A familiarity with the UPS parameter settings is required if changing the Battery pack quantity as when using the External Battery Cabinets.

Connect the input cable to the UPS and connect the other end to a grounded outlet. The batteries will charge automatically when connected to the main supply.

The UPS may be used immediately to power a load. However, the maximum battery back-up time will not be available until the recommended 8-hour minimum charge time has completed.

If a Site Wiring Fault is displayed, rotate the connector.

After charging the UPS, connect the load to the UPS.

Do not connect any devices to the UPS that may cause overloading of the UPS or that draws half-wave rectified current, such as hair dryers or vacuum cleaners.

See section 6 Computer and Alarm Connections if computer or alarm (rear panel) connections are used.

The installation is now complete.

Figure 2 Example of Installation of Plug & Play products.

2400 VA

The 2400 VA UPS input and output power is hardwired to the power terminals. The output of the UPS can be adjusted according to which output terminals are selected. See 2400VA Power Wiring Options, page 11.