15
6000 VA
The 6000 VA UPS comes in two sections, a Power Module and the Battery Pack. Each
unit is RM-3U tall. The input power is hardwired to the UPS power input ter minals.
The UPS accepts either 208V or 240V input. The UPS autosenses the input voltage and
provides the corresponding output voltage (208V or 240V). The UPS provides two
L6-30R receptacles.
Ensure that the UPS Main Circuit Breaker is open, and the UPS loads are
disconnected while connecting the External Battery Cabinet/s.
Use the battery cable supplied with the External Battery Cabinet to connect the
External Battery Cabinet to the UPS. If more than one battery cabinet is required,
use the supplied cable. The batteries will charge automatically when connected to
the main supply.
NOTE: The UPS may be used immediately to power a load. However, the
maximum battery back-up time will not be available until the recommended 8-hour
minimum charge time has completed.
After charging the UPS, connect the load to the UPS.