Battery | Acceptable manufacturer | Yuasa Taiwan only |
| Type / Rating | 9AH/12V Valve Regulated Lead Acid, Flame Retardant |
| 7 minutes | |
| degree C) (min) | |
|
| |
| Battery Bus Voltage (VDC) | 240 |
| Number of Batteries | 20 |
| Recharge | 4 hours to 90% for all ratings |
| Battery Mode Voltage Regulation | ±3% RMS for entire battery voltage range and 0 to 100% load |
| Battery Leakage | 100 mA maximum |
| Battery Test | Automatic and Manual |
| Replaceable Batteries | Not |
| Battery Protection | Fuse |
| 2 minutes | |
| Battery Level @ Shutdown | 1.67 VPC, ± 3% of battery voltage at FL with level automatically |
| raised for lighter loading | |
|
| |
| Overcharge Protection | 2.50 VPC, ± 3% of battery voltage |
|
| Maintains proper float voltage per battery specification over a |
| Temperature Compensated Charger | temperature range of 10 to 40 degree C (2.3V/cell at 25 degree C |
| with a temperature coefficient of minus 5 millivolts per degree | |
|
| |
|
| C) |
| Voltage Level | 2.25 minimum, 2.275 nominal, 2.30V maximum voltage of |
| battery voltage | |
|
| |
| Protection against Batteries Deep |
|
| Discharge |
|
Environment | Operating Temperature | 0 - 40oC (32 - 104oF) |
| Storage Temperature | |
| Operating Humidity | |
| Altitude | 11500 ft (3500 m) above sea level |
| Acoustical Noise | 50dB(A) maximum at 1 meter from Front Panel |
| Heat Generation (BTU/Hour) | 2234BTU/Hour |
Mechanical | Dimensions (Rackmount) LxWxH | 16.8 in. x23.5 in. x10.5 in. (427 mm x 597mm x 267mm) |
| Weight (Rackmount) | 148lbs (67.1 kg) |
| Line Cord | Terminal Block with |
| Receptacles | (2) |
| Enclosure | Enclosure of unit made from sheet metal meets NEMA 1 and UL |
| Type 1 Standard | |
|
| |
| Paint System | Black Color |
| Front Panel | 1000 Series Panel |
| Connectors/Options | EPO |
|
| Battery Connectors |
|
| Option card Slot (Network and Dry Contact) |
| Buzzer Volume | Mute/Unmute |
Warranty |
| Three years on electronics |
|
| Two years full replacement on battery (See Toshiba warranty |
|
| policy for full details.) |
•Output frequency can hard set at 50 or 60 Hz by installing an optional software upgrade. This upgrade enables the user
to select a fixed output frequency and simultaneously disables the bypass mode. Standards – FCC Part 15 Class A
Safety – EN
32