CHECKING FOR SUFFICIENT COMBUSTION AIR OR VENTING ISSUES

Draft Test

After successfully lighting the water heater, allow the unit to operate for 15 minutes and check the draft hood relief opening for proper draft. Make sure all other appliances in the area are operating and all doors/windows are closed when performing the draft test. Pass a match flame or smoke around the relief opening of the draft hood. A steady flame or smoke drawn into the opening indicates proper draft.

If the flame flutters or is blown out, combustion products are escaping from the relief opening. If this occurs, do not operate the water heater until proper adjustments or repairs are made to the vent pipe system and/or air supply requirements.

Flue Products Vented to Ouside of Building

Dilution Air

Dilution Air

Draft Hood

Match

Dilution Air

(Relief Opening)

Outer Door

Air is drawn in for combustion. Keep area clean and free from combustibles and flammable vapors.

Figure 18

External Inspection & Cleaning of the Base-Ring Filter

1.At least annually check the base-ring filter for any dust or debris that may have accumulated on the filter screen. NOTE: If the water heater is located in an area that is subjected to lint and dirt, it may be necessary to check the base-ring filter more frequently.

2.Follow the Lighting Instructions to turn off the water heater and allow it to cool for 10 minutes before attempting to clean the base-ring filter.

3.Use a vacuum cleaner with a hose attachment to remove any dust or debris that may have accumulated on the filter. NOTE: If unable to inspect or clean the base-ring filter, follow the “Cleaning the Combustion Chamber and Flame- arrestor” instructions below.

4.After the base-ring filter has been cleaned, follow the Lighting Instructions to return the water heater to service.

Cleaning the Combustion Chamber and Flame-arrestor

1.Follow procedure outlined in “Removing the Manifold/Burner Assembly” (See page 22).

2.Use a vacuum cleaner/shop vac to remove all loose debris in the combustion chamber. Use compressed air to clear any dust or debris that may have accumulated in the flame-arrestor.

COMBUSTION CHAMBER

FLAME ARRESTOR

DOOR GASKET

BASE-RING

FILTER

Figure 19

3.Reassemble following the procedure under “Replacing the Manifold/Burner Assembly” (See page 21).

19

Image 19 Contents
06/09 316876-000 Models GPX, GS6, GSX Series 200/201Page Tools Required for servicing gas models Service HandbookFire or Explosion Harzard Insufficient HOT Water No HOT WaterWater Leakage Problem Possible Cause Test / Corrective Action Table of Contents To Fixtures Hot Basic Installation & OperationSee Labels and Installation Instructions Water Supply- Cold Use & Care Guide for clearancesCold Water Temperature-PressureAnode Rod Hot WaterNormal Operation Thermal Cut Off Switch TCO The water heater Basic Installation & Operation Carbon Monoxide Warning Combustion Air RequirementsReference Vent Connectors PER FT Draining the Water Heater Filling the Water Heater Draining and Filling the Water HeaterChecking the GAS Supply Pressure Checking for Sufficient Combustion AIR or Venting IssuesThen Draft Test Thermal Switch Models Testing the Thermocouple and GAS Control VALVE/THERMOSTATRemoving the Burner from the Manifold/ Burner Assembly Removing the Manifold/Burner AssemblyReplacing the Thermocouple Replacing the Thermocouple and GAS Control VALVE/THERMOSTAT Replacing the Manifold/Burner AssemblyExplosion Hazard Removing the Gas Valve Removing and Replacing the Gas Control Valve/ThermostatReplacing the Gas Valve Water Time to Produce 2nd & 3rd Leakage Checkpoints GAS Water Heater Sizing Guide35-36 Technical BulletinsFIX Water HammerGeneral EffectsMineral BUILD-UP SymptomsCause If tank is new with no lime build-up to any degree Aluminum HydroxideIf tank is new with lime build-up to any degree Causes CondensationDiagnosis Treatment Discolored WaterSmelly Water Procedure Chlorination ProcedureStep Test Not Enough HOT Water GASResults Thermal Expansion Outlet Inlet Cold Water Inlet Valve SHUT-OFF Valve Leaking Temperature and Pressure Relief Valve Insulation Blankets Formulas and Conversions General InformationMM millimeters =Inches X Page Page