heat shields may not be field constructed.
Heatilator • Caliber CNXT Series • | 49 |