State Industries GS6, GSX, GPX manual Per Ft

Page 16

BASIC INSTALLATION & OPERATION

The connector must be firmly attached and sealed to prevent it from falling out.

To aid in removing the connector, a thimble or slip joint may be used.

The connector must not extend beyond the inner edge of the chimney as it may restrict the space between it and the opposite wall of the chimney

The following figures are examples of vent pipe system installations and may or may not be typical for your specific application. Consult the “National Fuel Gas Code”, NFPA 54, ANSI Z223.1-current edition and the guidelines set forth by prevailing local codes.

LOWEST DISCHARGE OPENING

LISTED VENT CAP

LISTED GAS VENT

LISTED LINED CHIMNEY

SUPPORT STRAP

12

x

 

2 FT. MINIMUM ABOVE ANY OBJECT

3 FT. MINIMUM

WITHIN 10FT. HORIZONTALLY

*MAINTAIN CLEARANCE

ROOF PITCH IS x/12

SUPPORT STRAP

H (MINIMUM) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING

MAINTAIN

TYPE B DOUBLE

CLEARANCE*

SEAL

DO NOT EXTEND VENT BEYOND EDGE OF CHIMNEY

VENT

WALL VENT PIPE

**MAINTAIN

SPECIFIED CLEARANCE

SLOPE

UP 1/4 IN.

PER FT.

MINIMUM

VENT CONNECTOR

CONNECTOR

SLOPE UP

1/4 IN. PER FT.

MINIMUM

VERTICAL GAS VENT SYSTEM WITH TYPE B DOUBLE WALL VENT PIPE.

CHIMNEY TERMINATION VENT SYSTEM

Figure 13

Do not reduce the vent to less than the draft hood outlet diameter. Do not terminate the vent connector in a chimney that has not been certified for this purpose. Some local codes may prohibit the termination of vent connectors in a masonry chimney.

Vertical Exhaust Gas Vent: Vertical exhaust gas vents must be installed with U.L. listed type B vent pipe according to the vent manufacturer’s instructions and the terms of its listing.

It must be connected to the water heater’s draft hood by a listed vent connector or by directly originating at the draft hood opening.

Vertical gas vents must terminate with a listed cap or other roof assembly and be installed according to their manufacturer’s instructions.

Gas vents must be supported to prevent damage, joint separation, and maintain clearances to combustible materials.

IMPORTANT: This gas vent must be terminated in a vertical position to facilitate the removal of the burnt gases.

An unused chimney flue or masonry enclosure may be used as a passageway for the installation of a gas vent. NOTE: The chimney flue or masonry enclosure size may be too large to allow proper venting.

Common (combined) venting is allowable with vertical type B vent systems and lined masonry chimneys as long as proper draft for the water heater is established under all conditions of operation. CAUTION: DO NOT common vent this water heater with any power vented appliance.

Figure 14

Consult the table found in the “National Fuel Gas Code”, NFPA 54, ANSI Z223.1-current edition to determine the minimum height from roof to lowest discharge opening.

 

 

LISTED VENT CAP

MAINTAIN MANUFACTURER’S

 

SPECIFIED MINIMUM CLEARANCE

**MAINTAIN

 

 

 

 

SPECIFIED

 

 

CLEARANCE

SUPPORT

 

 

STRAP

 

 

*MAINTAIN

 

 

CLEARANCE

SEAL

 

 

 

VENT

 

VENT CONNECTOR

CONNECTOR

 

UNUSED CHIMNEY

SLOPE UP

 

 

FLUE OR MASONRY

1/4 IN. PER FT.

 

 

ENCLOSURE

MINIMUM

 

 

 

VENTING THROUGH A CHIMNEY WITH

TYPE B DOUBLE WALL VENT PIPE.

Figure 15

*Maintain vent pipe clearance requirements to local, state and/or the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition.

**NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances states that these chimneys are intended to be installed in accordance with the installation instructions provided with each chimney support assembly. Minimum air space clearance to combustible materials should be maintained as marked on the chimney sections.

16

Image 16 Contents
Models GPX, GS6, GSX Series 200/201 06/09 316876-000Page Service Handbook Tools Required for servicing gas modelsFire or Explosion Harzard Insufficient HOT Water No HOT WaterWater Leakage Problem Possible Cause Test / Corrective Action Table of Contents Basic Installation & Operation See Labels and Installation InstructionsWater Supply- Cold Use & Care Guide for clearances To Fixtures HotTemperature-Pressure Anode RodHot Water Cold WaterNormal Operation Thermal Cut Off Switch TCO The water heater Basic Installation & Operation Combustion Air Requirements Carbon Monoxide WarningReference Vent Connectors PER FT Draining and Filling the Water Heater Draining the Water Heater Filling the Water HeaterChecking the GAS Supply Pressure Checking for Sufficient Combustion AIR or Venting IssuesThen Draft Test Testing the Thermocouple and GAS Control VALVE/THERMOSTAT Thermal Switch ModelsRemoving the Burner from the Manifold/ Burner Assembly Removing the Manifold/Burner AssemblyReplacing the Thermocouple Replacing the Thermocouple and GAS Control VALVE/THERMOSTAT Replacing the Manifold/Burner AssemblyExplosion Hazard Removing the Gas Valve Removing and Replacing the Gas Control Valve/ThermostatReplacing the Gas Valve Water Time to Produce 2nd & 3rd GAS Water Heater Sizing Guide Leakage CheckpointsTechnical Bulletins 35-36Water Hammer GeneralEffects FIXMineral BUILD-UP SymptomsCause If tank is new with no lime build-up to any degree Aluminum HydroxideIf tank is new with lime build-up to any degree Causes CondensationDiagnosis Discolored Water TreatmentSmelly Water Procedure Chlorination ProcedureStep Test Not Enough HOT Water GASResults Thermal Expansion Outlet Inlet Cold Water Inlet Valve SHUT-OFF Valve Leaking Temperature and Pressure Relief Valve Insulation Blankets General Information Formulas and ConversionsMM millimeters =Inches X Page Page