State Industries 705 Series 200 Horizontal with Concentric Termination, Vertical Terminations

Page 29

Flue Installation for the 705 Model

Horizontal with Concentric Termination

SLOPE INTAKE AND EXHAUST

TOWARD OUTSIDE TERMINATION

MINIMUM 1/4" PER FOOT

12” MIN. ABOVE

GRADE OR

SNOW LEVEL

Vertical Terminations

The air intake requires a return bend or two 90º elbows to prevent entry of rain.

The vent termination and air intake must be in the same pressure zone.

3”

 

 

3”

MAX

 

 

 

 

MAX

 

 

 

 

12” MIN

 

12” MIN

 

 

 

12”

 

 

12” MIN

MIN

 

 

 

 

 

ANTICIPATED

3”

 

 

SNOW LEVEL

COMBUSTION

 

MAX

 

 

AIR PIPE

 

EXHAUST PIPE

 

 

 

 

12” MIN

 

3”

12” MIN

 

 

 

305, 505, 705 Indoor Manual

29

 

Image 29
Contents ANS Z21.10.3 CSA Models 305 505 705Table of Contents Model 305 505 705 SpecificationsSafety Behavior and Practices Safety Features Consumer Safety InformationSafety Definitions Features Features Available on Temperature ControllersDescription of Operation Operating InstructionsTemperature Options Without a Temperature Controller Setting the TemperatureSetting Controller to Mute Temperature RangesModel Temperature Settings Available ºF Re-setting the Maximum TemperatureMaintenance Code Fault Remedy Error CodesError Code Table Code Water Quality Trouble Shooting for Common IssuesAccessing Operating Information Water Heater Flushing the Heat Exchanger Error Code LC orGeneral Instructions Installation InstructionsAttachment of the Water Heater Clearances from ApplianceGeneral Instructions Electrical ConnectionGas Piping Pipe Sizing Procedure Example Freeze Protection Water PipingPressure Relief Valve Water Heater Freeze Protection PipingQTY Recommended Piping for Basic InstallationFor this application Recommended Piping for Circulation SystemsFor this application Optional Piping for Circulation SystemsCondensate Venting InstructionsIntake / Exhaust Guidelines Maximum Vent Length Listed and Tested Vent Products for the 305 and 505 Models Venting ProductsListed and Tested Vent Products for the 705 Model Manufacturer Product PartsFlue Terminal Clearances ANS Z21.10.3 CSA Vent Terminal Area Where Terminal is not PermitttedInside Corner Additional Clearances Vent TerminalFlue Installation for the 305 and 505 Models Air Intake Assembly Flue Installation for the 705 ModelExhaust Pipe Assembly Venting Clearances to CombustiblesVertical Terminations Horizontal with Concentric TerminationConnecting Multiple Water Heaters High Altitude InstallationsNumber of Connected Water Heaters Accessories Necessary GuidelinesConfigurations Temperature Controller InstallationLocation Cable Lengths and SizeOutlineofofControllRem ter Mounting the ControllerOperating Instructions For Your Safety Read Before OperatingOutlet Flow Data Technical DataPressure Drop Curve Replacement Temperature SettingSpace Heating Pumps505 Models DimensionsHOT Ladder DiagramWhat will be done? WarrantyWhat is covered? Limitation on implied warranties How do I get service?What is not covered? U287-084