State Industries U287-084, 705 Series 200 installation manual Code

Page 10

Error Code Table

Code

Fault

Remedy

 

 

 

14

Thermal Fuse

Check gas type of unit and ensure it matches gas type being used.

 

 

Check for restrictions in air flow around unit and vent terminal.

 

 

Check for low water flow in a circulating system causing short-cycling.

 

 

Ensure dip switches are set to the proper position.

 

 

Check for foreign materials in combustion chamber and/or exhaust piping.

 

 

Check heat exchanger for cracks and/or separations.

 

 

Check heat exchanger surface for hot spots which indicate blockage due to scale build-

 

 

up. Refer to instructions in manual for flushing heat exchanger.

 

 

Measure resistance of safety circuit.

 

 

Ensure high fire and low fire manifold pressure is correct.

 

 

Check for improper conversion of product.

16

Over Temperature

Check for restrictions in air flow around unit and vent terminal.

 

Warning

Check for low water flow in a circulating system causing short-cycling.

 

 

Check for foreign materials in combustion chamber and/or exhaust piping.

 

 

Check for clogged heat exchanger.

32

Outgoing Water

Check sensor wiring for damage.

 

Temperature Sensor

Measure resistance of sensor.

 

Fault

Clean sensor of scale build-up.

 

 

Replace sensor.

33

Heat Exchanger

Check sensor wiring for damage.

 

Outgoing Temperature

Measure resistance of sensor.

 

Sensor Fault

Clean sensor of scale build-up.

 

 

Replace sensor.

34

Combustion Air

Check for restrictions in air flow around unit and vent terminal.

 

Temperature Sensor

Check sensor wiring for damage.

 

Fault

Measure resistance of sensor.

 

 

Clean sensor of scale build-up.

 

 

Ensure fan blade is tight on motor shaft and is in good condition.

 

 

Replace sensor.

52

Modulating Solenoid

Check modulating gas solenoid valve wiring harness for loose or damaged terminals.

 

Valve Signal Abnormal

Measure resistance of valve coil.

61

Combustion Fan

Ensure fan will turn freely.

 

Failure

Check wiring harness to motor for damaged and/or loose connections.

 

 

Measure resistance of motor winding.

71

SV0, SV1, SV2, and

Check wiring harness to all solenoids for damage and/or loose connections.

 

SV3 Solenoid Valve

Measure resistance of each solenoid valve coil.

 

Circuit Fault

 

72

Flame Sensing Device

Ensure flame rod is touching flame when unit fires.

 

Fault

Check all wiring to flame rod for damage.

 

 

Remove flame rod and check for carbon build-up; clean with sand paper.

 

 

Check inside burner chamber for any foreign material blocking flame at flame rod.

 

 

Measure micro amp output of sensor circuit with flame present.

 

 

Replace flame rod.

LC

Scale Build-up in Heat

Flush heat exchanger. Refer to instructions in manual.

 

Exchanger (when

Replace heat exchanger.

 

checking maintenance

 

 

code history, “00” is

 

 

substituted for “LC”)

 

No

Nothing happens when

Clean inlet water supply filter.

code

water flow is activated.

On new installations ensure hot and cold water lines are not reversed.

 

 

Check for bleed over. Isolate unit from building by turning off hot water line to building.

 

 

Isolate the circulating system if present. Open your pressure relief valve; if water is

 

 

flowing, there is bleed over in your plumbing.

 

 

Ensure you have at least the minimum flow rate required to fire unit.

 

 

Ensure turbine spins freely.

 

 

Measure the resistance of the water flow control sensor.

 

 

Check for DC shorts at components.

 

 

 

10

 

305, 505, 705 Indoor Manual

Image 10
Contents Models 305 505 705 ANS Z21.10.3 CSATable of Contents Specifications Model 305 505 705Safety Definitions Consumer Safety InformationSafety Behavior and Practices Safety Features Description of Operation Features Available on Temperature ControllersFeatures Operating InstructionsSetting the Temperature Temperature Options Without a Temperature ControllerModel Temperature Settings Available ºF Temperature RangesSetting Controller to Mute Re-setting the Maximum TemperatureMaintenance Error Code Table Error CodesCode Fault Remedy Code Accessing Operating Information Trouble Shooting for Common IssuesWater Quality Flushing the Heat Exchanger Error Code LC or Water HeaterInstallation Instructions General InstructionsClearances from Appliance Attachment of the Water HeaterGas Piping Electrical ConnectionGeneral Instructions Pipe Sizing Procedure Example Pressure Relief Valve Water PipingFreeze Protection Freeze Protection Piping Water HeaterRecommended Piping for Basic Installation QTYRecommended Piping for Circulation Systems For this applicationOptional Piping for Circulation Systems For this applicationIntake / Exhaust Guidelines Venting InstructionsCondensate Maximum Vent Length Listed and Tested Vent Products for the 705 Model Venting ProductsListed and Tested Vent Products for the 305 and 505 Models Manufacturer Product PartsVent Terminal Area Where Terminal is not Permittted Flue Terminal Clearances ANS Z21.10.3 CSAAdditional Clearances Vent Terminal Inside CornerFlue Installation for the 305 and 505 Models Exhaust Pipe Assembly Flue Installation for the 705 ModelAir Intake Assembly Venting Clearances to CombustiblesHorizontal with Concentric Termination Vertical TerminationsNumber of Connected Water Heaters Accessories Necessary High Altitude InstallationsConnecting Multiple Water Heaters GuidelinesLocation Temperature Controller InstallationConfigurations Cable Lengths and SizeMounting the Controller OutlineofofControllRem terFor Your Safety Read Before Operating Operating InstructionsPressure Drop Curve Technical DataOutlet Flow Data Space Heating Temperature SettingReplacement PumpsDimensions 505 ModelsLadder Diagram HOTWhat is covered? WarrantyWhat will be done? What is not covered? How do I get service?Limitation on implied warranties U287-084