LG Electronics LS-Q076BEL, LS-Q096BBG Remote Control Operation Mode, Buzzer Sounding Operation

Page 21

Remote Control Operation Mode

When the remote control is selected by the slide switch on the main unit, the appliance operates according to the input by the remote control.

Protection of the evaporator pipe from frosting

If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool- ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor evaporator pipe from frosting.

When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the outdoor fan is turned on according to the condition of the room temperature.

Buzzer Sounding Operation

When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.

When the appliance-pause key is input by the remote control, the long "beep— " sounds.

When a key is input by the remote control while the slide switch on the main unit of the appliance is on the forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that the remote control signal cannot be received.

-21-

Image 21
Contents Room Air Conditioner Contents Code Type Code of Model Meaning Details of LG Model Name2002Meaning Details of LG Model Name2003~Indoor Unit FunctionsRemote Control Room, Temperature Checking PLASMAOptional Setting the Time or Timer Timer SelectionAirflow Direction Control Air Circulation Product References Model NameUnit 1Ø, 220V, 60Hz All Models DimensionsOutdoor Unit 9k Heat Pump Cooling Only Models Refrigeration Cycle DiagramLS-Q096ABL, LS-Q096AEL LS-H096QNA0, LS-H096QNA0 Wiring DiagramCooling Mode Operation Healthy Dehumidification ModeOperation Details Defrost Control Heating Mode OperationFuzzy Operation C/O Model Fuzzy Operation H/P ModelFuzzy Operation for Cooling Airflow Speed Selection On-Timer OperationFuzzy Operation for Dehumidification Fuzzy Operation for HeatingOff-Timer ↔ On-Timer Operation Off-Timer OperationSleep Timer Operation Chaos Swing ModeJet Cool Mode Operation H/P Model Jet Cool Mode Operation C/O ModelAir Cleaner Operation Forced OperationRemote Control Operation Mode Protection of the evaporator pipe from frostingBuzzer Sounding Operation Self-diagnosis Function Display FunctionHeating Model Cooling ModelInstallation Selection of the best locationPiping length and elevation Drill a hole in the wall How to fix installation plateFlaring work Indoor unit installation Connection of piping IndoorFor right rear piping Tighten the flare nut with a wrench Wrap the insulation material around the connecting portionTape the drain hose and the connecting cable Insert the connecting cable into the indoor unitConnection of the pipes-Outdoor Align the center of the pipings and sufficientlyTighten the flare nut by hand Connect the cable to the Indoor unit Connecting The Cable Between Indoor Unit and Outdoor UnitConnect the cable to the outdoor unit Form the piping Checking the drainageTo remove the front panel from the indoor unit To check the drainagePump Down Procedure Prepare remote controlSettlement of outdoor unit Evaluation of the performanceOperation Name and Function-Remote ControlON/OFF Timer Buttons To remove the Grille from the Chassis Disassembly of the parts Indoor unitTo remove the Control Box When repair, do not damage the Caution labelTo remove the Discharge Grille To remove the EvaporatorTo remove the Cross-Flow Fan To remove the Motor CoverWay Valve Liquid Side Way, 3-way ValveProcedure Check for gas leakagePurge the air from the system Set the 2-way valve to the closed position Air purging of the charge hoseRe-air purging Gas leakage Balance refrigerant of the 2-way, 3-way valvesAll amount of refrigerant leaked EvacuationAfter Evacuation Connect the charge hose to the charging cylinderPurge the air from the charge hose Trouble analysis Cycle Troubleshooting GuideElectronic Parts Troubleshooting Guide Product is not operate with the remote control Compressor/Outdoor Fan are unable to drive When indoor Fan does not operate When Vertical Louver does not operate Way Relay When Heating does not operatePage Electronic Control Device Main P.W.B Assembly DC Part TOP View Bottom View TOP View 6871A20194 TOP View 6871A30009 TOP View6871A20227 TOP View 6871A20391 TOP View 6871A20390 TOP ViewSchematic Diagram LED Type HVB Typeplasma Heat Pump Model LED Type Heat Pump Model HVB Type Exploded View and Replacement Parts List LS-Q076ABL LS-Q076BBG LS-Q076BEL Parts ListIndoorLS-Q096ABL LS-Q096BBG CABLE, Flat CABLE, Falt Cover ASSEMBLY,MOTOR LS-Q082AAL LS-C082QMA0 LS-C082QNA0 LS-C096QGL0 LS-C096QLA0 LS-C096QNA0 LS-H096QGL1 W0CZZ Parts ListOutdoor 552202 567502 561410 554160 447910 550140 430410 552203-2 TUBE,CAPILLARY Bend Compressor Base ASSEMBLY,OUTDOOR Tube ASSY,CAPILLARY LS-C082QMA0 LS-C082QNAO LS-C096QGL0 3041AR2415K April