LG Electronics LS-Q096ABM Jet Cool Mode Operation C/O Model, Jet Cool Mode Operation H/P Model

Page 20

Jet Cool Mode Operation (C/O Model)

If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.

In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.

In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C

When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.

When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then operated in order that the air outflow could reach further.

Jet Cool Mode Operation (H/P Model)

While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.

In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.

In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.

When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.

When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then operated in order that the air outflow could reach further.

Forced Operation

Operation procedures when the remote control can't be used.

The operation will be started if the power button is pressed.

If you want to stop operation, re-press the button.

 

Cooling Model

 

Heat pump Model

 

 

 

 

 

 

Room Temp. 24°C

21°C Room Temp. < 24°C

Room Temp. < 21°C

 

 

 

 

 

 

 

Operating mode

Cooling

Cooling

Healthy Dehumidification

Heating

Indoor FAN Speed

High

High

High

High

 

 

 

 

 

Setting Temperature

22°C

22°C

23°C

24°C

 

 

 

 

 

While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation.

Test operation

During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem- perature and resets in 18±1 minutes.

During test operation, if remote controller signal is received, the unit operates as remote controller sets.

If you want to use this operation, open the front panel upward and Press the power button let it be pressed for about 3 seconds.

If you want to stop the operation, re-press the button.

Auto restart

In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate procedures automatically to the previous operating conditions.

Air Cleaner Operation

When an air cleaner function is selected during Air Conditioner operation

-Plasma air cleaner function will be operated while in any operation mode with selecting the function.

-The function is to be stopped while it is operating with selecting the function.

When an air cleaner function is selected during operation off

-The function will be only operated.

When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B) will be operated again.

-20-

Image 20
Contents Room Air Conditioner Contents Details of LG Model Name2002 Code Type Code of Model MeaningDetails of LG Model Name2003~ MeaningFunctions Indoor UnitRemote Control Airflow Direction Control Air Circulation Room, Temperature CheckingPLASMAOptional Setting the Time or Timer Timer Selection Unit Product ReferencesModel Name 1Ø, 220V, 60Hz Dimensions All ModelsOutdoor Unit 9k Heat Pump Refrigeration Cycle Diagram Cooling Only ModelsWiring Diagram LS-Q096ABL, LS-Q096AEL LS-H096QNA0, LS-H096QNA0Operation Details Cooling Mode OperationHealthy Dehumidification Mode Heating Mode Operation Defrost Control Fuzzy Operation for Cooling Fuzzy Operation C/O Model Fuzzy Operation H/P Model On-Timer Operation Airflow Speed SelectionFuzzy Operation for Dehumidification Fuzzy Operation for HeatingOff-Timer Operation Off-Timer ↔ On-Timer OperationSleep Timer Operation Chaos Swing ModeJet Cool Mode Operation C/O Model Jet Cool Mode Operation H/P ModelAir Cleaner Operation Forced OperationBuzzer Sounding Operation Remote Control Operation ModeProtection of the evaporator pipe from frosting Display Function Self-diagnosis FunctionHeating Model Cooling ModelPiping length and elevation InstallationSelection of the best location How to fix installation plate Drill a hole in the wallFlaring work For right rear piping Indoor unit installationConnection of piping Indoor Wrap the insulation material around the connecting portion Tighten the flare nut with a wrenchInsert the connecting cable into the indoor unit Tape the drain hose and the connecting cableTighten the flare nut by hand Connection of the pipes-OutdoorAlign the center of the pipings and sufficiently Connecting The Cable Between Indoor Unit and Outdoor Unit Connect the cable to the Indoor unitConnect the cable to the outdoor unit Checking the drainage Form the pipingTo remove the front panel from the indoor unit To check the drainagePrepare remote control Pump Down ProcedureSettlement of outdoor unit Evaluation of the performanceName and Function-Remote Control OperationON/OFF Timer Buttons Disassembly of the parts Indoor unit To remove the Grille from the ChassisWhen repair, do not damage the Caution label To remove the Control BoxTo remove the Discharge Grille To remove the EvaporatorTo remove the Motor Cover To remove the Cross-Flow FanWay, 3-way Valve Way Valve Liquid SidePurge the air from the system ProcedureCheck for gas leakage Air purging of the charge hose Set the 2-way valve to the closed positionRe-air purging Balance refrigerant of the 2-way, 3-way valves Gas leakageEvacuation All amount of refrigerant leakedPurge the air from the charge hose After EvacuationConnect the charge hose to the charging cylinder Cycle Troubleshooting Guide Trouble analysisElectronic Parts Troubleshooting Guide Product is not operate with the remote control Compressor/Outdoor Fan are unable to drive When indoor Fan does not operate When Vertical Louver does not operate When Heating does not operate Way RelayPage Electronic Control Device Main P.W.B Assembly DC Part TOP View Bottom View TOP View 6871A20227 TOP View 6871A20194 TOP View6871A30009 TOP View 6871A20390 TOP View 6871A20391 TOP ViewSchematic Diagram LED Type HVB Typeplasma Heat Pump Model LED Type Heat Pump Model HVB Type Exploded View and Replacement Parts List Parts ListIndoor LS-Q076ABL LS-Q076BBG LS-Q076BELLS-Q096ABL LS-Q096BBG CABLE, Flat CABLE, Falt Cover ASSEMBLY,MOTOR LS-Q082AAL LS-C082QMA0 LS-C082QNA0 LS-C096QGL0 LS-C096QLA0 LS-C096QNA0 LS-H096QGL1 W0CZZ Parts ListOutdoor 552202 567502 561410 554160 447910 550140 430410 552203-2 TUBE,CAPILLARY Bend Compressor Base ASSEMBLY,OUTDOOR Tube ASSY,CAPILLARY LS-C082QMA0 LS-C082QNAO LS-C096QGL0 3041AR2415K April