State Industries GS6, GSX, GPX manual Leaking Temperature and Pressure Relief Valve, General

Page 37

BULLETIN 52

LEAKING TEMPERATURE AND PRESSURE RELIEF VALVE

SYMPTOMS

Water seeping around the relief valve tank connection

Leakage at the threaded portion of the relief valve connection

Intermittent weeping and/or dribbling from the relief valve

Large volume of hot water sporadically discharged from the relief valve

GENERAL

The temperature and pressure relief valve (T & P) is a safety device limiting temperature and pressure levels in a water heater. Each T & P has both a temperature and pressure rating.

Normally, the temperature and pressure relief valve will have a temperature rating of 210°F. A probe (part of the relief valve) extends into the tank measuring the stored water temperature. This probe must be within the top six inches of the water heater. If the water heater’s thermostat malfunctions, higher than normal water temperatures could be produced. Once the probe senses a temperature approaching its temperature rating, the relief valve will open to full capacity releasing “very hot” water until the temperature is below its reset temperature.

The pressure rating on the relief valve should be the same or less than the certified working pressure of the tank (generally 150 psi) and be below the lowest maximum working pressure rating of any system components. Once the pressure in the tank reaches the valve’s pressure rating, it will slightly open relieving the pressure. Relieving of pressure can be noted as “dribbling” or “weeping” water from the relief valve.

If an incorrectly sized temperature and pressure relief valve is installed, the warranty will be void.

THE FIX

Follow these easy steps to diagnose thermal expansion:

Intermittent weeping and/or dribbling at the relief valve - The relief valve relieves water slowly when actuating on pressure. A closed system can cause pressure to increase in the system. This condition is called thermal expansion. For additional information regarding thermal expansion please see Bulletin 45.

Leaking at the spud of the water heater - Spuds are welded to the tank and are not repairable. The heater should be replaced.

Leakage at the threaded relief valve connection - Remove relief valve and reseal connection.

Large volume of hot water sporadically discharged from the relief valve - The relief valve relieves water quickly when actuating on temperature. The only cause of this problem is a malfunctioning thermostat.

37

Image 37 Contents
06/09 316876-000 Models GPX, GS6, GSX Series 200/201Page Tools Required for servicing gas models Service HandbookFire or Explosion Harzard Insufficient HOT Water No HOT WaterWater Leakage Problem Possible Cause Test / Corrective Action Table of Contents See Labels and Installation Instructions Basic Installation & OperationWater Supply- Cold Use & Care Guide for clearances To Fixtures HotAnode Rod Temperature-PressureHot Water Cold WaterNormal Operation Thermal Cut Off Switch TCO The water heater Basic Installation & Operation Carbon Monoxide Warning Combustion Air RequirementsReference Vent Connectors PER FT Draining the Water Heater Filling the Water Heater Draining and Filling the Water HeaterChecking the GAS Supply Pressure Checking for Sufficient Combustion AIR or Venting IssuesThen Draft Test Thermal Switch Models Testing the Thermocouple and GAS Control VALVE/THERMOSTATRemoving the Burner from the Manifold/ Burner Assembly Removing the Manifold/Burner AssemblyReplacing the Thermocouple Replacing the Thermocouple and GAS Control VALVE/THERMOSTAT Replacing the Manifold/Burner AssemblyExplosion Hazard Removing the Gas Valve Removing and Replacing the Gas Control Valve/ThermostatReplacing the Gas Valve Water Time to Produce 2nd & 3rd Leakage Checkpoints GAS Water Heater Sizing Guide35-36 Technical BulletinsGeneral Water HammerEffects FIXMineral BUILD-UP SymptomsCause If tank is new with no lime build-up to any degree Aluminum HydroxideIf tank is new with lime build-up to any degree Causes CondensationDiagnosis Treatment Discolored WaterSmelly Water Procedure Chlorination Procedure Step Test Not Enough HOT Water GASResults Thermal Expansion Outlet Inlet Cold Water Inlet Valve SHUT-OFF Valve Leaking Temperature and Pressure Relief Valve Insulation Blankets Formulas and Conversions General InformationMM millimeters =Inches X Page Page