36
LIMITATIONS AND EXCLUSIONS 1. This limited warranty shall not cover the UPS, UPS parts, or BATTERY during their respective warranty periods, if the following storage, maintenance, installation, operating conditions are not met throughout the warranty periods (5 conditions below):
Valve Regulated Lead Acid (VRLA) Batteries for T oshiba UPS Re quire d O per ating, Installation, and
Maintenance Conditions
1. Temperature
Annual Average Temperature is to be 77°F (25 °C) with no greater
temperature of 89
°
F (32
°
C) for more than 30 days
2. Maximum # of Full
Charge/Discharge
Cycles
Maximum Number of Cycles (24 Months)***
Discharge Time
Battery > 9 AHr
Battery < 9 AHr
30 min
20
69
15 min
25
86
10 min
32
110
5 min
38
130
*** > 9AHr Typically extended runtimes < 9AHr Typically Single Phase
Systems.
3. Storage
While UPS is in Transit or in storage, it must always be in a suitable
temperature (as stated above)
4. External Battery
Parallel battery string applications must be approved by TIC in writing
5. Idle Batteries
User must recharge the batteries if not in use (c harged) for more than 6
months
2. This Warranty does not cover damage or defect caused by misus e, improper applicati on, wrong or
inadequate electrical current/voltage/ frequency, inadequate conn ections, inadequate water or d rain
services, user negligence, repair by non-Toshiba designa ted personnel, accident during shipment,
tampering, alterations, a change in UPS and/or BATTER Y location or application, exposure t o the
elements, acts of God, force nature, theft, sabotage, installation contrary to TIC's recommendations or
specifications (Published Operation Manuals), also if serial numbers have been altered, defaced, or
removed.
Credit for Replacement Battery When Approved Warranty
Time from Shipments
Cost to Customer
Months
% List Price
0-24
0
25-30
45
31-36
55
37-42
65
43-48
75
49-54
85
55-60
95