4. Checking the Drainage and Forming the Pipings

1) Checking the drainage

1.To remove the front panel from the indoor unit.

Set the air direction louvers up-and-down to the posi- tion(horizontally) by hand.

Remove the securing screws that retain the front pan- el. Pull the lower left and right sides of the grille toward you and lift it off.

Pull the right and the left side.

2.To check the drainage.

Pour a glass of water on the evaporator.

Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.

2) Form the piping

1.Form the piping by wrapping the connecting por- tion of the indoor unit with insulation material and secure it with two kinds of vinyl tapes.

If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.

2.In cases where the outdoor unit is installed below the indoor unit perform the following.

Tape the piping, drain hose and connecting cable from down to up.

Secure the tapped piping along the exterior wall using saddle or equivalent.

Seal small openings around pipings with a gum type sealer.

Taping Taping

Drain

Drain hose

hose

 

Pipings

Pipings

Connecting

Connecting

cable

cable

LS-Q096AAL

LS-Q096ABL

3.Drain piping

The drain hose should point downward for easy drain flow.

Downward slope

• Do not make drain piping.

 

Do not raise

 

Accumulated

 

 

 

 

 

drain water

 

 

 

 

 

 

 

Tip of drain hose

 

 

 

 

Air

 

Less than

 

 

 

 

 

dipped in water

 

 

 

 

 

50mm gap

 

 

 

 

 

 

Water

 

Water

Waving

Water

 

 

leakage

 

leakage

leakage

Ditch

 

 

 

 

 

 

 

 

 

 

Trap is required to prevent water from entering into electrical parts.

3.In cases where the Outdoor unit is installed above the Indoor unit perform the following.

Tape the piping and connecting cable from down to up.

Secure the taped piping along the exterior wall. Form a trap to prevent water entering the room.

Fix the piping onto the wall by saddle or equivalent.

Seal a small opening around the pipings with gum type sealer.

Trap

Trap

-32-

Image 32
Contents Room Air Conditioner Contents Details of LG Model Name2002 Code Type Code of Model MeaningDetails of LG Model Name2003~ MeaningFunctions Indoor UnitRemote Control Airflow Direction Control Air Circulation Room, Temperature CheckingPLASMAOptional Setting the Time or Timer Timer Selection Unit Product ReferencesModel Name 1Ø, 220V, 60Hz Dimensions All ModelsOutdoor Unit 9k Heat Pump Refrigeration Cycle Diagram Cooling Only ModelsWiring Diagram LS-Q096ABL, LS-Q096AEL LS-H096QNA0, LS-H096QNA0Operation Details Cooling Mode OperationHealthy Dehumidification Mode Heating Mode Operation Defrost ControlFuzzy Operation for Cooling Fuzzy Operation C/O ModelFuzzy Operation H/P Model On-Timer Operation Airflow Speed SelectionFuzzy Operation for Dehumidification Fuzzy Operation for HeatingOff-Timer Operation Off-Timer ↔ On-Timer OperationSleep Timer Operation Chaos Swing ModeJet Cool Mode Operation C/O Model Jet Cool Mode Operation H/P ModelAir Cleaner Operation Forced OperationBuzzer Sounding Operation Remote Control Operation ModeProtection of the evaporator pipe from frosting Display Function Self-diagnosis FunctionHeating Model Cooling ModelPiping length and elevation InstallationSelection of the best location How to fix installation plate Drill a hole in the wallFlaring work For right rear piping Indoor unit installationConnection of piping Indoor Wrap the insulation material around the connecting portion Tighten the flare nut with a wrenchInsert the connecting cable into the indoor unit Tape the drain hose and the connecting cable Tighten the flare nut by hand Connection of the pipes-Outdoor Align the center of the pipings and sufficiently Connecting The Cable Between Indoor Unit and Outdoor Unit Connect the cable to the Indoor unitConnect the cable to the outdoor unit Checking the drainage Form the pipingTo remove the front panel from the indoor unit To check the drainagePrepare remote control Pump Down ProcedureSettlement of outdoor unit Evaluation of the performanceName and Function-Remote Control OperationON/OFF Timer Buttons Disassembly of the parts Indoor unit To remove the Grille from the ChassisWhen repair, do not damage the Caution label To remove the Control BoxTo remove the Discharge Grille To remove the EvaporatorTo remove the Motor Cover To remove the Cross-Flow FanWay, 3-way Valve Way Valve Liquid SidePurge the air from the system ProcedureCheck for gas leakage Air purging of the charge hose Set the 2-way valve to the closed positionRe-air purging Balance refrigerant of the 2-way, 3-way valves Gas leakageEvacuation All amount of refrigerant leakedPurge the air from the charge hose After EvacuationConnect the charge hose to the charging cylinder Cycle Troubleshooting Guide Trouble analysisElectronic Parts Troubleshooting Guide Product is not operate with the remote control Compressor/Outdoor Fan are unable to drive When indoor Fan does not operate When Vertical Louver does not operate When Heating does not operate Way RelayPage Electronic Control Device Main P.W.B Assembly DC Part TOP View Bottom View TOP View 6871A20227 TOP View 6871A20194 TOP View6871A30009 TOP View 6871A20390 TOP View 6871A20391 TOP ViewSchematic Diagram LED Type HVB Typeplasma Heat Pump Model LED Type Heat Pump Model HVB Type Exploded View and Replacement Parts List Parts ListIndoor LS-Q076ABL LS-Q076BBG LS-Q076BELLS-Q096ABL LS-Q096BBG CABLE, Flat CABLE, Falt Cover ASSEMBLY,MOTOR LS-Q082AAL LS-C082QMA0 LS-C082QNA0 LS-C096QGL0 LS-C096QLA0 LS-C096QNA0 LS-H096QGL1 W0CZZ Parts ListOutdoor 552202 567502 561410 554160 447910 550140 430410 552203-2 TUBE,CAPILLARY Bend Compressor Base ASSEMBLY,OUTDOOR Tube ASSY,CAPILLARY LS-C082QMA0 LS-C082QNAO LS-C096QGL0 3041AR2415K April