9.5Backup Time at Partial Loads

Below is the estimated backup time at various fractions of full load for each 1000 Series model. This table assumes the batteries are fresh and begin with a .full initial charge

Load

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

1000 VA Backup (min)

150

56

38

30

23

19

15

12

10

7

1500 VA Backup (min)

80

37

21

19

18

15

13

11

8

6

2000 VA Backup (min)

150

68

38

26

19

14

11

9

7

6

2400 VA Backup (min)

200

76

53

42

33

28

22

18

15

11

3000 VA Backup (min)

80

40

25

19

15

12

9

8

6

5

6000 VA Backup (min)

45

36

29

22

18

15

13

11

9

7

Table 9.1 – Backup Time vs. Partial Load

34

Page 59
Image 59
Toshiba 1000 user manual Backup Time at Partial Loads