3.Insert the connecting cable into the indoor unit.

Don't connect the cable to the indoor unit.

Make a small loop with the cable for easy connection later.

4.Tape the drain hose and the connecting cable.

Connecting cable

5.Indoor unit installation

Hang the indoor unit from the hooks at the top of the installation plate.

Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.

Indoor unit

Spacer

Installation plate

8cm

Outside diameter

 

Torque

 

 

 

 

mm

 

inch

kg.m

Ø6.35

 

1/4

1.8

Ø9.52

 

3/8

4.2

 

 

 

 

Ø12.7

 

1/2

5.5

 

 

 

 

Ø15.88

 

5/8

6.6

Ø19.05

 

3/4

6.6

 

 

 

 

When extending the drain hose at the indoor unit, install the drain pipe.

Drain hose

Indoor unit drain hose

Adhesive Vinyl tape (narrow)

7.Wrap the insulation material around the con- necting portion.

Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.

Plastic bands Insulation material

6.Connecting the pipings to the indoor unit and the drain hose to drain pipe.

Align the center of the pipes and sufficiently tighten the flare nut by hand.

Indoor unit tubing

Flare nut Pipes

• Tighten the flare nut with a wrench.

Open-end wrench (fixed)

Flare nut

Wrap the area which accommodates the rear piping housing section with vinyl tape.

Connection

Indoor

unit piping

pipe

 

Vinyl tape

Wrap with vinyl tape

(wide)

 

 

Pipe

 

Vinyl tape(narrow)

Connecting cable

 

Wrench

Connection pipe

Indoor unit tubing

-28-

Image 28
Contents Room Air Conditioner Contents Details of LG Model Name2002 Code Type Code of Model MeaningDetails of LG Model Name2003~ MeaningFunctions Indoor UnitRemote Control PLASMAOptional Setting the Time or Timer Timer Selection Room, Temperature CheckingAirflow Direction Control Air Circulation Model Name Product ReferencesUnit 1Ø, 220V, 60Hz Dimensions All ModelsOutdoor Unit 9k Heat Pump Refrigeration Cycle Diagram Cooling Only ModelsWiring Diagram LS-Q096ABL, LS-Q096AEL LS-H096QNA0, LS-H096QNA0Healthy Dehumidification Mode Cooling Mode OperationOperation Details Heating Mode Operation Defrost ControlFuzzy Operation H/P Model Fuzzy Operation C/O ModelFuzzy Operation for Cooling On-Timer Operation Airflow Speed SelectionFuzzy Operation for Dehumidification Fuzzy Operation for HeatingOff-Timer Operation Off-Timer ↔ On-Timer OperationSleep Timer Operation Chaos Swing ModeJet Cool Mode Operation C/O Model Jet Cool Mode Operation H/P ModelAir Cleaner Operation Forced OperationProtection of the evaporator pipe from frosting Remote Control Operation ModeBuzzer Sounding Operation Display Function Self-diagnosis FunctionHeating Model Cooling ModelSelection of the best location InstallationPiping length and elevation How to fix installation plate Drill a hole in the wallFlaring work Connection of piping Indoor Indoor unit installationFor right rear piping Wrap the insulation material around the connecting portion Tighten the flare nut with a wrenchInsert the connecting cable into the indoor unit Tape the drain hose and the connecting cableAlign the center of the pipings and sufficiently Connection of the pipes-OutdoorTighten the flare nut by hand Connecting The Cable Between Indoor Unit and Outdoor Unit Connect the cable to the Indoor unitConnect the cable to the outdoor unit Checking the drainage Form the pipingTo remove the front panel from the indoor unit To check the drainagePrepare remote control Pump Down ProcedureSettlement of outdoor unit Evaluation of the performanceName and Function-Remote Control OperationON/OFF Timer Buttons Disassembly of the parts Indoor unit To remove the Grille from the ChassisWhen repair, do not damage the Caution label To remove the Control BoxTo remove the Discharge Grille To remove the EvaporatorTo remove the Motor Cover To remove the Cross-Flow FanWay, 3-way Valve Way Valve Liquid SideCheck for gas leakage ProcedurePurge the air from the system Air purging of the charge hose Set the 2-way valve to the closed positionRe-air purging Balance refrigerant of the 2-way, 3-way valves Gas leakageEvacuation All amount of refrigerant leakedConnect the charge hose to the charging cylinder After EvacuationPurge the air from the charge hose Cycle Troubleshooting Guide Trouble analysisElectronic Parts Troubleshooting Guide Product is not operate with the remote control Compressor/Outdoor Fan are unable to drive When indoor Fan does not operate When Vertical Louver does not operate When Heating does not operate Way RelayPage Electronic Control Device Main P.W.B Assembly DC Part TOP View Bottom View TOP View 6871A30009 TOP View 6871A20194 TOP View6871A20227 TOP View 6871A20390 TOP View 6871A20391 TOP ViewSchematic Diagram LED Type HVB Typeplasma Heat Pump Model LED Type Heat Pump Model HVB Type Exploded View and Replacement Parts List Parts ListIndoor LS-Q076ABL LS-Q076BBG LS-Q076BELLS-Q096ABL LS-Q096BBG CABLE, Flat CABLE, Falt Cover ASSEMBLY,MOTOR LS-Q082AAL LS-C082QMA0 LS-C082QNA0 LS-C096QGL0 LS-C096QLA0 LS-C096QNA0 LS-H096QGL1 W0CZZ Parts ListOutdoor 552202 567502 561410 554160 447910 550140 430410 552203-2 TUBE,CAPILLARY Bend Compressor Base ASSEMBLY,OUTDOOR Tube ASSY,CAPILLARY LS-C082QMA0 LS-C082QNAO LS-C096QGL0 3041AR2415K April