9.2Power Range 2400 VA (208/240 V)
Tower | US 208/240 Model | UT1G2L024C6T |
Input | Voltage | 208 or 240 VAC (161 – 276 V) |
| Voltage Range | +15% to |
| Frequency | 50 / 60 Hz auto sensing |
| Power Factor | Greater than 0.97 |
| Topology | True |
Output | Voltage | 120/208/240 VAC |
| Capacity (VA) | 2400 VA |
| Capacity (W) | 1920 W |
| Frequency | 50 / 60 |
| Wave Form | Sine wave, zero transfer time |
| Load Power Factor | 0.8 |
| Efficiency | Greater than 87% |
| AC/DC/AC |
|
| Rated Current | 10 A @ 240V |
| Overload Capacity | 125% for 1 min 130% for 10 sec |
| Crest Factor | 3.0 at full load |
Battery | DC Voltage | 72V / 12 V (9 AH x 6) |
| Backup Time | 11 min (full load) |
| Interface | |
Physical | Dimensions | 23.2”L x 10.1”W x 27.6”H |
| Weight | 154.3 lbs |
| Line Cord | None (Hardwired) |
| Receptacles | None (Hardwired) |
Environmen | Operating | 32 – 104°F (0 – 40°C) |
t | Temperature |
|
| Altitude | 3300 ft (1000 m) above sea level |
Warranty |
| Three years on electronics |
|
| Two years full replacement on battery (See Toshiba warranty policy for |
|
| full details.) |
•Output frequency can hard set at 50 or 60 Hz by installing an optional software upgrade. This upgrade enables the user to select a fixed output frequency and simultaneously disables the bypass mode.
Standards – FCC Part 15 Class A
Safety – EN
30