State Industries 705 Series 200, U287-084 Water Piping, Pressure Relief Valve, Freeze Protection

Page 17

Water Piping

General Instructions

A manual water control valve must be placed in the water inlet connection to the water heater before it is connected to the water line. Unions may be used on both the hot and cold water lines for future servicing and disconnection of the unit.

The piping (including soldering materials) and components connected to this appliance must be approved for use in potable water systems.

Purge the water line to remove all debris and air. Debris will damage the water heater.

Pressure Relief Valve

An approved pressure relief valve is required by the American National Standard (ANSI Z21.10.3) / Canadian Standard (CSA 4.3) for all water heating systems.

The relief valve must comply with the standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems ANSI Z21.22 and /or the standard Temperature, Pressure, Temperature and Pressure Relief Valves and Vacuum Relief Valves, CAN1-4.4.

The relief valve must be rated up to 150 psi and to at least the maximum BTU/hr of the appliance.

The discharge from the pressure relief valve should be piped to the ground or into a drain system to prevent exposure or possible burn hazards to humans or other plant or animal life. Follow local codes. Water discharged from the relief valve could cause severe burns instantly, scalds, or death.

The pressure relief valve must be manually operated once a year to check for correct operation.

Toxic chemicals such as those used for boiler water treatment are not to be introduced to the potable water used for space heating.

If the appliance will be used as a potable water source, it must not be connected to a system that was previously used with a nonpotable water heating appliance.

Ensure that the water filter on the water heater is clean and installed.

The relief valve should be added to the hot water outlet line according to the manufacturer’s instructions. DO NOT place any other type valve or shut off device between the relief valve and the water heater.

Do not plug the relief valve and do not install any reducing fittings or other restrictions in the relief line. The relief line should allow for complete drainage of the valve and the line.

If a relief valve discharges periodically, this may be due to thermal expansion in a closed water supply system. Contact the water supplier or local plumbing inspector on how to correct this situation. Do not plug the relief valve.

Neither this water heater nor the American National Standard (ANSI Z21.10.3) / Canadian Standard (CSA 4.3) requires a combination temperature and pressure relief valve for this appliance. However, local codes may require a combination temperature and pressure relief valve.

Freeze Protection

The freeze protection features include electrical heating elements and intermittent firing of the burner. Freeze protection may be disabled if electricity or gas is not supplied, or if there is an error preventing the water heater from functioning. Loss of freeze protection may result in water damage from a burst heat exchanger or water lines.

The installation of auto drain down solenoid valves is optional. However, it is strongly recommended that these valves be installed to prevent damage from freezing in case the normal freeze protection should become disabled. Any product damage due to freezing will not be covered by the warranty.

In addition, the solenoid valves should be connected electrically to a surge protector with terminals that attaches to the PC board in the unit. This allows the solenoid valves to operate if the water heater is disabled due to an error code.

The solenoid valves and the surge protector with terminals are available for purchase separately.

305, 505, 705 Indoor Manual

17

Image 17
Contents ANS Z21.10.3 CSA Models 305 505 705Table of Contents Model 305 505 705 SpecificationsSafety Behavior and Practices Safety Features Consumer Safety InformationSafety Definitions Features Features Available on Temperature ControllersDescription of Operation Operating InstructionsTemperature Options Without a Temperature Controller Setting the TemperatureSetting Controller to Mute Temperature RangesModel Temperature Settings Available ºF Re-setting the Maximum TemperatureMaintenance Code Fault Remedy Error CodesError Code Table Code Water Quality Trouble Shooting for Common IssuesAccessing Operating Information Water Heater Flushing the Heat Exchanger Error Code LC orGeneral Instructions Installation InstructionsAttachment of the Water Heater Clearances from ApplianceGeneral Instructions Electrical ConnectionGas Piping Pipe Sizing Procedure Example Freeze Protection Water PipingPressure Relief Valve Water Heater Freeze Protection PipingQTY Recommended Piping for Basic InstallationFor this application Recommended Piping for Circulation SystemsFor this application Optional Piping for Circulation SystemsCondensate Venting InstructionsIntake / Exhaust Guidelines Maximum Vent Length Listed and Tested Vent Products for the 305 and 505 Models Venting ProductsListed and Tested Vent Products for the 705 Model Manufacturer Product PartsFlue Terminal Clearances ANS Z21.10.3 CSA Vent Terminal Area Where Terminal is not PermitttedInside Corner Additional Clearances Vent TerminalFlue Installation for the 305 and 505 Models Air Intake Assembly Flue Installation for the 705 ModelExhaust Pipe Assembly Venting Clearances to CombustiblesVertical Terminations Horizontal with Concentric TerminationConnecting Multiple Water Heaters High Altitude InstallationsNumber of Connected Water Heaters Accessories Necessary GuidelinesConfigurations Temperature Controller InstallationLocation Cable Lengths and SizeOutlineofofControllRem ter Mounting the ControllerOperating Instructions For Your Safety Read Before OperatingOutlet Flow Data Technical DataPressure Drop Curve Replacement Temperature SettingSpace Heating Pumps505 Models DimensionsHOT Ladder DiagramWhat will be done? WarrantyWhat is covered? Limitation on implied warranties How do I get service?What is not covered? U287-084