9.4Power Range 1000-3000 VA (230 V)
Tower | International | UT1E1E010C6 | UT1E1E015C6 |
| UT1E1E020C6 | UT1E1E030C6 |
| 230V Model |
|
|
|
|
|
Rack- | International | UT1E1E010C6 | UT1E1E015C6 |
| UT1E1E020C6 | UT1E1E030C6RKB |
mount (2U) | 230V Model | RKB2 | RKB2 |
| RKB2 | 2 |
Input | Voltage |
| 230 VAC | (161 – 276 V) |
| |
| (International) |
|
|
|
|
|
| Voltage Range |
| +20% to |
| ||
| (International) |
|
|
|
|
|
| Frequency |
| 50 / 60 Hz auto sensing |
| ||
| Power Factor |
| Greater than 0.97 |
| ||
| Topology | True | ||||
Output | Voltage |
|
| 230 VAC |
| |
| (International) |
|
|
|
|
|
| Capacity (VA) | 1000 VA | 1500 VA |
| 2000 VA | 3000 VA |
| Capacity (W) | 700 W | 1050 W |
| 1400 W | 2100 W |
| Frequency |
| 50 / 60 Hz auto | sensing* |
| |
| Wave Form |
| Sine wave, zero transfer time |
| ||
| Load Power |
|
| 0.7 |
| |
| Factor |
|
|
|
|
|
| Efficiency |
| Greater than 86% | Greater than 85% | ||
| AC/DC/AC |
|
|
|
|
|
| Rated Current | 4.3 A | 6.5 A |
| 13 A | 13 A |
| (International) |
|
|
|
|
|
| Overload | 125% | for 1 min., 150% for | 10 sec. | 125% for 1 min., | |
| Capacity |
|
|
|
| 130% for 10 sec. |
| Crest Factor |
| 3.0 at full load |
|
| 2.5 at full load |
Battery | DC Voltage | 36 V / 12 V |
| 72V | / 12 V | |
| (Tower & 2U) | 9 AH x 3 |
| 9 AH x 6 | ||
| Backup Time | 7 min | 6 min |
| 5 min | 5 min |
| (Tower & 2U) | (full load) | (full load) |
| (full load) | (full load) |
| Interface | RemotEye II® and | EMD option | |||
Physical | Dimensions | 16.5”L x 6.0”W x 9.4”H |
| 16.7" L x 8.9" W | 16.7" L x 8.9" W x | |
| (Tower) |
|
|
| x 14.2" H | 14.2" H |
| Dimensions | 16.7”L x 16.9”W x 3.5”H |
| 25.0"L x 16.9"W | 25.0"L x 16.9"W x | |
| (2U) |
|
|
| x 3.5"H" | 3.5"H" |
| Weight | 35.6 lbs / | 37.4 lbs / |
| 68.4 lbs / | 72.6 lbs / 71.5 lbs |
| (Tower/2U) | 37.6 lbs | 37.6 lbs |
| 69.5 lbs |
|
| Line Cord |
|
| IEC 320 |
| |
| (International) |
|
|
|
|
|
| Receptacles | IEC 320 (4 / 4) | IEC 320 (8 / 4) | IEC 320 (8 / 4) | ||
| (Tower/2U) |
|
|
|
|
|
| International |
|
|
|
|
|
Environ- | Operating |
| 32 – 104°F (0 – 40°C) |
| ||
ment | Temperature |
|
|
|
|
|
| Altitude |
| 11,500 ft (3500 m) above sea level |
| ||
Warranty |
| Three years on electronics |
|
|
| |
|
| Two years full replacement on battery (See Toshiba warranty policy for full details.) | ||||
|
|
|
|
|
|
|
Output frequency can hard set at 50 or 60 Hz by installing an optional software upgrade. This upgrade enables the user to select a fixed output frequency and simultaneously disables the bypass mode.
Standards - Safety: EN
33