31
9.3 Power Range 6000 VA (208/240 V)
1000 Series 6kVA Specification
Specification
Rackmount
US 208/240V
UT1G1G060C6RKB3 + UT1-BR-0607
General Topology
True on-line, Double conversion, IGBT Power Factor Correction
Input
Certifications
CE
Input
Voltage (V)
Single Phase - 208/240Vin
Capacity (VA)
6kVA
Frequency
45-65 Hz auto sensing
Frequency Synchronization
± 3Hz
Power Factor
Greater than 0.97
Current THD
Less than 15%
Cold Start (0 to 100% load)
Default Output Frequenc y 60 Hz
Earth leakage (max.)
2mA (UPS only)
Bypass
Voltage (V)
+10/-15% of nominal (default)
+10/-10% of nominal
+15/-20% of nominal
Set by display panel
Output
Voltage
208V or 240V
Voltage Regulations
± 3%
Capacity (W)
4.2kW
Frequency
50 / 60 Hz auto sensing
Battery Mode/Free Run Mode
± 0.25 Hz
Wave Form
Sine wave, zero transfer time
Load Power Factor
0.7 PF
Efficiency AC/DC/AC
Greater than 89% at Nominal Voltage
High Efficiency Mode Efficiency
Greater than 92%
Rated Current (based on 240V)
25.0
Inverter Overload Capacity
125% for 1 min, 150% for 10 sec
Crest Factor
3.0 at full load
Voltage Transient Res p onse
(battery mode with R type load)
0%100%0%; ± 15 % max.
20%100%20%; ± 9 % max.
Voltage Transient Reco very (R
type Load)
Return to nominal voltage within 30 ms
On-line Transfer Time Inverter to
Bypass and Bypass to Inverter
Less than 4m sec
High Efficiency Transfer T ime
Inverter to Bypass and Bypass to
Inverter
Less than 4m sec transfer time
Short Circuit Protection
Electronic overload and short circuit.
Voltage Total Harmon ic Distortion
(Full Linear Load)
Less than 3 % THD
Voltage Total Harmon ic Distortion
(Full Non-Linear Load)
Less than 5 % THD
Steady State Output Voltage
Regulation
No-load to Full-load +/- 2% at full battery.
Common Mode Noise
less than 0.5Vrms
Leakage Current
.5mA
Surge Protection
MOV 260 Jules on Output