Error Code Table
| Code | Fault | Remedy | 
| 
 | 
 | 
 | 
| 14 | Thermal Fuse | Check gas type of unit and ensure it matches gas type being used. | 
| 
 | 
 | Check for restrictions in air flow around unit and vent terminal. | 
| 
 | 
 | Check for low water flow in a circulating system causing  | 
| 
 | 
 | Ensure dip switches are set to the proper position. | 
| 
 | 
 | Check for foreign materials in combustion chamber and/or exhaust piping. | 
| 
 | 
 | Check heat exchanger for cracks and/or separations. | 
| 
 | 
 | Check heat exchanger surface for hot spots which indicate blockage due to scale build- | 
| 
 | 
 | up. Refer to instructions in manual for flushing heat exchanger. | 
| 
 | 
 | Measure resistance of safety circuit. | 
| 
 | 
 | Ensure high fire and low fire manifold pressure is correct. | 
| 
 | 
 | Check for improper conversion of product. | 
| 16 | Over Temperature | Check for restrictions in air flow around unit and vent terminal. | 
| 
 | Warning | Check for low water flow in a circulating system causing  | 
| 
 | 
 | Check for foreign materials in combustion chamber and/or exhaust piping. | 
| 
 | 
 | Check for clogged heat exchanger. | 
| 32 | Outgoing Water | Check sensor wiring for damage. | 
| 
 | Temperature Sensor | Measure resistance of sensor. | 
| 
 | Fault | Clean sensor of scale  | 
| 
 | 
 | Replace sensor. | 
| 33 | Heat Exchanger | Check sensor wiring for damage. | 
| 
 | Outgoing Temperature | Measure resistance of sensor. | 
| 
 | Sensor Fault | Clean sensor of scale  | 
| 
 | 
 | Replace sensor. | 
| 34 | Combustion Air | Check for restrictions in air flow around unit and vent terminal. | 
| 
 | Temperature Sensor | Check sensor wiring for damage. | 
| 
 | Fault | Measure resistance of sensor. | 
| 
 | 
 | Clean sensor of scale  | 
| 
 | 
 | Ensure fan blade is tight on motor shaft and is in good condition. | 
| 
 | 
 | Replace sensor. | 
| 52 | Modulating Solenoid | Check modulating gas solenoid valve wiring harness for loose or damaged terminals. | 
| 
 | Valve Signal Abnormal | Measure resistance of valve coil. | 
| 61 | Combustion Fan | Ensure fan will turn freely. | 
| 
 | Failure | Check wiring harness to motor for damaged and/or loose connections. | 
| 
 | 
 | Measure resistance of motor winding. | 
| 71 | SV0, SV1, SV2, and | Check wiring harness to all solenoids for damage and/or loose connections. | 
| 
 | SV3 Solenoid Valve | Measure resistance of each solenoid valve coil. | 
| 
 | Circuit Fault | 
 | 
| 72 | Flame Sensing Device | Ensure flame rod is touching flame when unit fires. | 
| 
 | Fault | Check all wiring to flame rod for damage. | 
| 
 | 
 | Remove flame rod and check for carbon  | 
| 
 | 
 | Check inside burner chamber for any foreign material blocking flame at flame rod. | 
| 
 | 
 | Measure micro amp output of sensor circuit with flame present. | 
| 
 | 
 | Replace flame rod. | 
| LC | Scale  | Flush heat exchanger. Refer to instructions in manual. | 
| 
 | Exchanger (when | Replace heat exchanger. | 
| 
 | checking maintenance | 
 | 
| 
 | code history, “00” is | 
 | 
| 
 | substituted for “LC”) | 
 | 
| No | Nothing happens when | Clean inlet water supply filter. | 
| code | water flow is activated. | On new installations ensure hot and cold water lines are not reversed. | 
| 
 | 
 | Check for bleed over. Isolate unit from building by turning off hot water line to building. | 
| 
 | 
 | Isolate the circulating system if present. Open your pressure relief valve; if water is | 
| 
 | 
 | flowing, there is bleed over in your plumbing. | 
| 
 | 
 | Ensure you have at least the minimum flow rate required to fire unit. | 
| 
 | 
 | Ensure turbine spins freely. | 
| 
 | 
 | Measure the resistance of the water flow control sensor. | 
| 
 | 
 | Check for DC shorts at components. | 
| 
 | 
 | 
 | 