5.5Front Panel Settings

Listed below are the default settings of the primary UPS parameters.

Settings

Options

Default

Remarks

1) O/P VOLT SET

100/110/115/120/127

120 V

120 V (FOR LV series)

(output voltage

208/220/230/240 Vac

230 V

230 V (FOR HV series)

set)

 

 

 

 

 

 

 

2) I/P FREQ SET

+/- 2%

+/- 5%

Input Frequency range in

(input frequency

+/- 5%

 

Free Run mode

setting)

+/- 7%

 

 

3) I/P BYPASS

+/- 10%

+10%

Input Voltage range when

SET

+10% -15%

-15%

Bypass mode is on

(input bypass

+15% -20%

 

 

setting)

 

 

 

4) FREE RUN

ON/OFF

ON

If ON, enable UPS runs on

SET

 

 

Asynchronous mode.

 

 

 

For example:

 

 

 

If input freq 55Hz

 

 

 

output freq stays at 60Hz.

 

 

 

If OFF, disable UPS runs on

 

 

 

synchronous mode.

 

 

 

For example:

 

 

 

If input freq 55Hz,

 

 

 

UPS will go to battery mode.

5) HE MODE SET

ON/OFF

OFF

If ON, enable UPS runs in

 

 

 

High efficiency mode. The

 

 

 

unit will be in bypass mode

 

 

 

with 95% or higher

 

 

 

efficiency.

 

 

 

If OFF, the unit will be in the

 

 

 

online mode with 85%

 

 

 

efficiency.

6) MANUAL

ON/OFF

OFF

If ON, enable UPS switch to

BYPASS

 

 

Bypass mode immediately.

 

 

 

 