3. Storage

Please adhere to the following instructions if the UPS is not installed when received:

Store the equipment in its original packing and shipping carton.

Store the unit in a temperature of 59 – 77 °F (15 – 25 °C).

Ensure that the equipment is fully protected from wet or damp areas and from moist air.

In order to maintain the vitality of the batteries, ensure that the UPS is recharged every 6 months for at least 8 hours during storage.

4. Shipping

The cold start function must be disabled before the UPS is shipped. Cold start applies power to the UPS output with no UPS input. This can pose a shock or fire hazard if the output terminals are shorted. Toshiba is not responsible for any resultant fire or damage if the cold start function is not disabled.

Cold Start Disable Procedure (1000/1500/2000/2400/3000/6000 VA):

1.Ensure the UPS is switched OFF.

2.Plug In AC Power.

3.For 1/1.5/2/3/6kVA UPS: Press and hold the Function Key while pressing the “Enter” key 3 times.

For 2.4kVA UPS: Press and hold the Function Key while pressing the “Status” key 3 times.

4.After a beep sounds, unplug the AC power cord and wait for UPS to shutdown automatically.

**Note: Cold start will be automatically re-enabled when the UPS is plugged into commercial power and switched ON.