Gas Piping

Pipe Sizing Procedure - Example

The gas supply must be capable of handling the entire gas load at the location. Gas line sizing is based on gas type, the pressure drop in the system, the gas pressure supplied, and gas line type. Refer to the National Fuel Gas Code, NFPA 54, for proper gas line sizing. The below information is provided as an example.

1.Determine the cubic feet per hour of gas required by dividing the gas input (on the rating plate) by the heating value of the gas (available from the local gas company). The gas input needs to include all gas products at the location and the maximum BTU usage at full load when all gas products are in use.

Gas Input of the water heater (BTU / HR)

Cubic Feet per Hour (CFH) =

Heating Value of Gas (BTU / FT 3 )

2.Use the table for your gas type to find the pipe size required for your cubic feet per hour of gas and your pipe length.

Example: The heating value of propane gas for your location is 2516 BTU / FT 3.

The gas input is 190,000 BTU/HR. Additional appliances at the location require 75,000 BTU/HR. Therefore the cubic feet per hour = (190,000+75,000) / 2516 = 105.3 FT 3/ HR.

If the pipe length is 100 ft then the 3/4 inch pipe size capable of supplying 197 FT 3/ HR of propane gas will be adequate.

Length

 

Pipe Size (inches)

 

3/4

1

1 1/4

1 1/2

 

10

273

514

1060

1580

20

188

353

726

1090

 

 

 

 

 

30

151

284

583

873

 

 

 

 

 

40

129

243

499

747

 

 

 

 

 

50

114

215

442

662

 

 

 

 

 

60

104

195

400

600

 

 

 

 

 

70

95

179

368

552

 

 

 

 

 

80

89

167

343

514

 

 

 

 

 

90

83

157

322

482

 

 

 

 

 

100

79

148

304

455

 

 

 

 

 

125

70

131

269

403

 

 

 

 

 

150

63

119

244

366

 

 

 

 

 

175

58

109

224

336

 

 

 

 

 

200

54

102

209

313

 

 

 

 

 

Length

 

Pipe Size (inches)

 

 

 

 

 

1/2

3/4

1

1 1/4

 

 

 

 

 

 

10

291

608

1150

2350

 

 

 

 

 

20

200

418

787

1620

 

 

 

 

 

30

160

336

632

1300

 

 

 

 

 

40

137

287

541

1110

 

 

 

 

 

50

122

255

480

985

 

 

 

 

 

60

110

231

434

892

 

 

 

 

 

80

101

212

400

821

 

 

 

 

 

100

94

197

372

763

 

 

 

 

 

125

89

185

349

716

 

 

 

 

 

150

84

175

330

677

 

 

 

 

 

175

74

155

292

600

 

 

 

 

 

200

67

140

265

543

 

 

 

 

 

16

305, 505, 705 Indoor Manual

Image 16
Contents Models 305 505 705 ANS Z21.10.3 CSATable of Contents Specifications Model 305 505 705Safety Definitions Consumer Safety InformationSafety Behavior and Practices Safety Features Features Available on Temperature Controllers FeaturesDescription of Operation Operating InstructionsSetting the Temperature Temperature Options Without a Temperature ControllerTemperature Ranges Setting Controller to MuteModel Temperature Settings Available ºF Re-setting the Maximum TemperatureMaintenance Error Code Table Error CodesCode Fault Remedy Code Accessing Operating Information Trouble Shooting for Common IssuesWater Quality Flushing the Heat Exchanger Error Code LC or Water HeaterInstallation Instructions General InstructionsClearances from Appliance Attachment of the Water HeaterGas Piping Electrical ConnectionGeneral Instructions Pipe Sizing Procedure Example Pressure Relief Valve Water PipingFreeze Protection Freeze Protection Piping Water HeaterRecommended Piping for Basic Installation QTYRecommended Piping for Circulation Systems For this applicationOptional Piping for Circulation Systems For this applicationIntake / Exhaust Guidelines Venting InstructionsCondensate Maximum Vent Length Venting Products Listed and Tested Vent Products for the 305 and 505 ModelsListed and Tested Vent Products for the 705 Model Manufacturer Product PartsVent Terminal Area Where Terminal is not Permittted Flue Terminal Clearances ANS Z21.10.3 CSAAdditional Clearances Vent Terminal Inside CornerFlue Installation for the 305 and 505 Models Flue Installation for the 705 Model Air Intake AssemblyExhaust Pipe Assembly Venting Clearances to CombustiblesHorizontal with Concentric Termination Vertical TerminationsHigh Altitude Installations Connecting Multiple Water HeatersNumber of Connected Water Heaters Accessories Necessary GuidelinesTemperature Controller Installation ConfigurationsLocation Cable Lengths and SizeMounting the Controller OutlineofofControllRem terFor Your Safety Read Before Operating Operating InstructionsPressure Drop Curve Technical DataOutlet Flow Data Temperature Setting ReplacementSpace Heating PumpsDimensions 505 ModelsLadder Diagram HOTWhat is covered? WarrantyWhat will be done? What is not covered? How do I get service?Limitation on implied warranties U287-084