8. Maintenance
With a minimal amount of maintenance you can expect years of satisfactory operation
from the UPS unit. The most critical issues for the reliability of the UPS are
environmental issues. Ensure that the te mperature and humidity are always in
accordance with the specifications and keep the area around the unit clean and dust free.
The typical battery lifetime is 4 years when operated at 77° (25 °C).
Check the back-up time capability of the UPS/battery at 6 to 12 month intervals to
ensure adequate support for the application.
8.1 Battery Servicing
Servicing of batteries should be performed or supervised by personnel knowledgeable
about batteries and the required precautions. See IMPORTANT SAFETY
INSTRUCTIONS Qualified Personnel.
CAUTIONWhen replacing batteries, replace with the same type and number of
batteries.
Battery Type: Lead-Acid Type
Battery Rating: Total DC 72V, 96 Ah. (6 Pcs Battery/SET, 2 SET)
Replacement batteries available:
Manufacturer
Type
Rating
TAIWAN YUASA BATTERY CO LTD
(MH28947)
REW45-12 12 Vdc, 8.0 Ah
REW45-12FR
12 Vdc, 8.0 Ah