State Industries U287-084 Flue Installation for the 705 Model, Air Intake Assembly

Page 28

Flue Installation for the 705 Model

Air Intake Assembly

The air intake system consists of a field supplied 4 inch diameter stainless steel, Schedule 40 PVC, ABS or CPVC pipe. A maximum 6 feet of semi-rigid flexible aluminum ducting can also be used. Foil wrapped dryer vent and cell core products are not authorized.

The air intake has a zero clearance to combustibles.

Air Intake Connection

1.Drill 2 small holes at the end of the air intake pipe. 2.Slide the pipe over the air intake terminal.

3.Using a level, ensure the pipe is straight up and down.

4.With self tapping screws, attach the pipe to the air intake terminal.

5.Apply a bead of silicone around the pipe and air intake terminal, ensuring an air tight connection.

12

34

Exhaust Pipe Assembly

Refer to the manufacturer’s installation instructions for the specific exhaust vent system.

Venting Clearances to Combustibles

 

Enclosed

Unenclosed

Vent Size

 

 

Horizontal &

Horizontal &

 

Vertical

Vertical

4" (102 mm)

4" (102 mm)

1" (26 mm)

 

 

 

Horizontal Terminations

The air intake must be located in relation to the exhaust as shown below. The air intake must angle 1/4 inch per foot to the termination to prevent entry of rain.

6

12”

 

Vent

4”

 

8

 

Optional

 

Intake

EXHAUST

Intake

COMBUSTION AIR /

INTAKE

The vent termination and air

12” MIN. ABOVE

intake must be in the same

pressure zone and face the

GRADE OR

same direction.

SNOW LEVEL

SLOPE INTAKE AND EXHAUST

TOWARD OUTSIDE TERMINATION

MINIMUM 1/4" PER FOOT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

305, 505, 705 Indoor Manual

 

Image 28
Contents Models 305 505 705 ANS Z21.10.3 CSATable of Contents Specifications Model 305 505 705Safety Definitions Consumer Safety InformationSafety Behavior and Practices Safety Features Features Available on Temperature Controllers FeaturesDescription of Operation Operating InstructionsSetting the Temperature Temperature Options Without a Temperature ControllerTemperature Ranges Setting Controller to MuteModel Temperature Settings Available ºF Re-setting the Maximum TemperatureMaintenance Error Code Table Error CodesCode Fault Remedy Code Accessing Operating Information Trouble Shooting for Common IssuesWater Quality Flushing the Heat Exchanger Error Code LC or Water HeaterInstallation Instructions General InstructionsClearances from Appliance Attachment of the Water HeaterGas Piping Electrical ConnectionGeneral Instructions Pipe Sizing Procedure Example Pressure Relief Valve Water PipingFreeze Protection Freeze Protection Piping Water HeaterRecommended Piping for Basic Installation QTYRecommended Piping for Circulation Systems For this applicationOptional Piping for Circulation Systems For this applicationIntake / Exhaust Guidelines Venting InstructionsCondensate Maximum Vent Length Venting Products Listed and Tested Vent Products for the 305 and 505 ModelsListed and Tested Vent Products for the 705 Model Manufacturer Product PartsVent Terminal Area Where Terminal is not Permittted Flue Terminal Clearances ANS Z21.10.3 CSAAdditional Clearances Vent Terminal Inside CornerFlue Installation for the 305 and 505 Models Flue Installation for the 705 Model Air Intake AssemblyExhaust Pipe Assembly Venting Clearances to CombustiblesHorizontal with Concentric Termination Vertical TerminationsHigh Altitude Installations Connecting Multiple Water HeatersNumber of Connected Water Heaters Accessories Necessary GuidelinesTemperature Controller Installation ConfigurationsLocation Cable Lengths and SizeMounting the Controller OutlineofofControllRem terFor Your Safety Read Before Operating Operating InstructionsPressure Drop Curve Technical DataOutlet Flow Data Temperature Setting ReplacementSpace Heating PumpsDimensions 505 ModelsLadder Diagram HOTWhat is covered? WarrantyWhat will be done? What is not covered? How do I get service?Limitation on implied warranties U287-084